Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-22 Cont ID  
Sent By kstevens Date 2003-07-22 Time 14:26 Rev Time 0.33
Received By kstevens Date 2003-07-22 Time 14:26 Sent To  
Notes
2003-07-22 00:00:00 
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED. MIN
 1,100 CUBIC FEET REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-22 Cont ID  
Sent By shernand Date 2003-07-17 Time 13:54 Rev Time 0.50
Received By kstevens Date 2003-07-22 Time 09:54 Sent To  
Notes
2003-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A) FOLLOWING INFORMATION REQUIRED FOR
 APPLICATION FOR GAS PERMIT.
 1. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS