Plan Review Details - Permit 03080509
Plan Review Stops For Permit 03080509
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-15 Cont ID  
Sent By jgomez Date 2004-03-15 Time 17:29 Rev Time 0.50
Received By jgomez Date 2004-03-15 Time 17:29 Sent To PC
Notes
2004-03-15 00:00:00REVISION BUILDING REVIEW PROVISO:
 1-ICYNENE INSULATION SYSTEM TO BE
 APPLIED ONLY BY CONTRACTOR CERTIFIED TO
 TO THIS TYPE OF INSULATION.
 2-INSTALLER TO PROVIDE LETTER CERTIFYING
 INSTALLATION AS REQUIRED ON SEC. 4.2.3
 OF LEGACY REPORT NER-420.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-02 Cont ID  
Sent By csiegber Date 2004-03-11 Time 11:23 Rev Time 0.50
Received By jgomez Date 2004-02-02 Time 14:09 Sent To PC
Notes
2004-02-02 00:00:00SUBMITTAL: REVISED TRUSS LAYOUT TO
 INCLUDE ATTIC LIVE LOAD, SURVEY, FIRE-
 PLACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-20 Cont ID  
Sent By csiegber Date 2004-01-16 Time 13:35 Rev Time 2.00
Received By jgomez Date 2003-10-20 Time 10:40 Sent To PC
Notes
2003-10-20 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SURVEY THAT IS PREPARED FOR
 CONSTRUCTION. SURVEYORS NOTES NOTE #4
 DOESN'T ALLOW SURVEY SUBMITTED TO BE
 USED FOR CONSTRUCTION.
 2-SPECIFY SIZES OF FASTENERS ON AIR
 HANDLING UNIT. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-PROVIDE SITE SPECIFIC ENGINEERING FOR
 ENTRY DOOR UNDR A SEPARATE PERMIT.
 4-SOIL TEST REPORT: A)REVISE PROJECT
 DESCRIPTION. PROPOSED HOUSE IS A TWO
 STORY BUILDING, NOT ONE STORY.
 B)NEEDS ENGINEER ORIGINAL SIGNATURE. NOT
 RUBBER STAMP. CHAPTER 471 FL STATUTES.
 4-PROVIDE SPECIFIC FIREPLACE UL LISTING
 TO VERIFY IF IS CURRENT. SBCCI REPORT
 # 9626 WAS DELETED FROM THE LISTING.
 5-REVISE ROOF LOADING TABLE ON SHEET A5.
 BOTTOM CHORD NEED TO HAVE 10# LIVE
 LOAD. SEE TABLE 1604.1 FBC 2001.REVISE
 THIS INFO. TO ENSURE TRUSSES ARE
 DESIGNED INCLUDING THIS LOADING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-09 Cont ID  
Sent By btrobaug Date 2003-10-08 Time 16:05 Rev Time 3.00
Received By jgomez Date 2003-09-08 Time 16:45 Sent To PC
Notes
2003-09-08 00:00:00BUILDING CHECKLIST:
 1-CASEMENT WINDOWS DON'T COMPLY WITH
 EGRESS REQUIREMENTS OF SEC. 1005.4.4
 FBC 2001. CENTER MULLION DOESN'T
 ALLOW THE 20" MIN. REQUIRED WIDTH.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-3" PVC PIPE SHOWN ON SITE PLAN IS
 ENCROACHING INTO NEIGHBOR'S PROPERTY.
 WHAT'S THIS PIPE FOR?. HOW IS IT
 PROTECTED CONSIDERING THAT WILL BE
 UNDER THE DRIVEWAY. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE SPECIFICATIONS/DETAILS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES.
 INCLUDING FIREBLOCKING AT STAIRS. SEE
 SEC. 2305 FBC 2001. FOR FIREBLOCKING
 REQUIRED LOCATIONS.
 6-PROVIDE AIR HANDLING UNIT MOUNTING
 DETAIL. SPECIFY ALL FASTENERS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-NOTE: ALL DRAWINGS THAT ARE REVISED
 NEED TO BE TAKEN TO HISTORIC DEPT. FOR
 APPROVAL STAMP PRIOR TO RESUBMITTAL TO
 THIS OFFICE.
 8-PROVIDE ATTIC ACCESS AT SECOND FLOOR
 ROOF. SEC. 2309.6 FBC 2001.
 9-UPDATE TRUSS ANCHOR SCHEDULE TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001, WHICH
 DOESN'T ALLOW THE STEEL STRESS TO BE
 INCREASED.
 **NOTE: USE SIMPSON HIGH WIND-RESISTANT
 CONSTRUCTION CATALOGUE WHICH IS THE
 ONLY SIMPSON CATALOGUE THAT'S UPDATED
 TO REFLECT THIS SECTION OF THE CODE.
 OTHERWISE, PROVIDE ENGINEERING CALCS
 FOR VALUES OTHER THAN THOSE PUBLISHED.
 10-SPECIFY JOINTS IN CONCRETE SLAB OR
 CLEARLY SPECIFY WWM SUPPORTS AND
 SPACING. SEE SEC. 1909.3 FBC 2001.
 11-PROVIDE COMPLETE DETAIL/SPECS FOR
 BALCONY RAILINGS. SPECIFY ATTACHMENTS
 & GUARDRAIL OPENINGS BETWEEN PICKETS
 & BOTTOM RAIL. SEE SEC. 1015 FBC 2001.
 12-REVISE WINDOW & DOOR BUCK DETAILS.
 SEE SEC. 1707.4.4 FBC 2001. REVISE
 DETAILS 2,4 AND 8 OF SHEET S1.
 13-PROVIDE COMPLETE DETAIL/SPECS FOR
 CONSTRUCTION AT LANAI CEILING. SPECIFY
 ALL FASTENERS. SEE ASTM C-926 AND
 ASTM C-1063 AS REQ'D BY SEC. 2504.2FBC
 14-PROVIDE ROOF SHEATHING NAILING
 DIAPHRAGM. SEE SEC. 2306 OF CITY
 AMENDMENTS TO FBC 2001. SPECIFY NAIL
 SIZE/SPACING AND IDENTIFY ROOF ZONES.
 15-SOIL TEST REPORT. NEED TO REFERENCE
 FBC 2001, NOT SBC 1997.
 **NEED 2 COPIES WITH ENGINEER'S ORIGINAL
 SEAL, SIGNATURE, DATE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 **NEED THE 15 BORING AS RECOMMENDED ON
 ON THIS OIL TEST REPORT.
 16-PROVIDE PRODUCT APPROVAL FOR:
 A)WINDOW MULLIONS FOR IMPACT WINDOWS.
 B)ENTRY DOOR: CLARIFY IF USING DOOR
 COVERED BY PRODUCT APPROVAL OR SITE
 SPECIFIC ENGINEER LETTER ATTACHED.
 **NOTE: SITE SPECIFIC ENGINEERING NEEDS
 A COMPLETE ENGINEERING PACKAGE WITH
 CALCS AND SPECIFICATIONS. NEED TO FILL
 FORM (SEE ATTACHED SAMPLE) AND THE
 ENGINEER OF RECORD NEED TO SIGN AND
 SEAL FORM AS WELL AS REQUIRED BY THE
 BUILDING OFFICIAL.
 C)GARAGE DOOR THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER.
 D)FIREPLACE UL LISTING & COMPLETE SPECS.
 E)GARAGE EXTERIOR SWING DOOR.
 F)FRENCH DOORS WITH SIDELITES: CIRCLE ON
 PRODUCT APPROVAL SPECIFIC CONDITIONS
 TO BE USED IN THIS PROJECT TO VERIFY
 FOR DESIGN PRESSURES.
 G)CASEMENT WINDOWS: CIRCLE ON PRODUCT
 APPROVAL SPECIFIC CONDITIONS FOR THIS
 JOB TO VERIFY DESIGN PRESSURES.
  
 17-NEED TO PAY ATTACHED RECEIPTS FOR
 APPROACH PERMIT AND RADON FEES.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-03-16 Cont ID  
Sent By btrobaug Date 2004-03-16 Time 12:45 Rev Time 0.50
Received By btrobaug Date 2004-03-16 Time 12:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-03-09 Time 10:02 Rev Time 0.50
Received By btrobaug Date 2004-03-01 Time 15:41 Sent To  
Notes
2004-03-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUPPLY THE FOLLOWING
 INFORMATION REGARDING THE GENERATOR.
 A) TYPE OF FUEL USED.
 B) WIRING DIAGRAM OR SCHEMATIC SHOWING
 THAT THE GENERATOR WILL NOT
 BACKFEED FPL THROUGH THE TRANSFER
 SWITCH.
 C) THE TRANSFER SWITCH APPEARS TO BE
 BEHIND THE GENERATOR AND NOT IN
 COMPLIANCE WITH 110.26.
 D) HOW IS THE EXHAUST FROM THE GENER-
 ATOR BEING VENTED?
  
 2} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 3} THE DEMAND ON PANEL "A" IS TOO LARGE
 FOR THE 200 AMP PANEL.PLEASE
 RECALCULATE OR MOVE LOADS. SHOW
 CALCULATIONS PER 215.5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-08 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:34 Rev Time 0.55
Received By btrobaug Date 2003-10-08 Time 15:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-10-02 Time 11:35 Rev Time 1.00
Received By btrobaug Date 2003-08-20 Time 16:01 Sent To M
Notes
2003-08-21 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 1} THE METER IS NOT RATED FOR 400 AMPS.
  
 2} THE SERVICE CONDUCTORS ARE NOT RATED
 FOR 200 AMPS.SEE 310.15(B)(6).
  
 3} THE GROUNDING ELECTRODE CONDUCTOR IS
 NOT IN COMPLIANCE WITH 250.66,1/0 MIN.
  
 4} PANEL "A" IS SHOWN AS 200 AMPS ON
 THJE RISER AND 150 AMPS ON THE
 SCHEDULE,PLEASE CORRELATE.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER212.12
  
 6} PLEASE SHOW THE LOCATION OF THE
 DISCONNECTS,SHOWN ON THE RISER,ON THE
 PLAN.
  
 7} THE GARAGE RECEPTACLES MUST COMPLY
 WITH 210.8.(A)(2).
  
 8} NOTE THAT ALL KITCHEN COUNTERTOP
 RECEPTACLES MUST COMPLY WITH
 210.8(A)(6).
  
 9} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 10} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.SEE
 REVIEWED SET.
  
 11} THE POWDER ROOM REQUIRES AN OUTLET
 TO COMPLY WITH 210.52(D).
  
 12} PLEASE SEE THAT THE PLACEMENT OF
 THESMOKE DETECTORS COMPLY WITH THE
 INTENT
 OF 8-1.4.1.6 NFPA-72(1999).
  
 13} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 AFTER CORRECTIONS TO COMMENTS ARE MADE,
 PLEASE RESUBMIT FOR REVIEW AND PROVIDE
 THE OLD SHEETS TO FACILITATE THE REVIEW.
  
 IF THERE AREANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-03-11 Time 11:23 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 11:23 Sent To B
Notes
2004-03-11 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-09 Time 10:02 Rev Time 0.00
Received By csiegber Date 2004-03-09 Time 10:02 Sent To E
Notes
2004-03-09 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 14:34 Sent To M
Notes
2004-02-19 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 14:34 Sent To E
Notes
2004-02-19 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 13:35 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 13:35 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-20 Cont ID  
Sent By jgomez Date 2003-10-20 Time 15:17 Rev Time 0.00
Received By jgomez Date 2003-10-20 Time 15:17 Sent To PC
Notes
2003-10-20 00:00:00CONTRACTOR BROUGHT PAID RECEIPT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-10-02 Time 11:35 Rev Time 0.00
Received By jgomez Date 2003-10-02 Time 11:35 Sent To PC
Notes
2003-10-20 00:00:00CALLED CONTRACTOR TO BRING IMPACT FEES
 PAID RECEIPT. ONE SUBMITTED SHOWS
 BALANCE DUE.
2003-10-02 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-12 Cont ID  
Sent By alange Date 2003-08-12 Time 16:29 Rev Time 0.00
Received By alange Date 2003-08-12 Time 16:29 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-11 Cont ID  
Sent By mmclean Date 2003-08-12 Time 12:50 Rev Time 0.00
Received By dbaxter Date 2003-08-11 Time 14:07 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-24 Cont ID  
Sent By pkrauss Date 2004-02-24 Time 15:36 Rev Time 0.30
Received By pkrauss Date 2004-02-24 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:35 Rev Time 0.25
Received By pkrauss Date 2003-08-26 Time 12:03 Sent To P
Notes
2003-08-26 00:00:00PROVISO:
  
 1.BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 2.BATHROOM SHALL HAVE A WINDOW WITH
 A MINIMUM OF 3 SQ FT CLEAR OPENING OR
 BE MECHANICALLY VENTILATED. 2001 FBC(M)
 402.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-03 Cont ID  
Sent By pkrauss Date 2003-08-26 Time 12:03 Rev Time 0.33
Received By kstevens Date 2003-09-03 Time 11:53 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-11 Time 14:08 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***