Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-16 Cont ID  
Sent By kstevens Date 2003-08-16 Time 09:43 Rev Time 1.00
Received By kstevens Date 2003-08-16 Time 09:43 Sent To  
Notes
2003-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) BATHROOMS AND SINKS ARE NOT VENTED
 PROPERLY. 1002.3(5)
 B) WATER CLOSETS SHALL NOT BE DOUBLE
 TRAPPED. TRAP IS IN FIXTURE. 1002.1
 C) SINKS ARE NOT SHOWN ON FLOOR PLAN.
 D) FLOOR PLAN ON THE DEMO PLAN INDICAT-
 ES ONE FLOOR. RISER DIAGRAM INDICATES
 TWO FLOORS. PLEASE CLAIRFY.
 E) TUB ARE NOT VENTED. 901.2.1
 2) SUBMIT A NEW FLOOR PLAN FOR COMPARI-
 SON.
  