Plan Review Details - Permit 03080143
Plan Review Stops For Permit 03080143
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-28 Cont ID  
Sent By sthyng Date 2003-08-28 Time 11:52 Rev Time 1.00
Received By sthyng Date 2003-08-28 Time 11:52 Sent To  
Notes
2003-08-28 00:00:00PROVISO
 SEP PERMITS FOR HURRICANE SHUTTERS
 SUBMIT REVISION FOR S1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-28 Cont ID  
Sent By dpalmer Date 2003-08-28 Time 08:45 Rev Time 0.00
Received By sthyng Date 2003-08-28 Time 08:44 Sent To P
Notes
2003-08-19 00:00:00*****CORRECTONS******
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)ALL EXTERIOR DOORS ARE GLAZED.
 ONE METHOD OF EGRESS ON THE FIRST FLOOR
 MUST BE PROVIDED, CANNOT BE SHUTTERED,
 FBC1005.4.5, 2003 AMENDMENT.
  
 3.)SUBMIT PRODUCT APPROVALS FOR ALL
 GLAZING, DOORS, ROOF, MULLIONS,SHUTTERS.
 ANY PRODUCT APPROVALS NOT SUBMITTED
 BEFORE THE LAST REVIEW WILL REQUIRE
 SEPARATE PERMITS FOR THOSE ITEMS.
  
 4.)DETAIL S1-38, THE BOTTOM OF
 FOUNDATIONS SHALL EXTEND NO LESS THAN
 12" BELOW FINISH GRADE, FBC1804.1.3.
  
 5.)DETAIL S3-12 ATTACHMENT CONFLICTS
 WITH THE USP 2003 CATALOG.NO UPLIFT
 IS SPECIFIED IN THE CATALOG WHEN 10DX
 1 1/2 NAILS ARE USED.CHECK ALL
 ATTACHMENTS.
  
 6.)FEES DUE; $20.44.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-20 Cont ID  
Sent By jleahy Date 2004-04-20 Time 08:33 Rev Time 0.15
Received By jleahy Date 2004-04-20 Time 08:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-14 Cont ID  
Sent By jleahy Date 2004-04-14 Time 14:45 Rev Time 0.15
Received By jleahy Date 2004-04-14 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-28 Cont ID  
Sent By csiegber Date 2004-04-13 Time 11:50 Rev Time 0.50
Received By dpalmer Date 2003-08-28 Time 08:45 Sent To B
Notes
2003-08-28 00:00:00************ NOTES REDLINED *********
  
 SD MISSING IN ROOM BY FRONT DOOR NFPA-72
 MISSING RECEPT ON COUNTER IN KITCHEN.
 210.52C1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-13 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 14:00 Rev Time 0.33
Received By dpalmer Date 2003-08-13 Time 18:30 Sent To M
Notes
2003-08-13 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER AND NOTES
 FOR RISER. ONE SHOWS 225A, OTHER AT 200A
 CONDUCTORS ARE SHOWN FOR 225 AND PANEL
 IS SHOWN AS MLO.?
  
 2)NOTE: PLEASE REVISE ALL CODES SHOWN
 ON PLANS TO 2002 NEC AS OF JULY 1ST,
 2003.
  
 3)NOTE: PLEASE SEE SUB PANEL, SHOWN AS
 65A? PLEASE CORRECT AND CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 11:50 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 11:50 Sent To E
Notes
2004-04-13 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:29 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 14:29 Sent To M
Notes
2004-01-28 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-27 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 14:00 Rev Time 0.00
Received By dbaxter Date 2003-08-27 Time 14:00 Sent To E
Notes
2003-08-27 00:00:00TO DPALMER DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-11 Cont ID  
Sent By dbaxter Date 2003-08-11 Time 15:38 Rev Time 0.00
Received By dbaxter Date 2003-08-11 Time 15:38 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-06 Cont ID  
Sent By mmclean Date 2003-08-11 Time 14:13 Rev Time 0.00
Received By alange Date 2003-08-06 Time 13:42 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-06 Cont ID  
Sent By pkrauss Date 2004-02-06 Time 07:49 Rev Time 0.30
Received By pkrauss Date 2004-02-06 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-19 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:29 Rev Time 0.25
Received By pkrauss Date 2003-08-19 Time 06:51 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-20 Cont ID  
Sent By sthyng Date 2003-08-28 Time 11:51 Rev Time 0.25
Received By jleech Date 2003-08-20 Time 19:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-11 Cont ID  
Sent By alange Date 2003-08-06 Time 13:42 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***