Plan Review Details - Permit 03071713
Plan Review Stops For Permit 03071713
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-22 Cont ID  
Sent By rmcdouga Date 2003-08-22 Time 10:20 Rev Time 2.00
Received By rmcdouga Date 2003-08-22 Time 10:20 Sent To  
Notes
2003-08-22 00:00:00PROVISO
  
 1) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 2)THE PRELIMINARY SOIL REPORT RECOMMENDS
 ADDITIONAL TESTING. THE CONTRACTOR IS
 PROCEEDING AT HIS OWN RISK WITHOUT THIS
 ADDITIONAL TESTING.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE
 74"X 96" FIXED GLASS WINDOW AND FOR THE
 37"X 24" FIXED GLASS WINDOW WITH DESIGN
 PRESSURES OF -47.2 AND + 35.3 PSF.
  
 4) PRODUCT APPROVAL FOR STORM PANELS IS
 EXPIRED. SUBMIT COPIES OF CURRENT
 PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-22 Cont ID  
Sent By alange Date 2003-08-21 Time 12:59 Rev Time 3.00
Received By rmcdouga Date 2003-08-15 Time 14:28 Sent To  
Notes
2003-08-15 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT A FINAL SOIL TEST REPORT AS
 REQUIRED BY THE PRELIMINARY SOIL REPORT
 AND FBC 1804.2.2.
  
 3) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 4) REVISE NOTE #11 UNDER PLAN NOTES ON
 C1. FBC 1606.1.4 REQUIRES PROTECTION OF
 GLAZED OPENINGS IN WINDBOURNE DEBRIS
 REGIONS AS WELL AS THE HVHZ.
  
 5) REVISE NOTE #15 UNDER FRAMING NOTES
 ON C1. ASTM C 1063 REQUIRES HIGH RIB
 METAL LATH TO BE ATTACHED AT EACH RIB
 (4"O.C.).
  
 6) THE ENERGY CALCS. ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. SEE FBC
 CHAPTER 13.
  
 7) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 1/2" DIA. A.B. FOR THE GARAGE DOOR BUCK
 ON A4.
  
 8) CLARIFY ON THE BUCK DETAIL FOR THE
 SLIDING GLASS DOOR ON A4 THAT THE FRAME
 IS FASTENED THROUGH THE 1X BUCK. SEE
 FBC 1707.4.4.2.
  
 9) DETAIL 6 ON A5 SPECIFIES A HANGER
 WITH THROUGH BOLTS AT A BLOCK WALL.
 PLEASE CLARIFY.
  
 10) THE GLASS BLOCK OPENINGS IN THE
 MASTER BATH ARE IN HAZARDOUS LOCATIONS
 AND ARE REQUIRED TO BE TEMPERED OR HAVE
 A MINIMUM UNIFORM FACE THICKNESS OF
 0.25" PER FBC 2405.2.2. PLEASE SPECIFY
 ON THE PLANS.
  
 11) THE BUILDING SET BACKS ON THE SITE
 PLAN S-1 AND THE SURVEY DIFFER. PLEASE
 CORRECT.
  
 12) SUBMIT THE CLEAR OPENING DIMENSIONS
 AND AREA FROM THE MANUFACTURER FOR THE
 SH 24-4 EGRESS WINDOWS.
  
 13) THE TAG FOR DETAIL 3 ON A5 IS SHOWN
 ON THE FRAMING PLAN IN THE WRONG
 LOCATION.
  
 14) FBC 1609.4.3 DOES NOT ALLOW THE ONE-
 THIRD INCREASE IN THE STEEL CALCULATIONS
 FOR COMBINED LOADS. PLEASE REVISE THE
 DETAILS ON A5 AND THE TRUSS CONNECTOR
 SCHEDULE ON A6 TO VALUES THAT DO NOT
 INCLUDE THIS INCREASE. SEE THE 2003 USP
 CATALOG.
  
 15) THE SITE SPECIFIC PRODUCT APPROVAL
 LETTER FROM SCOTT DISHER DOES NOT
 INDICATE THE LOT NUMBER.
  
 16) THE SITE SPECIFIC ENGINEERING FOR
 THE FIXED GLASS WINDOWS DOES NOT HAVE
 THE 74"X 96" F.G.WINDOW AT THE LIVING
 ROOM OR THE 18" DIAMETER F.G. WINDOW IN
 BATH 2.
  
 17) THE 37"X 24" FIXED GLASS WINDOW IN
 THE FAMILY ROOM THAT IS IN THE END ZONE
 EXCEEDS THE DESIGN PRESSURES LISTED IN
 THE SITE SPECIFIC ENGINEERING.
  
 18) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOWS
 - STRUCTURAL MULLIONS (CONNECTING THE
 (2) 35SH WINDOWS AT THE MASTER SUITE)
  
 19) THE FRONT ELEVATION LISTS THE WRONG
 SIZE M.O. FOR THE WINDOW IN BEDROOM 4.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-03-09 Cont ID  
Sent By dpalmer Date 2004-03-09 Time 09:38 Rev Time 0.33
Received By dpalmer Date 2004-03-09 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-03-08 Time 10:20 Rev Time 0.33
Received By dpalmer Date 2004-01-30 Time 10:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-29 Time 10:18 Rev Time 0.50
Received By dpalmer Date 2004-01-27 Time 10:05 Sent To  
Notes
2004-01-27 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 A COMPLETE SIGNATURE AS REQ'D PER FS
 481.221.
 PLEASE PROVIDE COPY OF ARCH LICENSE
 CONTAINING SIGNATURE AND /OR DRIVERS
 LICENSE.
 WE HAVE MORE THAN ONE SET OF PLANS WITH
 MORE THAN ONE SIGNATURE. WE WILL BE
 RETAINING ONE COPY OF THIS SET FOR A A
 FILE FOR VERIFICATION.
  
 2)NOTE: PLEASE SEE TITLE BLOCK, PLEASE
 PROVIDE ALL LICENSE #'S AS REQUIRED
 PER FS 481.219 AND FAC 61G1-16.004
  
 3)NOTE: PLEASE MOVE SD IN HALL TO BE
 OUTSIDE BEDROOMS AND INTHE IMEDIATE
 VICINITY, OR ADD ADDITIONAL SD.
  
 4)NOTE: PLEASE SEE ONE OF THE RECEPTS
 IN BEDROOM THAT IS REQ'D ON 2' OF WALL
 SPACE SEEMS TO BE IN A CLOSET?
 210.52
  
 5)NOTE: PLEASE SEE THAT THIS PROJECT IS
 PERMITTED UNDER THE 2002 NEC AS OF
 7/1/03. PLEASE ADJUST NOTE FOR ARC FAULT
 PROTECTION AND LIST REQ'D CIRCUITS ON
 PANELS SCHEDULES. PER 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-29 Time 07:57 Rev Time 0.25
Received By dpalmer Date 2003-07-30 Time 19:47 Sent To M
Notes
2003-07-30 00:00:00MAIN REDLINED FOR METER/MAIN AS SHOWN
 ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-08 Time 10:20 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 10:20 Sent To E
Notes
2004-03-08 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-01-29 Time 10:18 Rev Time 0.00
Received By csiegber Date 2004-01-29 Time 10:18 Sent To E
Notes
2004-01-29 00:00:00TO DP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-21 Cont ID  
Sent By alange Date 2003-08-21 Time 12:59 Rev Time 0.00
Received By alange Date 2003-08-21 Time 12:59 Sent To B
Notes
2003-08-21 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-29 Cont ID  
Sent By alange Date 2003-07-29 Time 07:57 Rev Time 0.00
Received By alange Date 2003-07-29 Time 07:57 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-23 Cont ID  
Sent By mmclean Date 2003-07-28 Time 16:34 Rev Time 0.00
Received By alange Date 2003-07-23 Time 15:37 Sent To Z
Notes
2003-07-23 00:00:00PERMIT 03071717,03071716 WITH THIS PERMI

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-10 Cont ID  
Sent By dpalmer Date 2003-07-30 Time 19:47 Rev Time 0.25
Received By pkrauss Date 2003-08-10 Time 18:37 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-11 Cont ID  
Sent By pkrauss Date 2003-08-10 Time 18:38 Rev Time 0.25
Received By jleech Date 2003-08-11 Time 19:11 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-28 Cont ID  
Sent By alange Date 2003-07-23 Time 15:38 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***