Plan Review Stops For Permit 03080861 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2004-01-17 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-01-22 |
Time |
10:56 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2004-01-17 |
Time |
18:33 |
Sent To |
Z |
|
Notes |
2004-01-17 00:00:00 | ***PROVISO**** | | APPLY FOR AN A/C PERMIT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2003-12-17 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-12 |
Time |
16:17 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2003-12-17 |
Time |
18:56 |
Sent To |
Z |
|
Notes |
2003-12-17 00:00:00 | *****CORRECTIONS****** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)SEPARATE PERMITS REQUIRED. | | | | 2.)ADDITIONAL FEES DUE, $43.06, | | BZ WAS IN PACKAGE BUT IS NOW GONE. | | | | 3.)A NOTICE OF COMMENCMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 4.)SEE PREVIOUS LISTS, 3RD TIME ON | | THIS CORRECTION, PROVIDE WIND | | INFORMATION ON THE PLAN FBC1606.1.7 | | INCLUDING COMPONENTS AND CLADDING | | (DESIGN PRESSURE FOR DOORS). | | | | 5.)SEE PREVIOUS LISTS, 3RD TIME ON | | THIS CORRECTION, MTSM16 NAILING | | CONFLICTS WITH CATALOG.ADDRESS. | | | | 6.)SEE PREVIOUS LISTS, 3RD TIME, | | REGARDING PLYWOOD SOFFIT AND CEILING, | | FBC2303.3. | | | | 7.)SEE PREVIOUS LISTS IN REGARDS | | TO LSTA18, NAILING CONFLICTS WITH | | CATALOG.3RD TIME | | | | 8.)THE ROOM DESIGNATION FOR EXISTING | | ROOMS WAS REMOVED ON THE NEW DRAWING. | | THE ROOM LEADING FROM THE HOUSE TO THE | | STORAGE MUST BE SHOWN ON THE PLAN. | | | | 9.)THE SITE PLAN WHICH WAS NOT ON THE | | PLAN PREVIOUSLY BUT IS NOW ON THE NEW | | DRAWINGS CONFLICTS WITH THE APPROVED | | ZONING.THE ADDITION IS NOW SHOWN ON | | THE OTHER SIDE OF THE BUILDING.ISN'T | | THIS ALREADY BUILT AND CLEARLY SHOWN ON | | THE SURVEY?CLARIFY. | | | | 10.)SEE THE FIRST LIST IN REGARDS | | TO STUCCO, VERTICAL APPLICATION OVER | | WIRE LATH IS TO BE 3 COAT 7/8" | | FBC2504.2.2.SECOND CORRECTION. | | | | 11.)SEE THE PREVIOUS TWO LISTS. APPLY | | FOR AN A/C PERMIT. | | | | 12.)AS PER FS553, A 4X PLAN REVIEW IS | | BEING CHARGED.SEE ATTACHED.THIS WILL | | BE CHARGED EVERY TIME THIS IS | | RESUBMITTED AND THE CORRECTIONS HAVE NOT | | BEEN MADE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2003-10-20 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-12-17 |
Time |
11:20 |
Rev Time |
1.00 |
Received By |
sthyng |
Date |
2003-10-20 |
Time |
16:02 |
Sent To |
|
|
Notes |
2003-10-20 00:00:00 | *****CORRECTIONS***** | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)SEPARATE PERMITS REQUIRED. | | | | 2.)SEE PREVIOUS LIST, TITLE BLOCK | | REQUIRED FOR ENGINEER FAC61G15-23.002(2) | | | | 3.)ADDITIONAL FEES DUE, ADJUSTED | | VALUE AND RADON, $43.06, BZ231382. | | | | 4.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 5.)SEE PREVIOUS LIST, ITEM #7, PROVIDE | | WIND INFORMATION ON THE PLAN FBC1606.1.7 | | COMPONENTS AND CLADDING (NO DESIGN | | PRESSURE FOR DOORS). | | | | 6.)CHANGES MADE TO THE PLAN MUST BE | | CLOUDED AND INITIALED BY THE ENGINEER. | | DO NOT WHITE OUT THE PLAN. | | | | 7.)SEE PREVIOUS CORRECTION #10.MTS | | WAS CHANGED TO MTSM16, BUT THE FASTENERS | | WERE NOT CHANGED AND CONFLICT WITH THE | | CATALOG DETAIL YOU PROVIDED. | | | | 8.) SEE PREVIOUS LIST #13, REGARDING | | PLYWOOD SOFFIT AND CEILING, SURFACES | | EXPOSED TO THE WEATHER SHALL HAVE AN | | APPROVED BARRIER TO PROTECT THE | | STRUCTURAL FRAME FBC2303.3.A NOTE WAS | | MADE ON THE CORRECTION LIST, 1/2 PWT, | | PLYWOOD TREATED?THIS NEEDS TO BE ON | | THE PLAN, NOT A NOTE ON THE CORRECTION | | LIST. | | | | 9.)THE DETAIL PROVIDED FOR LSTA18 | | SHOWS A FLOOR TO FLOOR INSTALLATION; | | THIS DETAIL FOR AN APPLICATION YOU ARE | | NOT USING IS NOT NECESSARY.THE | | CORRECTION WAS RELATED TO THE NUMBER OF | | NAILS ORIGINALLY SPECIFIED. | | | | 10.) SEE PREVIOUS LIST #12.PROVIDE AN | | A/C PERMIT NUMBER. | | | | 11.) SEE ATTACHED NOTE REGARDING FS | | 553.80(2)(B). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-09-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-10-18 |
Time |
06:15 |
Rev Time |
2.00 |
Received By |
sthyng |
Date |
2003-09-20 |
Time |
10:29 |
Sent To |
|
|
Notes |
2003-09-20 00:00:00 | ******CORRECTION******** | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | 1.)SEPARATE PERMITS REQUIRED. | | | | 2.)TITLE BLOCK REQUIRED FOR ENGINEER; | | FAC61G15-23.002(2). | | | | 3.)ADDITIONAL FEES DUE; ADJUSTED VALUE | | AND RADON ($367.96).BZ231378 | | | | 4.)IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE | | STAMPED AND THE RECEIPT ATTACHED TO THE | | APPLICATION. | | | | 5.)IMPACT PROTECTION REQUIED FOR | | GLAZING; FBC1606.1.4.PROVIDE TWO | | COPIES OF PRODUCT APPROVALS. | | | | 6.)STUCCO IS REQUIRED TO BE 3-COAT | | (7/8") FOR VERTICAL APPLICATION ON | | WIRE LATH; FBC2504.2.2, ASTMC1063. | | | | 7.)PROVIDE WIND INFORMATION ON THE | | PLAN, FBC1606.1.7. | | | | 8.)CLARIFY - DOORS ARE SHOWN LEADING | | FROM THE KITCHEN TO THE NEW AREA.ARE | | THESE DOORS EXISTING? | | | | 9.)A TOTAL OF FIVE DOORS ARE SHOWN | | ON THE PLAN.ARE ALL OF THEM GLAZED? | | IF NOT, PROVIDE 2 COPIES OF PRODUCT | | APPROVALS FOR THE DOORS INSTALLED. | | THE PLAN SHOWS METAL DOORS. | | | | 10.) THE ATTACHMENT SPECIFIED FOR MTS12 | | AND LSTA18 CONFLICT WITH THE SIMPSON | | 2003 CATALOG. | | | | 11.) MTS12 IS A WOOD-TO-WOOD CONNECTOR. | | YOU ARE USING IT IN A WOOD-TO-MASONRY | | APPLICATION.EITHER SPECIFY A DIFFERENT | | CONNECTOR, OR GET CONFIRMATION FROM THE | | MANUFACTURER THAT YOU CAN USE IT IN THIS | | APPLICATION. | | | | 12.)APPLY FOR AN A/C PERMIT.NEW | | A/C IS SHOWN ON THE SURVEY, BUT I CANNOT | | FIND A RECORD OF AN A/C PERMIT IN OUR | | RECORDS. | | | | 13.)REGARDING THE PLYWOOD SOFFIT AND | | PLYWOOD CEILING, SURFACES EXPOSED TO THE | | WEATHER SHALL HAVE AN APPROVED BARRIER | | TO PROTECT STRUCTURAL FRAME, FBC2303.3. | | | | 14.)CLEARANCE BETWEEN WOOD SIDING | | AND EARTH SHALL NOT BE LESS THAN 6", | | FBC2304.2.5. | | | | 15.)BOTTOM OF FOOTER REQUIRED TO BE | | MINIMUM OF 12" BELOW GRADE, FBC1804.1.3. | | | | 16.)MTS12 IS A WOOD-TO-WOOD CONNECTOR, | | WHICH YOU ARE USING IN A WOOD-TO-MASONRY | | APPLICATION.EITHER SPECIFY A DIFFERENT | | ATTACHMENT OR GET CONFIRMATION FROM THE | | MANUFACTURER THAT YOU CAN USE IT IN THIS | | APPLICATION. | | | | 17.)REGARDING THE PLYWOOD SOFFIT AND | | THE PLYWOOD CEILING (PORCH), SURFACES | | EXPOSED TO THE WEATHER SHALL HAVE AN | | APPROVED BARRIER TO PROTECT THE | | STRUCTURAL FRAME, FBC2303.3. | | | | 18.)CLEARANCE BETWEEN WOOD SIDING AND | | THE EARTH SHALL NOT BE LESS THAN 6", FBC | | 2304.2.5. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-12-17 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-12-17 |
Time |
11:19 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2003-12-17 |
Time |
11:09 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2003-08-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2003-12-13 |
Time |
07:23 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2003-08-26 |
Time |
15:11 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-01-12 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-12 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-01-12 |
Time |
16:17 |
Sent To |
B |
|
Notes |
2004-01-12 00:00:00 | TO SH DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2003-12-04 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-04 |
Time |
08:19 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-12-04 |
Time |
08:19 |
Sent To |
P |
|
Notes |
2003-12-04 00:00:00 | TO KS BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-10-06 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-06 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-06 |
Time |
14:11 |
Sent To |
P |
|
Notes |
2003-10-06 00:00:00 | TO KS BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-08-20 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-20 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
dbaxter |
Date |
2003-08-20 |
Time |
16:32 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-08-18 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2003-08-20 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2003-08-18 |
Time |
11:37 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2003-09-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-09-03 |
Time |
14:44 |
Rev Time |
0.15 |
Received By |
pkrauss |
Date |
2003-09-12 |
Time |
08:32 |
Sent To |
B |
|
Notes |
2003-09-12 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2003-12-13 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2003-12-13 |
Time |
07:22 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2003-12-13 |
Time |
07:22 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2003-10-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-04 |
Time |
08:19 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2003-10-18 |
Time |
06:15 |
Sent To |
B |
|
Notes |
2003-10-18 00:00:00 | DENIED | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | | 1) COMMENTS FROM FIRST REVIEW HAVE NOT | | BEEN ADDRESSED. SEE FIRST PLUMBING RE- | | VIEW ATTACHED TO PERMIT APPLICATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-09-03 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-06 |
Time |
14:12 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2003-09-03 |
Time |
14:44 |
Sent To |
M |
|
Notes |
2003-09-03 00:00:00 | DENIED | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | | 1) 61G15-23.002(2) ENGINEERS SHALL LEGI- | | BLY INDICATE THEIR NAME, ADDRESS AND | | LICENSE NUMBER ON EACH SHEET. IF PRACT- | | ICING THROUGH A DULY AUTHORIZED ENGIN- | | EERING BUSINESS, ENGINEERS SHALL LEGIBLY | | INDICATE THEIR NAME AND LICENSE NUMBER, | | AS WELL AS, THE NAME, ADDRESS, AND CERT- | | IFICATE OF AUTHORIZATION NUMBER OF THE | | ENGINEERING BUSINESS ON EACH SHEET. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2004-01-22 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-01-22 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-01-22 |
Time |
10:55 |
Sent To |
B |
|
Notes |
2004-01-22 00:00:00 | SAMANTHA HILL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2003-12-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-01-17 |
Time |
18:34 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2003-12-23 |
Time |
16:07 |
Sent To |
|
|
Notes |
2003-12-23 00:00:00 | DENIED, OLD SURVEY AND NEW DRAWING DOES | | NOT MATCH CALLED CONTR ON BOTH NUMBERS | | OFFICE # DISCONNECTED & CELL # NOT A | | WORKING NUMBER FILE S MM |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-08-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2003-12-17 |
Time |
19:13 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
|
Time |
|
Sent To |
I |
|
Notes |
|
|