Plan Review Details - Permit 03080695
Plan Review Stops For Permit 03080695
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-21 Cont ID  
Sent By nmccray Date 2003-08-21 Time 14:34 Rev Time 0.00
Received By nmccray Date 2003-08-21 Time 14:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-14 Cont ID  
Sent By alange Date 2003-08-13 Time 13:39 Rev Time 0.00
Received By nmccray Date 2003-08-14 Time 10:11 Sent To  
Notes
2003-08-14 00:00:00UNDER THE FIRE ALARM SEQUENCE OF
 OPERATION. THE ACTIVATIN OF ANY HVAC
 DUCT DETECTOR SHALL ANNUNCIATE AT THE
 MAIN FIRE ALARM PANEL AS AN ALARM
 CONDITION SHOWING ZONE IN ALARM. AND
 TRANSMIT AN ALARM TO A U.L. LISTED
 CENTRAL STATION PER THE WEST PALM BEACH
 FIRE MARSHAL OFFICE. NOT A SUPERVISORY.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-08-21 Time 14:00 Rev Time 0.00
Received By csiegber Date 2003-08-21 Time 14:00 Sent To  
Notes
2003-08-21 00:00:00COMM BD #26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-13 Cont ID  
Sent By alange Date 2003-08-13 Time 13:39 Rev Time 0.00
Received By alange Date 2003-08-13 Time 13:39 Sent To FIRE
Notes
***NONE***