Plan Review Details - Permit 03071439
Plan Review Stops For Permit 03071439
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-02-26 Cont ID  
Sent By jwitmer Date 2004-02-26 Time 14:28 Rev Time 0.50
Received By jwitmer Date 2004-02-26 Time 14:28 Sent To  
Notes
2004-02-26 00:00:00REVISION 1-12-04JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-11-12 Cont ID  
Sent By csiegber Date 2004-02-18 Time 09:27 Rev Time 3.00
Received By jwitmer Date 2003-11-12 Time 16:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-10 Cont ID  
Sent By jwitmer Date 2003-10-10 Time 15:07 Rev Time 3.00
Received By jwitmer Date 2003-10-10 Time 15:07 Sent To  
Notes
2003-10-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03071439
 ADD: 1608 LAKE AVE
 CONT: PAUL NEWMAN
 TEL: (561)719-4248
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS W/ PROPOSED IMPROVEMENTS
 TO BE COMPLETED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SURVEY'S NOT SEALED.
  
 2) BED & BREAKFAST BEING A R-3 CLASSIF-
 ICATION (ROOMING HOUSE) BY DEFINITION
 MEETS THE REQUIREMENTS FOR SECTION 425,
 PUBLIC LODGING ESTABLISHMENTS:
 425.3.4.1 SPECIALIZED SMOKE DETECTORS
 FOR THE DEAF & HEARING-IMPAIRED SHALL
 BE MADE AVAILABLE UPON REQUEST BY GUESTS
 IN TRANSIENT PUBLIC LODGING ESTABLISH-
 MENTS.
  
 3) CONTRACTOR HAS SUBMITTED IMPACT & NON
 IMPACT PRODUCT APPROVALS FOR WINDOWS &
 DOORS. THE BUILDING OFFICIAL INTERPRETA-
 TION FOR LARGE MISSLE IMPACT PROTECTION
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) MULLIONS
 B) FRENCH DOORS W/ SIDELIGHTS
 C) GARAGE OVERHEAD DOORS
  
 5)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 6)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 7) SHEET A-03 INDICATES THE USE OF
 VANGARD PRE-FAB FIREPLACE:
 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
 2804.4.1 FACTORY-BUILT CHIMNEYS
 FACTORY BUILT CHIMNEYS SHALL BE LISTED
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, AND
 MANUFACTURER'S INSTRUCTION.
 2810 FRESH AIR INTAKES, FRESH AIR
 INTAKESSHALL BE SCREENED WITH A CORRO-
 SION RESITANT MATERIAL NOT LARGER THAN
 1/2 INCH MESH. FRESH AIR INTAKES SHALL
 NOT BE TAKEN FROM A LOCATION CLOSER THAN
 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR
 SANITARY SEWER VENT OUTLET, UNLESS SUCH
 VENT IS NOT LESS THAN 24" ABOVE THE
 FRESH AIR VENT. FRESH AIR INTAKE VENTS
 LOCATED ON THE ROOFS WILL BE PROPERLY
 MARKED WITH A UNIVERSAL MARKING,
 ***"INTAKE"***, PERMANETLY ATTACHED.
 SEE 705.1.1.4 FOR FIRE PROTECTION.
  
 8)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 9) 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIAE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 10) THEPLANS INDICATE THAT THE PLANTER
 IS OMITTED. THE PLANS DO NOT INDICATE
 IF THIS WILL BE A ROOFED OVER AREA?
  
 11) THE (4) GUEST QUARTERS ARE COVERED
 UNDER FAIR HOUSING REQUIRING THE BOTTOM
 UNITS TO HAVE ENTRY WITHOUT A STEP. DE-
 PENDING ON THE SINLGE UNIT IF TIED IN BY
 THE ROOF LINE IT ALSO WOULD HAVE TO MEET
 THIS REQUIREMENT.
  
 12) SHEET A)-1 CORRECT 1999 SBC TO
 2001 FBC & DESIGN LOAD SBCCI TO 2001
 FBC.
  
 DEPENDING ON THE POOL IF PUBLIC OR
 PRIVATE, THE FENCE HEIGHT AND THE GATE
 MAY NED TO BE HIGHER! ALSO SINCE THIS
 REVIEW FALLS INTO A R-3 CLASSIFICATION
 BE AWARE OF THE REQUIREMENTS FOR OUT-
 DOOR RESIDENTIAL SWIMMING BARRIER
 REQUIREMENTS: 424.2.17.1 THROUGH
 424.2.17.15.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By jwitmer Date 2003-08-13 Time 13:33 Rev Time 8.00
Received By jwitmer Date 2003-08-13 Time 13:33 Sent To Z
Notes
2003-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03071439
 ADD: 1608 LAKE AVE
 CONT: PAUL NEWMAN
 TEL: (561)719-4248
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ASSUMPTIONS: EXISTING RESIDENCE IS TO BE
 USED AS A SINGLE FAMILY RESIDENCE.
  
 ACTION: DENIED
  
 1) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 SURVEY'S ARE NOT SEALED.
  
 2) THE OUTDOOR POOL SHALL COMPLY WITH
 SECTION 424.2.17.1 THROUGH 424.2.17.1.15
  
 3)BED & BREAKFAST BEING A R-3 CLASSIFICA
 TION ( ROOMING HOUSE) BY DEFINITION
 MEETS THE REQUIREMENTS FOR SECTION 425,
 PUBLIC LODGING ESTABLISHMENTS
 425.3.4.1 SPECIALIZED SMOKE DETECTORS,
 FOR THE DEAF AND HEARING-IMPAIRED SHALL
 BE MADE AVAILABLE UPON REQUEST BY GUESTS
 IN TRANSIENT PUBLIC LODGING ESTABLISH-
 MENTS.
  
 4) MEASUREMENTS OF MEANS OF EGRESS,
 DOORWAYS 1003.2.3.1 THE CLEAR OPENING AT
 SWING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH
 THE DOOR AND THE STOP, WITH THE DOOR
 OPEN 90 DEGREES.
 TABLE 1004 HEADING: MINIMUM CLEAR OPEN-
 ING OF EXIT DOORS FOR R-3 32".
 SEE THE FRENCH ENTRY DOORS LISTED AS
 DOOR# 10 AS (2) 2'-6" DOORS. CLEAR OPEN-
 ING WOULD BE APPROX. 28".
  
 5) CONTRACTOR HAS SUBMITTED IMPACT AND
 NON IMPACT PRODUCT APPROVAL FOR WINDOWS
 AND DOORS. PLEASE PROVIDE A KEY PLAN
 WHICH IDENTIFIES ALL OPENINGS AND A
 LIST OF WHICH OPENINGS ARE TO BE IMPACT
 RATED AND WHICH AREN'T. THIS WILL ALSO
 TIE TO THE STORM SHUTTER REQUIREMENTS
 LISTED BELOW:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. SAMPLE ATTACHED.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) CASEMENT WINDOWS
 B) MULLIONS
 C) FRENCH DOORS W/ SIDE LIGHTS
 D) GARAGE OVERHEAD DOORS
  
 7)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 8)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 9)DISCREPANCY BETWEEN A-03 / A-12 AND
 WINDOW SCHEDULE, THE BATH WINDOW "D",
 A SECOND ISSUE IS THE WINDOW"C" ELEVA-
 TIONS VS THE WINDOW SCHEDULE.
  
 10) SHEET A-03 INDICATES THE USE OF
 VANGUARD PRE-FAB FIREPLACE:
 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
 CHIMNEYS FOR THE USE WITH FACTORY-
 BUILT FIREPLACES SHALL MEET THE
 REQUIREMENTS OF UL 127.
 2810 FRESH AIR INTAKES, FRESH AIR
 INTAKESSHALL BE SCREENED WITH A CORRO-
 SION RESITANT MATERIAL NOT LARGER THAN
 1/2 INCH MESH. FRESH AIR INTAKES SHALL
 NOT BE TAKEN FROM A LOCATION CLOSER THAN
 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR
 SANITARY SEWER VENT OUTLET, UNLESS SUCH
 VENT IS NOT LESS THAN 24" ABOVE THE
 FRESH AIR VENT. FRESH AIR INTAKE VENTS
 LOCATED ON THE ROOFS WILL BE PROPERLY
 MARKED WITH A UNIVERSAL MARKING,
 ***"INTAKE"***, PERMANETLY ATTACHED.
 SEE 705.1.1.4 FOR FIRE PROTECTION.
  
 11) ADDITIONAL INFORMATION REQUIED:
 VARIOUS DETAIL SHEETS INDICATETHE USE
 OF (2) 2X10 LEDGERS BUT NO DEPTH DIMEN-
 SION IS PROIDED FOR ANY FASTENER.
  
 12) SHEET A06/A-08 ROOF FRAMING PLANS
 DO NOT PROVIDE UPLIFT INFORMATION.
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 PROVIDE A TRUSS ANCHOR SCHEDULE!
 1606.2.4. MAIN WIND FORCE RESISTING
 SYSTEM,SHALL BE DESIGNED FOR VERTICAL
 AND HORIZONTAL LOADS BASED ON THE COM-
 BINED LEEWARD AND WINDWARD PRESSURES
 FOR WALLS AND ROOFS.
 SHEET A-14 NOTE FOR SIMPSON ANCHOR
 ETA-14, NOT IN THE CURRENT 2003 HIGH
 WIND CATALOG. PROVIDE NEW ANCHOR.
  
 13)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 14) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 16)1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 17) SHEET A-16 STAIRS, NOTE NOT CLEAR
 #5'S @6" IS THIS FOR TOP AND BOTTOM
 REBAR TO BE AT 6" O. C.
  
 18) SAME DETAIL WHAT TYPE OF FINISH
 MATERIALS IS THE BALCONY MADE OF?
  
 19) ADDITIONAL INFORMATION: A-14/A-15
 BOTH ARE INDICATED TO HAVE A RAISED
 PLANTER, PROVIDE THE LOAD CALCULATION
 PROVIDE INFO FOR THE HANGERS, IS THE
 DECK BEING 3/8 " A TYPO?
  
 20) PROVIDE CAST-CRETE LINTEL SHEETS.
  
 21)*******BUILDING OFFICIAL HAS DETER-
 MINED THAT THIS WILL NOT BE A R-3 RESI-
 DENCE BED & BREAKFAST BUT A R-1 BOARDING
 HOUSE WITH 6 UNITS. THE ADDITION TO THE
 EXISTING RESIDENCE WILL BE CONSIDERED A
 SEPERATE 6TH GUEST ROOM. THE PLANS INDI-
 CATE A 1-HR WALL SEPERATING THE TENANT
 SPACE FROM THE COMMON LIVING QUARTERS.
  
 22) SINCE THE REVIEW IS NOW A R-1 BOARD-
 ING HOUSE FL ACCESSIBILITY NOW BECOMES A
 ISSUE. AN ACCESSIBLE ROUTE TO ALL COMMON
 AREAS,RAMPS, NOT STEPS, VERTICAL ACCESSI
 BILITY TO NOT ONLY THE OFFICE, DINING
 ROOM, BOTH LAUNDRY AREAS, THE SECOND
 FLOOR UNITS AND ALL COMMON AREAS.
  
 THE BATHROOMS COMMON MUST MEET TURNING
 REQUIREMENTS AS WELL AS THE HANDICAPPED
 UNIT.
  
 23) 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 24) 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIABLE
 GRADE LEVEL.
  
 25)11-4.1.6(H) IF A PARTICULAR
 ENTRANCE IS NOT MADE ACCESSIBLE, APPRO-
 PRIATE ACCESSIBLE SIGNAGE INDICATING THE
 LOCATION OF THE NEAREST ACCESSIBLE
 ENTRANCE(S) SHALL BE INSTALLED AT OR
 NEAR THE INACCESSIBLE ENTRANCE, SUCH
 THAT A PERSON WITH DISABILITIES WILL
 NOT BE REQUIRED TO RETRACE THE APPROACH
 ROUTE FROM THE INNACCESSIBLE ENTRANCE.
  
 26)11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
  
 27)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 28) 11-4.13.5 DOORWAYS, MINIMUM
 CLEAR WIDTH: DOORWAY SHALL HAVE A MINI-
 MUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
  
 29)11.4.3.11AREAS OF RESCUE ASSISTANCE
 INDICATE LOCATION AND CONSTRUCTION TYPE
 FOR AREAS OF REFUGE, INDICATE ON PLAN
 WHICH CASE USED (1-7).
  
 30)11-4.3.11.2 STAIRWAY WIDTH, EACH
 STAIRWAY ADJACENT TO AN AREA OF RESCUE
 SHALL HAVE A MINIMUM CLEAR WIDTH OF
 48" BETWEEN HANDRAILS.
  
 31)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIP-
 TION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND, WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 COOPERATION .
 JIM WITMER
 PLAN REVIEW
 (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-09-24 Cont ID  
Sent By dpalmer Date 2004-09-24 Time 09:40 Rev Time 0.25
Received By dpalmer Date 2004-09-24 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-09-24 Time 08:58 Rev Time 0.33
Received By dpalmer Date 2004-09-16 Time 18:29 Sent To  
Notes
2004-09-16 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE LOAD CALCULAT-
 -IONS AND PANEL SCHEDULES FOR AHU'S.
 THIS IS FROM PREVIOUS NOTE #2.
  
 OWES REV FEE.
 CALLED ARCH WENT OVER NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-09-01 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:53 Rev Time 0.33
Received By dpalmer Date 2004-09-01 Time 09:46 Sent To  
Notes
2004-09-01 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER SHOWS PANEL
 "C" AS 100A, YET PANEL SCHEDULE AND
 PLANS/LOAD CALCS SHOW 125A??
  
 2)NOTE: PLEASE SEE PANEL SCHEDULES SHOW
 A TOTAL OF 9 AHU'S AND YET LOAD CALCS
 INDICATE 8 UNITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-28 Cont ID  
Sent By csiegber Date 2004-08-30 Time 09:27 Rev Time 0.50
Received By dpalmer Date 2003-10-28 Time 12:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-24 Cont ID  
Sent By dpalmer Date 2003-09-24 Time 17:56 Rev Time 2.50
Received By dpalmer Date 2003-09-24 Time 17:56 Sent To  
Notes
2003-09-24 00:00:00*************** UNSAT ***************
  
 PLEASE SEE THAT MANY COMMENTS FROM
 FIRST REVIEW NEED TO BE ADDRESSED FULLY.
  
  
 1)NOTE: PLEASE SEE SERVICE, PLEASE
 CORRELATE PANELS/RISER/ LOAD CALCULATION
 -S VOLTAGES ETC.
 LOAD CALCS SHOW 120/208V AND SOME PANELS
 SHOW 120/240V PLEASE VERIFY VOLTAGE AND
 SUBMIT ALL LOAD CALCS/PANEL TO MATCH.
 PLEASE CORRELATE RISER.
 PLEASE SEE THAT ALL PANELS, INCLUDING
 150A/125A ETC ARE SHOWN AS 42 CIRCUIT
 PANELS. PLEASE NOTE, A 125A PANEL IS NOT
 MADE FOR 42 CIRCUITS ETC.
 PLEASE SEE THAT PANEL 'A' IS SHOWN
 FEEDING PANELS B AND C, YET RISER DOES
 NOT SHOW THIS?
 ETC ETC.
  
 2)NOTE: PLEASE SEE 250.50 FOR GROUNDING.
 RISER NOTES, GROUND TO FOOTER STEEL OR
 COLD WATER OR GAS. PLEASE SEE THAT ALL
 OF THESE ARE REQ'D.
  
 3)NOTE: PLEASE SEE COMMENT ABOUT SD`S
 ON FIRST REVIEW. THIS COMMENT WAS MEANT
 FOR MAIN HOUSE. PLEASE SEE THAT SD'S ARE
 NOW PLACED OUTSIDE FOR SLEEPING ROOMS
 ON DETACHED BLDG??? NOT TO BE INSTALLED.
 MISSING FOR INSIDE.
  
 4)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 FOR ENTIRE SERVICE PER 220. PLEASE SEE
 LOAD CALCS FOR AHU'S ETC ETC.
  
 5)NOTE: PLEASE SEETHAT AN EXT CIRCUIT
 IS SHOWN FOR MAIN HOUSE AND ONLY ONE
 EXT SIGN SEEMS TO BE SHOWN? PLEASE SEE
 FIRE REVIEW COMMENT AND ALSO SEE 700.12E
 FOR CIRCUITING.
  
 6)NOTE: PLEASE SEE THAT WATER HEATER(S)
 STILL SHOWN ON ELECTRICAL PANEL? ALSO
 SHOWN AS GAS?
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT. MAINS/PANELS/ BREAKER
 S ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. 110.9/215.5
  
 8)NOTE: PLEASE CORREALET MECH/PLUMB/GAS
 PLAN WITH ELECTRICAL. SHOWS DRYER ALSO
 BEING GAS AND YET ON ELECTRICAL, THIS
 IS SHOWN AS ELEC??
  
 9)NOTE: PLEASE SEE THAT AHU'S ARE NOW
 SHOWN IN ATTIC SPACE, PLEASE SHOW LIGHT
 AND RECEPT REQ'D UNDER 210.63/210.70
  
 10)NOTE: PLEASE INDICATE INDIVIDUAL KW
 LOADS FOR AHU'S.
  
 11)NOTE: PLEASE SEE FBC CHAPTER 34
 3401.7.2/3401.7.1
 104.1 CHANGE OF OCCUPANCY TEC.
 PLEASE SHOW EXISTING ELECTRIC AND KNOW
 THAT ALL EXISTING MUST BE BROUGHT UP TO
 CODE.
  
 12)NOTE:PLEASE SEE COPY OF FS. 553.80(2)
 -(B) WITH RESPECT TO DESIGN PROFESSIONAL
 -S FOR PLAN REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-30 Cont ID  
Sent By dpalmer Date 2003-07-30 Time 06:31 Rev Time 2.00
Received By dpalmer Date 2003-07-30 Time 06:31 Sent To  
Notes
2003-07-30 00:00:00*********** UNSAT *******************
  
 PLEASE SEE THAT PLANS ARE NOT COMPLETE
 FOR FULL REVIEW.
  
 1)NOTE: PLEASE SHOW LOCATION FOR ALL
 SERVICE PANELS AND DISCONNECTS.
 PLEASE SHOW LOCATION OF MAIN SERVICE.
  
 2)NOTE: PLEASE SEE RISER, SHOWS 400A
 MAIN FEEDING TWO SEPARATE PANELS, ONE
 200A, ONE 150A? PLEASE SUBMIT PANEL
 SCHEDULE FOR 400A MAIN IF THIS A MDP?
 215.5/110.9
 PLEASE ALSO SUBMIT AIC RATING FOR 400A
 MAIN.
  
 3)NOTE: PLEASE SEE MISSING PANELS AT
 2-STORY APTS? PLEASE SEE 225.31 FOR
 MEANS OF DISCONNECT AT DETACHED STRUCT-
 -URES.
  
 4)NOTE: PLEASE SUBMIT GROUNDING FOR
 ALL DEATCHED BLDGS PER 250-32.
  
 5)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS PER 250.110 AND
 SIZE PER 250.122FOR ALL SUB-PANELS
 AFTER FIRST MEANS OF DISC. 250.24
  
 6)NOTE: PLEASE LIST ALL REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE(S)
 PER 210.12
  
 7)NOTE: PLEASE ALSO SHOW ALL A/C UNITS
 AND DISC'S PER 440.11
 RECEPTS NOW REQ'D FOR COND UNITS PER
 210.63 UNDER NEW 2002 NEC.
  
 8)NOTE: PLEASE CORRELATE RISER AND PANEL
 -BOARD "A", SHOWN AS 200A ON RISER AND
 AS 400A ON SCHEDULE?
  
 9)NOTE: PLEASE SEE RISER, SHOWS ONE
 POOL PUMP, YET PANEL 'A' SHOWS 1-20A
 BRKR FOR ONE, PANEL 'B' SHOWS ANOTHER
 POOL PUMP W/ 2P-30A AND LOAD CALCS FOR
 PANEL 'B' SHOWS @ 1.5 KW?? PLEASE
 CORRELATE.
  
 10)NOTE: PLEASE SEE MISSING SD`S. TO BE
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 NFPA-72 8-1.4.2 AND FBC
  
 11)NOTE: PLEASE LIST THE REQ'D SMALL
 APPLIANCE CIRCUITS MISSING . 210.52/
 210.11C.1, 220.16
  
 12)NOTE: PLEASELIST THE REQ'D DEDICAT-
 -ED BATH CIRCUIT(S) 210.52D/ 210.11C.3
  
 13)NOTE: PLEASE SEE FBC CHAPTER 34,
 3401.7.2, 3401.7.1 SEEFBC AND
 CITY-WIDE ADMIN CODE. 104.1 FOR
 CHANGE IN OCCUPANCY.
 PLEASE SHOW ALL EXISTING ELECTRICAL AS
 "E", PLEASE SHOW AS BRINGING UP TO CODE
 FOR ELECTRICAL.
  
 14)NOTE: PLEASE CORRELATE ALLAHU LOADS
 , OCP, AWG. SHOWN AS 20A AND LOAD CALCS
 WAY EXCEED THESE. PLEASE SHOW LOADS FOR
 ALL AHU HEAT STRIPS.
 240/424.3B
  
 15)NOTE: PLEASE SEE MIN CIRCUIT FOR
 WASHER 20A/#12, SHOWN AS #14
  
 16)NOTE: PLEASE SEE GARAGE RECEPTS TO
 BE SHOWN AS GFI/GFI PROTECTED. 210.8
  
 17)NOTE: PLEASE CORRELATE PLANS, SHOWS
 GAS WATER HEATERS AND ELECTRICAL?
  
 PLEASE NOTE, DUE TO MANY CHANGES IN PLAN
 -S TO MEET NEC CODE COMPLIANCE, THERE
 MAY BE OTHER COMMENTS TO FOLLOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE ALSO GO OVER ENTIRE SET
 OF PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-31 Cont ID  
Sent By mcarsill Date 2003-10-31 Time 16:22 Rev Time 0.00
Received By mcarsill Date 2003-10-31 Time 16:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-10-02 Cont ID  
Sent By mcarsill Date 2003-10-02 Time 07:18 Rev Time 0.00
Received By mcarsill Date 2003-10-02 Time 07:18 Sent To  
Notes
2003-10-02 00:00:001) FIRE SPRINKLER SYSTEM NOTES MAKE
 REFERENCES TO 13R AND 13D. PLEASE
 CLARIFY.
  
 2) SMOKE DETECTOR MISSING FROM NORTH
 ADDITION ELECTRICAL SHEET.
  
 3) TREADS ARE REQUIRED TO BE 11".
  
 4) IT APPEARS THAT ALL PREVIOUS
 COMMENTS BY FIRE RESCUE HAVE NOT
 BEEN PROPERLY ADDRESSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By mcarsill Date 2003-08-20 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2003-08-20 Time 12:44 Sent To  
Notes
2003-08-20 00:00:001) PLEASE CLEARLY IDENTIFY ALL SMOKE
 DETECTOR LOCATIONS. THE ELECTRICAL
 LEGEND DOES NOT CORRESPOND WITH
 REGARDS TO SMOKE DETECTORS.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 3) STORAGE NOTED UNDER STAIR SECTION AT
 NORTH ELEVATION. STORAGE IS ALLOWED
 UNDERNEATH THE STAIR SHALL BE THE
 SAME RATING AS THE STAIR.
  
 4) NO WINDOWS ARE ALLOWED WITHIN TEN
 FEET OF ANY EXIT STAIRS. PLEASE SEE
 NOTES WRITTEN BY HISTORIC DEPT.
  
 5) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 6) TREAD SIZES DO NOT APPEAR TO BE
 CORRECT 11 INCH TREADS ARE ALLOWED
 NOT 10.86.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-09-24 Cont ID  
Sent By csiegber Date 2004-09-24 Time 08:58 Rev Time 0.00
Received By csiegber Date 2004-09-24 Time 08:58 Sent To E
Notes
2004-09-24 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 15:53 Sent To E
Notes
2004-09-15 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 09:27 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 09:27 Sent To E
Notes
2004-08-30 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 09:27 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 09:27 Sent To B
Notes
2004-02-18 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 16:32 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 16:26 Sent To  
Notes
2003-10-24 00:00:00TO COMM BD#20

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 09:01 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 09:00 Sent To  
Notes
2003-09-19 00:00:00ON COMM BD#18

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-15 Cont ID  
Sent By mmclean Date 2003-09-18 Time 15:42 Rev Time 0.00
Received By csiegber Date 2003-09-15 Time 09:37 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-29 Cont ID  
Sent By alange Date 2003-07-29 Time 08:24 Rev Time 0.00
Received By alange Date 2003-07-29 Time 08:24 Sent To  
Notes
2003-07-29 00:00:00TO COMM BX 46

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-18 Cont ID  
Sent By shernand Date 2003-07-18 Time 13:28 Rev Time 0.00
Received By shernand Date 2003-07-18 Time 13:28 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-11-14 Cont ID  
Sent By pkrauss Date 2003-11-14 Time 08:07 Rev Time 0.33
Received By pkrauss Date 2003-11-14 Time 08:07 Sent To  
Notes
2003-11-14 00:00:00PROVISO:
 AUXILIARY DRAIN PANS REQUIRED AS PER
 2001 FBC(M) 307.
  
 ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 12:32 Rev Time 0.45
Received By pkrauss Date 2003-10-01 Time 12:32 Sent To  
Notes
2003-10-01 00:00:00PROVISO:
 1.PLAN SHEET M01 NOTE #17, AUXILIARY
 DRAIN PAN SHALL HAVE FLOAT SWITCH OR
 SECONDARY DRAIN TERMINATING AT A
 CONSPICUOUS POINT TO SERVE AS AN ALARM
 THAT THE PRIMARY DRAIN IS RESTRICTED.
  
 2.AHU IN THE ATTIC OR CEILING SPACE
 SHALL COMPLY WITH 2001 FBC CHAPTER 13
 SECTION 610.1.ABC.3.5.2.ACCESS SHALL
 COMPLY WITH 306.3 OF THE 2001 FBC(M).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By pkrauss Date 2003-08-20 Time 09:52 Rev Time 1.20
Received By pkrauss Date 2003-08-20 Time 09:52 Sent To  
Notes
2003-08-20 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1. PLAN SHEET M01, INDICATES DUCT
 PENTRATIONS THROUGH WALLS WITH FIRE
 RESISTANCE RATING OF 1 TO 2 HR.AS PER
 2001 FBC(M) 607.1.2.
  
 2. CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE
 AS PER 2001 FBC 1503.4.4.
  
 3. PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA ON THE FIRE PLACE.
  
 4. PROVIDE CALCULATIONS FOR COMBUSTUTION
 AIR (CONFINED SPACE). 2001 FBC(M)
 DEFINITIONS, CONFINED SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-11-04 Cont ID  
Sent By kstevens Date 2003-11-04 Time 18:26 Rev Time 2.00
Received By kstevens Date 2003-11-04 Time 18:26 Sent To  
Notes
2003-11-04 00:00:00SEPARATE GAS PERMIT REQUIRED.
  
  
  
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-08 Cont ID  
Sent By kstevens Date 2003-10-08 Time 17:02 Rev Time 2.00
Received By kstevens Date 2003-10-08 Time 17:02 Sent To  
Notes
2003-10-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 A) THE FOLLOWING COMMENTS WERE NOT ADD-
 RESSED FROM THE FIRST REVEIW. THE COMM-
 ENT NUMBERS SHALL STAY THE SAME FOR
 CLAIRITY.
 3) SHT P01 OF 29 FLOOR PLAN FOR A101/S3
 SECOND FLOOR STACK NOT SHOWN ON PLUMBING
 LAYOUT.
 7) A.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - GAS CHART SHOWS 80,000 BTU'S
 FOR NORTH ADDITION, BUT FLOOR PLAN SHOWS
 105,000 BTU'S. PLEASE CLAIRFY.
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 SHOWS .75 PSI. VERIFY WITH GAS PROVIDER.
 NORMAL PRESSURE IS EITHER .50 PSI OR
 2 PSI. PLEASE CLAIRFY.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 NEW COMMENT FOR GAS:
 K. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 10) SHT A04 OF 29 UNITS A101, A102, AND
 A103 SHALL COMPLY WITH FHA-98 AMENDED
 DESIGN MANUAL, REQUIREMENTS 1 THRU 7.
 DETAILS SHALL BE SUBMITTED. SHOW ALL
 BACKING PER REQ #6. SPECIFICATION "A" OR
 "B" BATHROOMS PER REQ. #7B, SHOW CLEAR
 FLOOR SPACE FOR ALL BATHROOM FIXTURES &
 KITCHEN FIXTURES. SHOW OPENING SIZE FOR
 ALL TOILETS, HEIGHTS FOR LAVS. ECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-18 Cont ID  
Sent By kstevens Date 2003-08-18 Time 15:25 Rev Time 2.50
Received By kstevens Date 2003-08-16 Time 15:37 Sent To  
Notes
2003-08-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHTS A05/07/09 SUBMIT CALCULATIOS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE OF ROOF & SHOW 1/2 AREA
 OF VERTICAL WALLS (PARAPETS) IN CALCUL-
 ATIONS. SHOW SIZE OF ALL DOWNSPOUTS.
 SHOW LOCATIONS FOR ALL SECONDARY ROOF
 DRAINS (SCUPPERS) - PROVIDE A DETAIL FOR
 ALL DRAINS. SHOW HEIGHT & WIDTH.
 2) SHT P01 OF 29 - S/4 & S/5, SHOW ALL
 PIPE SIZES ON ISOMETRIC DIAGRAMS. STAND-
 PIPE REQUIRED FOR WASH MACHINE. SECTION
 802.4. - CLEANOUTS REQUIRED 4' ABOVE
 FLOOR AT WASH MACHINE. SECTION 708.10
 3) SHT P01 OF 29 FLOOR PLAN FOR A101/S3
 SECOND FLOOR STACK NOT SHOWN.
 4) SHT P01 OF 29 FLOOR PLAN FOR A102/S4
 SHOWS PIPE RUNNING WEST OF SHOWER AT 2"
 THEN 1-1/2" AND TERMINATES IN LAUNDRY
 ROOM BY UNIT A103. PLEASE CLAIRFY. ALSO
 FLOOR PLAN DOES NOT SHOW WHERE IT TIES
 INTO SEWER.
 5) SHT P02 BY 29 ISOMETRIC RISER S/3
 2ND FLOOR BATHROOM SHALL TIE IN DOWN-
 STREAM OF 1ST FLOOR W/C.
 6) SHT P02 OF 29 ISOMETRIC RISER DOES
 NOT REFLECT FLOOR PLAN. SEE COMMENT #4.
 7) GAS PERMIT APPLICATION REQUIREMENTS.
 SEPARATE GAS PERMIT REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (GAS NOTES STATES POLYETHYLENE PIPE TO
 BE USED ABOVE GROUND. NOT APPROVED PER
 SECTION 403.3. DELETE REFERENCE).
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 (IF LP GAS FOLLOWING INFO REQUIRED)
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 8) SHT P02 OF 29 PLUMBING NOTES #8,
 TABLE 704.1 - PIPE SIZE 2-1/2" OR LESS
 SHALL BE RUN AT 1/4" PER FOOT SLOPE MIN.
 9) SHT P02 OF 29 PLUMBING NOTES #29.
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE.
 10) SHT A04 OF 29 UNITS A101 & A102
 SHALL COMPLY WITH FHA-98 AMENDED DESIGN
 MANUAL, REQUIREMENTS 1 THRU 7. DETAILS
 SHALL BE SUBMITTED. SHOW ALL BACKING PER
 REQ #6. SPECIFICATION "A" OR "B" BATH-
 ROOMS PER REQ. #7B, SHOW CLEAR FLOOR
 SPACE FOR ALL BATHROOM FIXTURES. SHOW
 OPENINGS FOR TOILETS, HEIGHT FOR LAVS.
 ECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2003-09-18 Cont ID  
Sent By mmclean Date 2003-09-18 Time 15:42 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-09-18 00:00:009/18/03 PASS ZONING OK PER ANGELLA JONES
 VANN MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-09-15 Time 09:49 Rev Time 0.25
Received By ajones Date   Time   Sent To  
Notes
2003-08-20 00:00:00THE DRIVEWAY ALONG THE NORTHERN PROPERTY
 LINE MUST BE EXPANED TO PARK 2-CARS.