Plan Review Details - Permit 03072132
Plan Review Stops For Permit 03072132
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-06 Cont ID  
Sent By sthyng Date 2003-10-06 Time 13:43 Rev Time 1.00
Received By sthyng Date 2003-10-06 Time 13:43 Sent To  
Notes
2003-10-06 00:00:00****PROVISO****
 1.) SEPARATE PERMIT REQUIRED FOR
 BAHAMA SHUTTERS
  
 2.)LIVE LOAD REQUIREMENTS FOR BOTTOM
 CHORD OF TRUSSES - 10 FOR ATTICS WITHOUT
 STORAGE, 30 FOR ATTICS WITH STORAGE
 FBC TABLE 1604.1.
  
 3.)ATTIC ACCESS REQUIRED, FBC2309.6.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-10-03 Time 09:17 Rev Time 2.50
Received By sthyng Date 2003-09-17 Time 10:30 Sent To  
Notes
2003-09-17 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).
  
 2.)ADDITIONAL PERMITS REQUIRED.
  
 3.)FEES DUE, $2.16 (RADON), BZ230486
 ATTACHED.PAY AT CASHIER.
  
 4.)SEE PREVIOUS CORRECTION LIST, ITEM
 7.NOTE THE MINIMUM ELEVATION ON THE
 PLAN.A SURVEY WAS SUBMITTED, BUT IT
 WAS FOR A COMMERCIAL BUILDING LOCATED ON
 MEADOW PARK LOT 8 BLOCK 9.
  
 5.)SEE PREVIOUS CORRECTION LIST, #9.
 WINDOWS G, D, AND E ARE 3'1 X 3'1. THIS
 SIZE DOES NOT COMPLY WITH FBC1005.4
 REQUIREMENTS FOR EMERGENCY EGRESS.
  
 6.)PRODUCT APPROVALS APPROVED FOR:
 EXTERIOR DOOR
 SINGLE HUNG IMPACT WINDOW
 ROOF TILE
  
 THE PRODUCT APPROVAL FOR THE GARAGE DOOR
 WAS ILLEGIBLE.SUBMIT 2 LEGIBLE COPIES.
  
 PRODUCT APPROVALS FOR THE BAHAMA
 SHUTTERS AND THE MULLIONS WERE REQUESTED
 BUT NOT SUBMITTED.
  
 PRODUCT APPROVALS MAY BE AVAILABLE
 ONLINE AT WWW.MIAMIDADE.GOV (FIND A
 DEPARTMENT, BUILDING CODE COMPLIANCE,
 PRODUCT CONTROL, SEARCH APPROVED
 PRODUCTS).
  
 7.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED
 IS NOT SIGNED OR RECORDED.
  
 8.)WHEN RESUBMITTING, REPLACE SHEETS
 WHICH HAVE BEEN CHANGED.OLD SHEETS
 ARE TO BE SUBMITTED SEPARATELY.THERE
 SHOULD BE TWO COMPLETE COLLATED PLAN
 SETS WITH THE MOST CURRENT REVISION OF
 EACH SHEET IN THAT SET.ALL CHANGES ARE
 TO BE CLOUDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-14 Cont ID  
Sent By pkrauss Date 2003-09-16 Time 07:11 Rev Time 2.50
Received By sthyng Date 2003-08-14 Time 16:06 Sent To  
Notes
2003-08-14 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)ENERGY CALCS REQUIRED, FBC13-103.1.
 2.WHEN RESUBMITTING, SIGN THE OWNER/
 AGENT LINE OF THE ENERGY CALC.
  
 4.)FEES DUE ($2.16, RADON)
  
 5.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 6.)IMPROVEMENTS OF OVER 50% MUST
 COMPLY WITH FBC3401.7.2.6.
  
 7.)THIS PROPERTY IS IN A FLOOD ZONE
 AND MUST COMPLY WITH CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B)(1).
 PROVIDE A SURVEY AND FLOOD ELEVATION
 CERTIFICATE FOR THIS PROPERTY.SHOW
 THE PROPOSED ELEVATION FOR THE ADDITION.
  
 8.)ROOF FRAMING PLAN REFERS TO
 ATTACHMENT 2, NOT ON THE CONNECTION
 SCHEDULE.
  
 9.)ALL WINDOWS ARE SHOWN AS FIXED
 IMPACT GLASS ON THE SCHEDULE (A1).
 ALL BEDROOMS ARE REQUIRED TO HAVE
 EMERGENCY EGRESS, FBC1005.4.
  
 10.) A-43, CONTINUOUS GABLE ENDWALL
 REINFORCEMENT, REFERS TO 110 MPH.CITY
 OF WPB IS 140MPH 3 SECOND GUST.
  
 11.) PLYWOOD SHEATHING NAILING SCHEDULE
 (A3) COMPLIES WITH THE CITY OF WPB
 AMENDMENTS TO THE FBC, TABLE 2306.1,
 BUT THE WALL SECTION DOES NOT (A-A3).
  
 12.) BOTTOM OF FOOTING MUST BE MINIMUM
 OF 12" BELOW GRADE, FBC1804.1.3.SHOW
 ON WALL SECTION.
  
 13.)FLOOR ELEVATION IS REQUIRED TO BE
 A MINIMUM OF 4" ABOVE FINISH GRADE,
 CITY OF WPB AMENDMENTS TO THE FBC
 1804.1.7.REVISE WALL SECTION.
  
 14.) A1, FLOOR PLAN REMODEL, AT THE
 NEW WIC, SHOWS DETAIL 1-A4.NOT ON
 PLAN.
  
 15.)FIRESTOP REQUIRED, FBC705.3.
  
 16.)SUBMIT TWO LEGIBLE COPIES OF
 PRODUCT APPROVALS:
 GARAGE DOOR
 BAHAMA SHUTTES
 WINDOWS
 MULLIONS
 ROOF TILE (MAY BE SUBMITTED W/ROOF
 PERMIT APPLICATION)
  
 17.)PROVIDE A SOILS INVESTIGATION
 REPORT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-05 Cont ID  
Sent By btrobaug Date 2003-09-05 Time 19:20 Rev Time 0.50
Received By btrobaug Date 2003-09-05 Time 18:56 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 16:48 Rev Time 0.50
Received By btrobaug Date 2003-08-04 Time 09:27 Sent To P
Notes
2003-08-04 00:00:00PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} DRYER VA IN THE LOAD CALCULATION MUST
 COMPLY WITH 210.18(5000 VA).
  
 3} THE AIR HANDLER IS SHOWN AS 10 KW ON
 THE SCHEDULE BUT CALCULATED @ 7400.IT
 WAS ALSO TAKEN AGAIN IN THE DEMAND FOR
 OTHER LOADS.PLEASE SEE 220.3(B).(100%).
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE INCLUIDE SMALL APPLIANCE
 CIRCUITS IN CALC.PER210.16(A).
  
 6} DINNING RM RECEPTACLE SPACING TO
 COMPLY WITH 210.52(A). SEE REVIEWD SET
 OF PLANS.
  
 7} GARAGE RECEPTACLES TO COMPLY WITH
 210.8(A)(2).GFI.
  
 8} ADD A SMOKE DETECTOR IN THE HALL
 OUTSIDE THE BEDROOMS PER 24.3.4
 NFPA-101.
  
 9} FIXTURES IN THE CLOSETS MUST COMPLY
 410.8
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 09:17 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 09:17 Sent To B
Notes
2003-10-03 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-15 Time 16:03 Rev Time 0.00
Received By csiegber Date 2003-09-15 Time 16:03 Sent To B
Notes
2003-09-15 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 16:48 Rev Time 0.00
Received By csiegber Date 2003-09-04 Time 16:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 15:59 Rev Time 0.00
Received By alange Date 2003-07-30 Time 15:59 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-28 Cont ID  
Sent By mmclean Date 2003-07-30 Time 12:03 Rev Time 0.00
Received By alange Date 2003-07-28 Time 15:46 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-16 Cont ID  
Sent By pkrauss Date 2003-09-16 Time 07:10 Rev Time 0.25
Received By pkrauss Date 2003-09-16 Time 07:10 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-08-12 Cont ID  
Sent By btrobaug Date 2003-09-05 Time 19:20 Rev Time 0.20
Received By pkrauss Date 2003-08-12 Time 06:31 Sent To B
Notes
2003-08-12 00:00:00DENIED:
  
 PLEASE CLARIFY RETURN AIR.PLANS DO NOT
 INDICATE DUCT SIZE.RETURN OR TRANSFER
 AIR REQUIRED FROM BEDROOM AREAS AS PER
 2001 FBC(M) 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-07 Cont ID  
Sent By pkrauss Date 2003-08-12 Time 06:31 Rev Time 0.25
Received By kstevens Date 2003-08-07 Time 17:07 Sent To  
Notes
2003-08-07 00:00:00PASSED/PROVISO
  
 VENT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-28 Time 15:46 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***