Plan Review Details - Permit 03080678
Plan Review Stops For Permit 03080678
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-10 Cont ID  
Sent By lsmith Date 2003-09-10 Time 12:36 Rev Time 0.75
Received By lsmith Date 2003-09-10 Time 12:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-27 Cont ID  
Sent By pkrauss Date 2003-08-27 Time 07:55 Rev Time 1.00
Received By lsmith Date 2003-08-27 Time 10:07 Sent To  
Notes
2003-08-27 00:00:00********FAILED**************
  
 1. ENERGY EFFECIENCY CODE FORM SHOWS 8
 WINDOWS; HOUSE HAS 9 SINGLE & 2 DOUBLE
 SINGLE HUNG WINDOWS.
  
 2.AT LEAST ONE BATH DOOR MUST HAVE 30"
 CLEAR OPENING PER FBC 2001.
  
 3. EACH BEDROOM MUST COMPLY WITH THE
 FBC MEANS OF EGRESS.
  
 4. A PRE-INSPECTION IS REQUIRED PRIOR TO
 PERMITTING.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2003-09-10 Cont ID  
Sent By kstevens Date 2003-09-26 Time 14:14 Rev Time 0.00
Received By lsmith Date 2003-09-10 Time 12:38 Sent To  
Notes
2003-09-10 00:00:00***************PROVISO***************
  
  
 ELECTRIC DELETED FORM SUBMITTAL.
 ELECTRICAL CONTRACTOR WILL SUBMIT
 SEPARATE PLANS & GET SEPARATE PERMIT
 FOR ELECTRIC.
 ALL SUBS WILL APPLY FOR SEPARATE PERMITS
  
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2003-09-10 Cont ID  
Sent By dpalmer Date 2003-09-10 Time 11:46 Rev Time 0.25
Received By dpalmer Date 2003-09-10 Time 11:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-08 Cont ID  
Sent By dpalmer Date 2003-09-08 Time 10:18 Rev Time 0.50
Received By dpalmer Date 2003-09-08 Time 10:17 Sent To P
Notes
2003-09-08 00:00:00********* UNSAT **************
  
 PLEASE SEE THAT NOW PLANS HAVE COME BACK
 IN W/OUT ELECTRICAL PLANS ???
 PLEASE CLARIFY?
  
 PLEASE SUBMIT THE ABOVE, OR PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-18 Cont ID  
Sent By dbaxter Date 2003-09-02 Time 15:36 Rev Time 0.75
Received By dpalmer Date 2003-08-18 Time 13:50 Sent To P
Notes
2003-08-18 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY SERVICE, NEW,
 EXISTING?
 IF NEW SUBMIT AIC RATING FOR NEW MCB.
 110.9/215.5
  
 2)NOTE: PLEASE SEE RISER DAIGRAM, SHOWS
 SUB-FEED TO ANOTHER PANEL? 3-3/0`S ?
 PLEASE SEE PANEL SCHEDULE SUBMITTED,
 DOES NOT SHOW THIS? PLEASE CLARIFY.
  
 3)NOTE: PLEASE SEE OCP SHOWN FOR AHU,
 10KW W/ 30A OCP. PLEASE SEE 424.3B
  
 4)NOTE: PLEASE SEE 220.16 FOR MIN LOAD
 FOR WASHER CIRCUIT. 1500VA
  
 5)NOTE: PLEASE SEE 220.18 FOR MIN LOAD
 FOR DRYER.
  
 6)NOTE: PLEASE NOTE, RISER DIAGRAM SHOWS
 GEC TO FOOTER STEEL, THIS IS NOT REQ'D
 WHEN THERE IS AN EXISTING BLDG, HOWEVER
 IF SHOWN ON PLANS, THEN IT WILL BE REQ'D
 TO BE INSTALLED. 250.50.
  
 7)NOTE: PLEASE MOVE SD IN MAIN RM TO BE
 IN THEN VICINITY OUTSIDE BEDRM DOOR.
 NFPA-72 8-1.4.2
  
 8)NOTE: PLEASE SEE MISSING GFI RECEPT
 REQ'D FRONT OF DWELLING. 210.52E
  
 9)NOTE: PLEASE SEE ONLY TWO SM APPL
 FIGURED IN LOAD CALCS AND THREE SHOWN
 ON PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-11 Cont ID  
Sent By csiegber Date 2003-09-11 Time 14:52 Rev Time 0.00
Received By csiegber Date 2003-09-11 Time 14:52 Sent To  
Notes
2003-09-11 00:00:00TO LM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-02 Cont ID  
Sent By dbaxter Date 2003-09-02 Time 15:36 Rev Time 0.00
Received By dbaxter Date 2003-09-02 Time 15:35 Sent To E
Notes
2003-09-02 00:00:00TO DPALMER DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-13 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 11:00 Rev Time 0.00
Received By dbaxter Date 2003-08-13 Time 11:00 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-27 Cont ID  
Sent By kstevens Date 2003-08-22 Time 18:25 Rev Time 0.25
Received By pkrauss Date 2003-08-27 Time 07:35 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-09-26 Cont ID  
Sent By kstevens Date 2003-09-26 Time 14:14 Rev Time 0.50
Received By kstevens Date 2003-09-26 Time 14:14 Sent To E
Notes
2003-09-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. SUBMIT A REVISION
 OF THE FLOOR PLAN THAT SHOWS THE LOCAT-
 ION OF THE WASH MACHINE. 104.2.1
 2) AND REVISION OF A SIGNED AND SEALED
 PLAN SHALL BE SIGNED AND SEALED BY THE
 ENGINEER OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2003-09-10 Cont ID  
Sent By lsmith Date 2003-09-10 Time 12:51 Rev Time 0.25
Received By lsmith Date 2003-09-10 Time 12:51 Sent To  
Notes
2003-09-10 00:00:00PLUMBING PLANS & PERMIT WILL BE APPLIED
 FOR SEPARATELY LS

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-22 Cont ID  
Sent By dpalmer Date 2003-09-08 Time 10:27 Rev Time 0.33
Received By kstevens Date 2003-08-22 Time 18:25 Sent To M
Notes
2003-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) WASH MACHINE CONNECTION REQUIRED PER
 TABLE 403.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]