Plan Review Details - Permit 03071140
Plan Review Stops For Permit 03071140
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 13:43 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 13:43 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-28 Cont ID  
Sent By pkrauss Date 2003-07-28 Time 16:34 Rev Time 0.33
Received By pkrauss Date 2003-07-28 Time 16:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-18 Cont ID  
Sent By pkrauss Date 2003-07-18 Time 07:18 Rev Time 0.55
Received By pkrauss Date 2003-07-18 Time 07:12 Sent To  
Notes
2003-07-18 00:00:00DENIED:
 REFERENCE COMMENTS ON BUILDING PERMIT
 03040476.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 INDICATE SIZE AND MATERIAL OF THE O.A.
 DUCT.
  
 INTAKE LOUVER SHALL BE SCREENED PER 2001
 FBC(M) TABLE 401.6.PLEASE INDICATE
 SIZE OF INTAKE LOUVER.
  
 CONDENSER UNIT STAND SHALL COMPLY WITH
 2001 FBC TABLE 1511.7, SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.