Plan Review Details - Permit 03072426
Plan Review Stops For Permit 03072426
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-27 Cont ID  
Sent By sthyng Date 2003-09-30 Time 10:41 Rev Time 0.00
Received By sthyng Date 2003-09-30 Time 10:41 Sent To  
Notes
2003-09-30 00:00:00PASSED WITH PROVISOS
  
 1.)THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE.AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 2.)THE PRELIMINARY SOIL REPORT
 RECOMMENDS ADDITIONAL TESTING.THE
 CONTRACTOR IS PROCEEDING AT HIS OWN
 RISK WITHOUT THIS ADDITIONAL TESTING.
  
 3.)SUBMIT PRODUCT APPROVALS FOR THE
 3'X8' FIXED GLASS WINDOWS.
  
 4.)SUBMIT LEGIBLE PRODUCT APPROVALS
 FOR THE STEEL DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-09-17 Time 16:05 Rev Time 3.00
Received By rmcdouga Date 2003-08-21 Time 15:01 Sent To  
Notes
2003-08-21 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) PROVIDE A FINAL SOIL BORING TEST AS
 REQUIRED BY THE PRELIMINARY SOIL REPORT
 AND FBC 1804.2.2.
  
 4) REVISE NOTE #11 ON C1. FBC 1606.1.4
 REQUIRES PROTECTION OF GALZED OPENINGS
 IN WINDBORNE DEBRIS REGIONS AS WELL AS
 THE HVHZ.
  
 5) REVISE NOTE #15 UNDER FRAMING NOTES
 ON C1. HIGH RIB METAL LATH IS REQUIRED
 TO BE FASTENED AT EVERY RIB (4"O.C.) PER
 ASTM C 1063.
  
 6) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 1/2" DIA. ANCHOR BOLTS FOR THE GARAGE
 DOOR BUCKS ON THE DETAIL ON A4.
  
 7) CLARIFY ON THE S.G.D. BUCK DETAIL ON
 A4 THAT THE FRAME IS FASTENED THROUGH
 THE 1X BUCK.
  
 8) SUBMIT A TRUSS ANCHOR SCHEDULE. FBC
 1609.4.3 NO LONGER ALLOWS THE ONE-THIRD
 INCREASE IN THE STEEL CALCULATIONS FOR
 COMBINATION LOADS. SEE THE 2003 USP OR
 2002 SIMPSON HIGH WIND CONSTRUCTION
 CATALOGS FOR CONNECTOR VALUES WITHOUT
 THE INCREASE.
  
 9) REVISE CONNECTION DETAIL 2 ON A5. THE
 MAXIMUM UPLIFT VALUE IS 1125# WITH (7)
 16D NAILS IN EACH MEMBER. SEE 2003 USP
 CATALOG.
  
 10) DETAIL 11 ON A5 SPECIFIES A HANGER
 ON A MASONRY WALL FASTENED WITH (2) 5/8"
 THROUGH BOLTS ON EACH SIDE. PLEASE
 CLARIFY.
  
 11) AN ID. TAG FOR A DETAIL 1 ON A6 IS
 GIVEN ON THE FRAMING PLAN ON A5, HOWEVER
 THERE IS NO SUCH DETAIL. PLEASE CORRECT.
  
 12) AN ID. TAG FOR DETAIL 1 ON A8 IS ON
 THE FRAMING PLAN ON A5 AND THERE IS NOT
 A SHEET A8. PLEASE CORRECT.
  
 13) A SEPARATE PERMIT FOR ROOFING WILL
 BE REQUIRED.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOWS.
  
 15) THE SITE SPECIFIC PRODUCT APPROVALS
 DO NOT LIST THE 3'X 8' F.G. WINDOWS.
 THE SITE SPECIFIC PRODUCT APPROVAL FORM
 IS REQUIRED TO BE SIGNED BY THE DESIGNER
 RECORD OR A SIGNED AND SEALED LETTER OF
 APPROVAL FROM THE D.O.R. MUST ACCOMPANY
 THE FORM.
  
 16)THE STORM PANEL KEY PLAN AND SCHEDULE
 DO NOT CORRESPOND TO THE PLANS. THE
 PRODUCT APPROVAL THAT WAS SUBMITTED HAS
 EXPIRED. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-23 Cont ID  
Sent By dpalmer Date 2004-02-23 Time 10:55 Rev Time 0.33
Received By dpalmer Date 2004-02-23 Time 10:52 Sent To  
Notes
2004-02-23 00:00:00REDLINED SD, TO BE MOVED INTO BEDROOM.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-12 Cont ID  
Sent By alange Date 2003-08-05 Time 13:42 Rev Time 0.50
Received By btrobaug Date 2003-08-12 Time 16:21 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 16:05 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 16:05 Sent To B
Notes
2003-09-17 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-18 Cont ID  
Sent By alange Date 2003-08-18 Time 15:35 Rev Time 0.00
Received By alange Date 2003-08-18 Time 15:35 Sent To  
Notes
2003-08-18 00:00:00PUT WITH ORIGONAL PLANS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-06 Time 15:38 Rev Time 0.00
Received By alange Date 2003-08-06 Time 15:38 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 13:42 Rev Time 0.00
Received By alange Date 2003-08-05 Time 13:41 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-01 Cont ID  
Sent By mmclean Date 2003-08-05 Time 10:22 Rev Time 0.00
Received By alange Date 2003-08-01 Time 10:11 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-14 Cont ID  
Sent By btrobaug Date 2003-08-12 Time 16:37 Rev Time 0.25
Received By pkrauss Date 2003-08-14 Time 13:20 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-20 Cont ID  
Sent By pkrauss Date 2003-08-14 Time 13:20 Rev Time 0.33
Received By jleech Date 2003-08-20 Time 17:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-01 Time 10:12 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***