Plan Review Details - Permit 03072377
Plan Review Stops For Permit 03072377
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-23 Cont ID  
Sent By sthyng Date 2003-09-23 Time 15:33 Rev Time 1.50
Received By sthyng Date 2003-09-23 Time 12:30 Sent To  
Notes
2003-09-23 00:00:00PROVISO - SUBMIT REVISION FOR SHEET 5B

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-19 Cont ID  
Sent By dbaxter Date 2003-09-22 Time 15:44 Rev Time 2.00
Received By sthyng Date 2003-08-19 Time 09:27 Sent To  
Notes
2003-08-19 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEPARATE PERMITS REQUIRED (POOL,
 GAS).
  
 3.)FIRESTOP REQUIRED, FBC705.3 (REVISE
 WALL SECTION).
  
 4.)ADDITIONAL FEES DUE (RADON),$47.66.
  
 5.)SOME ATTACHMENTS ARE NOT CONSISTENT
 WITH THE USP2003 CATALOG EITHER IN
 NAIL SIZE OR NUMBER.NO DESIGN UPLIFT
 WAS GIVEN ON THE PLAN.EXAMPLE: DETAIL
 19-4S2 SPECIFIES HTA20 WITH 10-10DX
 1 1/2.USP CATALOG SPECIFIES 13 10DX
 1 1/2 OR 10 10D FOR 1500 UPLIFT. CONFIRM
 CONNECTIONS AND REVISE IF NECESSARY;
 NOTE ON THE PLAN.
  
 6.) PROVIDE HURRICANE SHUTTER ATTACHMENT
 SCHEDULE (SEE ATTACHED).
  
 7.) THERMA-TRU PRODUCT APPROVAL IS NOT
 LEGIBLE AND MAY BE INCOMPLETE.THIS
 MAY BE AVAILABLE FOR DOWNLOAD AT
 WWW.MIAMIDADE.GOV (FIND A DEPT; BUILDING
 CODE COMPLIANCE; PRODUCT CONTROL, SEARCH
 APPROVED PRODUCTS).
  
 8.) WINDOWS 4,5,6,21,23,24 MUST COMPLY
 WITH FBC2405.1 (SAFETY GLASS).

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-16 Cont ID  
Sent By btrobaug Date 2004-08-16 Time 09:10 Rev Time 0.50
Received By btrobaug Date 2004-08-16 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-13 Cont ID  
Sent By csiegber Date 2004-08-09 Time 13:26 Rev Time 0.50
Received By dpalmer Date 2003-08-12 Time 16:45 Sent To M
Notes
2003-08-13 00:00:00************ NOTES REDLINED**********
  
 BED RM # 2, 210.52
 METERCAN SHOULD BE SIZED AT 300A'S.
 OUTSIDE RECEPTS NOTED AS WP RECEPTS, BUT
 NOT AS GFI. 210.8

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-09 Time 13:26 Rev Time 0.00
Received By csiegber Date 2004-08-09 Time 13:26 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-02-04 Time 09:23 Rev Time 0.00
Received By csiegber Date 2004-02-04 Time 09:23 Sent To M
Notes
2004-02-04 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-22 Cont ID  
Sent By dbaxter Date 2003-09-22 Time 15:44 Rev Time 0.00
Received By dbaxter Date 2003-09-22 Time 15:44 Sent To B
Notes
2003-09-22 00:00:00TO STHYNG DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 11:44 Rev Time 0.00
Received By alange Date 2003-08-05 Time 11:43 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-31 Cont ID  
Sent By mmclean Date 2003-08-05 Time 10:42 Rev Time 0.00
Received By alange Date 2003-07-31 Time 11:37 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-12 Cont ID  
Sent By pkrauss Date 2004-02-12 Time 16:45 Rev Time 0.25
Received By pkrauss Date 2004-02-12 Time 12:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-14 Cont ID  
Sent By csiegber Date 2004-02-04 Time 09:24 Rev Time 0.25
Received By pkrauss Date 2003-08-14 Time 12:54 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-08-14 Cont ID  
Sent By pkrauss Date 2003-08-14 Time 12:55 Rev Time 0.33
Received By jleech Date 2003-08-14 Time 19:52 Sent To B
Notes
2003-08-14 00:00:00NO RISER DIAGRAM. NO PLUMBING PLAN
 REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-05 Cont ID  
Sent By alange Date 2003-07-31 Time 11:37 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-08-05 00:00:008/5/03 DENIED, NEED COPY OF SURVEY WITH
 SETBACKS, CALLED CONTR FILE LOCATED IN
 MICHELLE'S OFFICE MM
 8/5/03 PASS ZONING MM