Plan Review Details - Permit 03072263
Plan Review Stops For Permit 03072263
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-04 Cont ID  
Sent By csiegber Date 2003-11-25 Time 09:49 Rev Time 0.75
Received By jwitmer Date 2003-08-04 Time 08:02 Sent To  
Notes
2003-08-04 00:00:00MASTER PLAN 02080925 MODEL "E"
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS ANCHOR SCHEDULE BEFORE
 FOOR FRAMING INSPECTION.
 JIM WITMER
 (561)805-6715
  
 REVISION SUBMITTED W/ PLANS, NEED TO PAY
 FOR REV/ RESUBMIT!!!

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-13 Cont ID  
Sent By btrobaug Date 2003-08-13 Time 14:53 Rev Time 0.50
Received By btrobaug Date 2003-08-13 Time 14:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-08 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2003-08-04 Time 08:02 Sent To  
Notes
2003-08-04 00:00:00MASTER PLAN 02080925

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-25 Cont ID  
Sent By csiegber Date 2003-11-24 Time 13:31 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 13:31 Sent To B
Notes
2003-11-24 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 09:07 Rev Time 0.00
Received By alange Date 2003-08-08 Time 09:01 Sent To E
Notes
2003-08-08 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 14:13 Rev Time 0.00
Received By alange Date 2003-07-30 Time 14:13 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By pkrauss Date 2003-12-04 Time 12:18 Rev Time 0.25
Received By pkrauss Date 2003-12-04 Time 12:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By csiegber Date 2003-11-24 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2003-08-04 Time 08:02 Sent To  
Notes
2003-08-04 00:00:00MASTER PLAN 02080925

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By jwitmer Date 2003-08-04 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2003-08-04 Time 08:02 Sent To  
Notes
2003-08-04 00:00:00MASTER 02080925

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-05 Cont ID  
Sent By alange Date 2003-07-30 Time 14:13 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
***NONE***