Plan Review Details - Permit 03080861
Plan Review Stops For Permit 03080861
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-01-17 Cont ID  
Sent By mmclean Date 2004-01-22 Time 10:56 Rev Time 1.00
Received By shill Date 2004-01-17 Time 18:33 Sent To Z
Notes
2004-01-17 00:00:00***PROVISO****
 APPLY FOR AN A/C PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-12-17 Cont ID  
Sent By csiegber Date 2004-01-12 Time 16:17 Rev Time 1.00
Received By shill Date 2003-12-17 Time 18:56 Sent To Z
Notes
2003-12-17 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)ADDITIONAL FEES DUE, $43.06,
 BZ WAS IN PACKAGE BUT IS NOW GONE.
  
 3.)A NOTICE OF COMMENCMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)SEE PREVIOUS LISTS, 3RD TIME ON
 THIS CORRECTION, PROVIDE WIND
 INFORMATION ON THE PLAN FBC1606.1.7
 INCLUDING COMPONENTS AND CLADDING
 (DESIGN PRESSURE FOR DOORS).
  
 5.)SEE PREVIOUS LISTS, 3RD TIME ON
 THIS CORRECTION, MTSM16 NAILING
 CONFLICTS WITH CATALOG.ADDRESS.
  
 6.)SEE PREVIOUS LISTS, 3RD TIME,
 REGARDING PLYWOOD SOFFIT AND CEILING,
 FBC2303.3.
  
 7.)SEE PREVIOUS LISTS IN REGARDS
 TO LSTA18, NAILING CONFLICTS WITH
 CATALOG.3RD TIME
  
 8.)THE ROOM DESIGNATION FOR EXISTING
 ROOMS WAS REMOVED ON THE NEW DRAWING.
 THE ROOM LEADING FROM THE HOUSE TO THE
 STORAGE MUST BE SHOWN ON THE PLAN.
  
 9.)THE SITE PLAN WHICH WAS NOT ON THE
 PLAN PREVIOUSLY BUT IS NOW ON THE NEW
 DRAWINGS CONFLICTS WITH THE APPROVED
 ZONING.THE ADDITION IS NOW SHOWN ON
 THE OTHER SIDE OF THE BUILDING.ISN'T
 THIS ALREADY BUILT AND CLEARLY SHOWN ON
 THE SURVEY?CLARIFY.
  
 10.)SEE THE FIRST LIST IN REGARDS
 TO STUCCO, VERTICAL APPLICATION OVER
 WIRE LATH IS TO BE 3 COAT 7/8"
 FBC2504.2.2.SECOND CORRECTION.
  
 11.)SEE THE PREVIOUS TWO LISTS. APPLY
 FOR AN A/C PERMIT.
  
 12.)AS PER FS553, A 4X PLAN REVIEW IS
 BEING CHARGED.SEE ATTACHED.THIS WILL
 BE CHARGED EVERY TIME THIS IS
 RESUBMITTED AND THE CORRECTIONS HAVE NOT
 BEEN MADE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-20 Cont ID  
Sent By btrobaug Date 2003-12-17 Time 11:20 Rev Time 1.00
Received By sthyng Date 2003-10-20 Time 16:02 Sent To  
Notes
2003-10-20 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)SEE PREVIOUS LIST, TITLE BLOCK
 REQUIRED FOR ENGINEER FAC61G15-23.002(2)
  
 3.)ADDITIONAL FEES DUE, ADJUSTED
 VALUE AND RADON, $43.06, BZ231382.
  
 4.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 5.)SEE PREVIOUS LIST, ITEM #7, PROVIDE
 WIND INFORMATION ON THE PLAN FBC1606.1.7
 COMPONENTS AND CLADDING (NO DESIGN
 PRESSURE FOR DOORS).
  
 6.)CHANGES MADE TO THE PLAN MUST BE
 CLOUDED AND INITIALED BY THE ENGINEER.
 DO NOT WHITE OUT THE PLAN.
  
 7.)SEE PREVIOUS CORRECTION #10.MTS
 WAS CHANGED TO MTSM16, BUT THE FASTENERS
 WERE NOT CHANGED AND CONFLICT WITH THE
 CATALOG DETAIL YOU PROVIDED.
  
 8.) SEE PREVIOUS LIST #13, REGARDING
 PLYWOOD SOFFIT AND CEILING, SURFACES
 EXPOSED TO THE WEATHER SHALL HAVE AN
 APPROVED BARRIER TO PROTECT THE
 STRUCTURAL FRAME FBC2303.3.A NOTE WAS
 MADE ON THE CORRECTION LIST, 1/2 PWT,
 PLYWOOD TREATED?THIS NEEDS TO BE ON
 THE PLAN, NOT A NOTE ON THE CORRECTION
 LIST.
  
 9.)THE DETAIL PROVIDED FOR LSTA18
 SHOWS A FLOOR TO FLOOR INSTALLATION;
 THIS DETAIL FOR AN APPLICATION YOU ARE
 NOT USING IS NOT NECESSARY.THE
 CORRECTION WAS RELATED TO THE NUMBER OF
 NAILS ORIGINALLY SPECIFIED.
  
 10.) SEE PREVIOUS LIST #12.PROVIDE AN
 A/C PERMIT NUMBER.
  
 11.) SEE ATTACHED NOTE REGARDING FS
 553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By kstevens Date 2003-10-18 Time 06:15 Rev Time 2.00
Received By sthyng Date 2003-09-20 Time 10:29 Sent To  
Notes
2003-09-20 00:00:00******CORRECTION********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)TITLE BLOCK REQUIRED FOR ENGINEER;
 FAC61G15-23.002(2).
  
 3.)ADDITIONAL FEES DUE; ADJUSTED VALUE
 AND RADON ($367.96).BZ231378
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 5.)IMPACT PROTECTION REQUIED FOR
 GLAZING; FBC1606.1.4.PROVIDE TWO
 COPIES OF PRODUCT APPROVALS.
  
 6.)STUCCO IS REQUIRED TO BE 3-COAT
 (7/8") FOR VERTICAL APPLICATION ON
 WIRE LATH; FBC2504.2.2, ASTMC1063.
  
 7.)PROVIDE WIND INFORMATION ON THE
 PLAN, FBC1606.1.7.
  
 8.)CLARIFY - DOORS ARE SHOWN LEADING
 FROM THE KITCHEN TO THE NEW AREA.ARE
 THESE DOORS EXISTING?
  
 9.)A TOTAL OF FIVE DOORS ARE SHOWN
 ON THE PLAN.ARE ALL OF THEM GLAZED?
 IF NOT, PROVIDE 2 COPIES OF PRODUCT
 APPROVALS FOR THE DOORS INSTALLED.
 THE PLAN SHOWS METAL DOORS.
  
 10.) THE ATTACHMENT SPECIFIED FOR MTS12
 AND LSTA18 CONFLICT WITH THE SIMPSON
 2003 CATALOG.
  
 11.) MTS12 IS A WOOD-TO-WOOD CONNECTOR.
 YOU ARE USING IT IN A WOOD-TO-MASONRY
 APPLICATION.EITHER SPECIFY A DIFFERENT
 CONNECTOR, OR GET CONFIRMATION FROM THE
 MANUFACTURER THAT YOU CAN USE IT IN THIS
 APPLICATION.
  
 12.)APPLY FOR AN A/C PERMIT.NEW
 A/C IS SHOWN ON THE SURVEY, BUT I CANNOT
 FIND A RECORD OF AN A/C PERMIT IN OUR
 RECORDS.
  
 13.)REGARDING THE PLYWOOD SOFFIT AND
 PLYWOOD CEILING, SURFACES EXPOSED TO THE
 WEATHER SHALL HAVE AN APPROVED BARRIER
 TO PROTECT STRUCTURAL FRAME, FBC2303.3.
  
 14.)CLEARANCE BETWEEN WOOD SIDING
 AND EARTH SHALL NOT BE LESS THAN 6",
 FBC2304.2.5.
  
 15.)BOTTOM OF FOOTER REQUIRED TO BE
 MINIMUM OF 12" BELOW GRADE, FBC1804.1.3.
  
 16.)MTS12 IS A WOOD-TO-WOOD CONNECTOR,
 WHICH YOU ARE USING IN A WOOD-TO-MASONRY
 APPLICATION.EITHER SPECIFY A DIFFERENT
 ATTACHMENT OR GET CONFIRMATION FROM THE
 MANUFACTURER THAT YOU CAN USE IT IN THIS
 APPLICATION.
  
 17.)REGARDING THE PLYWOOD SOFFIT AND
 THE PLYWOOD CEILING (PORCH), SURFACES
 EXPOSED TO THE WEATHER SHALL HAVE AN
 APPROVED BARRIER TO PROTECT THE
 STRUCTURAL FRAME, FBC2303.3.
  
 18.)CLEARANCE BETWEEN WOOD SIDING AND
 THE EARTH SHALL NOT BE LESS THAN 6", FBC
 2304.2.5.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-17 Cont ID  
Sent By btrobaug Date 2003-12-17 Time 11:19 Rev Time 0.33
Received By btrobaug Date 2003-12-17 Time 11:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By jleech Date 2003-12-13 Time 07:23 Rev Time 0.33
Received By btrobaug Date 2003-08-26 Time 15:11 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-12 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-01-12 Time 16:17 Sent To B
Notes
2004-01-12 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-04 Cont ID  
Sent By csiegber Date 2003-12-04 Time 08:19 Rev Time 0.00
Received By csiegber Date 2003-12-04 Time 08:19 Sent To P
Notes
2003-12-04 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 14:11 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 14:11 Sent To P
Notes
2003-10-06 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-20 Cont ID  
Sent By dbaxter Date 2003-08-20 Time 16:32 Rev Time 0.00
Received By dbaxter Date 2003-08-20 Time 16:32 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-18 Cont ID  
Sent By mmclean Date 2003-08-20 Time 10:33 Rev Time 0.00
Received By alange Date 2003-08-18 Time 11:37 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-09-12 Cont ID  
Sent By kstevens Date 2003-09-03 Time 14:44 Rev Time 0.15
Received By pkrauss Date 2003-09-12 Time 08:32 Sent To B
Notes
2003-09-12 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-12-13 Cont ID  
Sent By jleech Date 2003-12-13 Time 07:22 Rev Time 0.50
Received By jleech Date 2003-12-13 Time 07:22 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-18 Cont ID  
Sent By csiegber Date 2003-12-04 Time 08:19 Rev Time 0.33
Received By kstevens Date 2003-10-18 Time 06:15 Sent To B
Notes
2003-10-18 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
  
 1) COMMENTS FROM FIRST REVIEW HAVE NOT
 BEEN ADDRESSED. SEE FIRST PLUMBING RE-
 VIEW ATTACHED TO PERMIT APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-10-06 Time 14:12 Rev Time 0.33
Received By kstevens Date 2003-09-03 Time 14:44 Sent To M
Notes
2003-09-03 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
  
 1) 61G15-23.002(2) ENGINEERS SHALL LEGI-
 BLY INDICATE THEIR NAME, ADDRESS AND
 LICENSE NUMBER ON EACH SHEET. IF PRACT-
 ICING THROUGH A DULY AUTHORIZED ENGIN-
 EERING BUSINESS, ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME AND LICENSE NUMBER,
 AS WELL AS, THE NAME, ADDRESS, AND CERT-
 IFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2004-01-22 Cont ID  
Sent By mmclean Date 2004-01-22 Time 10:56 Rev Time 0.00
Received By mmclean Date 2004-01-22 Time 10:55 Sent To B
Notes
2004-01-22 00:00:00SAMANTHA HILL

Review Stop Z ZONING
Rev No 2 Status F Date 2003-12-23 Cont ID  
Sent By shill Date 2004-01-17 Time 18:34 Rev Time 0.00
Received By mmclean Date 2003-12-23 Time 16:07 Sent To  
Notes
2003-12-23 00:00:00DENIED, OLD SURVEY AND NEW DRAWING DOES
 NOT MATCH CALLED CONTR ON BOTH NUMBERS
 OFFICE # DISCONNECTED & CELL # NOT A
 WORKING NUMBER FILE S MM

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-20 Cont ID  
Sent By shill Date 2003-12-17 Time 19:13 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***