Plan Review Details - Permit 03080127
Plan Review Stops For Permit 03080127
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-03-04 Cont ID  
Sent By shill Date 2004-03-04 Time 17:46 Rev Time 1.00
Received By shill Date 2004-03-04 Time 17:46 Sent To  
Notes
2004-03-04 00:00:00REV 7.1 2/20/04, STRUCTURAL 2/19/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-10-15 Cont ID  
Sent By csiegber Date 2004-02-20 Time 14:47 Rev Time 0.50
Received By sthyng Date 2003-10-15 Time 14:54 Sent To  
Notes
2003-10-15 00:00:00SCOTT THOMSON MGR OF SGB LLC PER
 SUNBIZ.ORG
  
 SEE PREVIOUS PROVISOS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-10-09 Cont ID  
Sent By sthyng Date 2003-10-09 Time 14:21 Rev Time 0.00
Received By sthyng Date 2003-10-09 Time 14:20 Sent To  
Notes
2003-10-09 00:00:00IMPACT FEES ONLY
 SEE PROVISOS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By sthyng Date 2003-10-07 Time 10:38 Rev Time 2.00
Received By sthyng Date 2003-10-07 Time 10:37 Sent To  
Notes
2003-10-07 00:00:00*****PROVISO*****
  
 1.) 30PSF BOTTOM CHORD LIVE LOAD FOR
 ATTICS W/STORAGE, 10PSF NO STORAGE
 FBC TABLE 1604.1.
 2.) FIREBLOCK FOR STAIRS FBC2305.1.4.
 (DETAIL 3-7.1), REVISE.
 3.) FIRESTOP 2ND FLOOR WALL SECTION 7.1
 FBC705.3., REVISE GUARDRAIL/HANDRAIL
 LANGUAGE TO COMPLY FBC1608.2, SUBMIT
 REVISION.
 4.) REVISE SHEET 3.1 TO SHOW DRAFTSTOP
 FBC705.3.
 5.) SEPARATE PERMIT REQUIRED FOR
 HURRICANE SHUTTERS; SUBMIT ATTACHMENT
 SCHEDULE AND PRODUCT APPROVALS.
 6.) DETAIL A-2.1, 4" MIN ABOVE GRADE
 FLOOR ELEVATION, WPB AMEND FBC1804.1.7.
 SUBMIT REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-26 Cont ID  
Sent By jleech Date 2003-09-29 Time 19:18 Rev Time 3.50
Received By sthyng Date 2003-08-25 Time 09:32 Sent To  
Notes
2003-08-26 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED (ROOFING,
 MECHANICAL, PLUMBING).
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)"TOTAL CONDITIONED" 2133 SF (AREA
 CALCULATIONS, 4.1) SHOULD READ "TOTAL".
  
 4.)ENERGY CALC UNDER ATTIC AREA (1833)
 IS INCORRECT.THIS IS A 2 STORY HOUSE
 WITH A TOTAL SQUARE FOOT AREA OF 1833.
  
 5.)ADDITIONAL FEES DUE (VALUE
 ADJUSTMENT, RADON) $110.22.SEE
 ATTACHED BZ #228774 AND PAY AT THE
 CASHIER.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.THIS MAY BE DONE AFTER ALL
 REVIEWS ARE COMPLETE.233-5025
  
 7.)SOILS REPORT IS FOR A PROPOSED ONE
 STORY BUILDING.THIS IS A PROPOSED TWO
 STORY BUILDING.
  
 8.)DETAIL A-2.1 SHOWS FINISHED GRADE
 LEVEL WITH THE BOTTOM OF THE WATERSTOP.
 CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FBC 1804.1.7, REQUIRES BUILDING
 FLOOR ELEVATION TO BE A MINIMUM OF 4"
 ABOVE THE FINISH GRADE.
  
 9.)ROOF NOTE 03-3.1 SPECIFIES 1/2CDX;
 CONFLICTS WITH STRUCTURAL DETAIL 2-7.1.
 REVISE ROOF NOTE.
  
 10.) WINDOW TYPE 2, SHEET 9.1, IS NOT ON
 THE PLAN.PLEASE NOTE THAT A 60" SINGLE
 HUNG WINDOW DOES NOT MEET EMERGENCY
 EGRESS REQUIREMENTS FBC1005.4.SHOW
 EMERGENCY EGRESS COMPLIANCE ON THE
 PLAN FOR EACH BEDROOM.
  
 11.) DETAIL E-3.1 SHOWS A RAKE BEAM; THE
 ELEVATION (6.1) SHOWS CDX PLYWOOD ON THE
 GABLE.IS THIS CORRECT?
  
 12.) THE BALCONY GUARDRAIL IS TO COMPLY
 WITH FBC1015.3, 1026.5, 1608.2.2.
  
 13.) PROVIDE A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE, SEE ATTACHED FORM.
  
 14.) SBCCI REPORT IS NOT LEGIBLE.THIS
 REPORT MAY BE AVAILABLE ONLINE AT
 WWW.SBCCIES.ORG (TABLE OF CONTENTS;
 LISTED EVALUATION REPORTS).
  
 15.) DRAFTSTOPPING REQUIRED, PROVIDE A
 SCHEDULE (MAY BE SHOWN ON FLOOR FRAMING
 PLAN, 3.1); FBC705.3.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-23 Cont ID  
Sent By btrobaug Date 2003-09-23 Time 10:48 Rev Time 0.50
Received By btrobaug Date 2003-09-23 Time 09:41 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-14 Cont ID  
Sent By csiegber Date 2003-09-17 Time 12:56 Rev Time 1.00
Received By btrobaug Date 2003-08-13 Time 18:26 Sent To M
Notes
2003-08-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE EQUIPMENT GROUND SHOWN FROM THE
 METER TO THE DISCONNECT CREATES A
 PARALLEL RETURN PATH WITH THE NEUTRAL
 AND MUST NOT BE INSTALLED.
  
 2} PLEASE LIST THE SMALL APPLIANCE
 CIRCUITS PER 220.16(A).THE PANEL
 SCHEDULE ONLY SHOWS 1@ 7500VA.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E
  
 6} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210.52C 1,2,3,4,AND 5.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT.NFPA-72 8-1.4.1.6.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 14:47 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 14:47 Sent To B
Notes
2004-02-20 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 12:54 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 12:54 Sent To E
Notes
2003-09-17 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 07:53 Rev Time 0.00
Received By alange Date 2003-08-07 Time 07:53 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-05 Cont ID  
Sent By mmclean Date 2003-08-06 Time 12:56 Rev Time 0.00
Received By alange Date 2003-08-05 Time 10:20 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-19 Cont ID  
Sent By btrobaug Date 2003-08-14 Time 06:53 Rev Time 0.25
Received By pkrauss Date 2003-08-19 Time 07:04 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-29 Cont ID  
Sent By jleech Date 2003-09-29 Time 19:18 Rev Time 0.33
Received By jleech Date 2003-09-29 Time 19:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By btrobaug Date 2003-09-23 Time 10:48 Rev Time 0.33
Received By jleech Date 2003-08-20 Time 20:09 Sent To B
Notes
2003-08-20 00:00:00MINIMUM PLUMBING FACILITIES TABLE 403.1
 REQUIRES ONE AUTOMATIC CLOTHES WASHER
 CONNECTION PER DWELLING UNIT.
 MAKE RED LINE CORRECTIONS TO RISER
 DIAGRAM AS MARKED ON PLANS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-05 Time 10:20 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***