Plan Review Details - Permit 03080429
Plan Review Stops For Permit 03080429
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-27 Cont ID  
Sent By kstevens Date 2003-08-27 Time 09:54 Rev Time 1.50
Received By lsmith Date 2003-08-27 Time 12:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-19 Cont ID  
Sent By csiegber Date 2003-12-08 Time 11:38 Rev Time 0.50
Received By btrobaug Date 2003-08-19 Time 09:45 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-08 Cont ID  
Sent By csiegber Date 2003-12-08 Time 11:38 Rev Time 0.00
Received By csiegber Date 2003-12-08 Time 11:38 Sent To E
Notes
2003-12-08 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-10-28 Time 15:23 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 15:23 Sent To P
Notes
2003-10-28 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 13:51 Rev Time 0.00
Received By dbaxter Date 2003-08-12 Time 13:51 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-08 Cont ID  
Sent By mmclean Date 2003-08-12 Time 09:52 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:39 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By btrobaug Date 2003-08-19 Time 11:29 Rev Time 0.25
Received By pkrauss Date 2003-08-26 Time 07:55 Sent To P
Notes
2003-08-26 00:00:00PROVISO:
  
 PLEASE NOTE BALANCED AIR RETURN SHALL
 COMPLY WITH REVISIONS TO THE 2001 FBC(M)
 601.4 DATED JUNE 30, 2003 AS FOLLOWS:
  
 BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-11-01 Cont ID  
Sent By kstevens Date 2003-11-01 Time 10:29 Rev Time 0.50
Received By kstevens Date 2003-11-01 Time 10:29 Sent To  
Notes
2003-11-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM REVISION DOES
 NOT REFLECT THE FLOOR PLAN. THE APPROVED
 SANITARY RISER DIAGRAM REFLECTS THE
 FLOOR PLAN AND SHOWS AN OPT. BAR SINK
 ALREADY AND NO REVISION IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-10-28 Time 15:23 Rev Time 0.50
Received By kstevens Date 2003-08-27 Time 09:53 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-12 Cont ID  
Sent By alange Date 2003-08-08 Time 16:39 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***