Plan Review Details - Permit 03070910
Plan Review Stops For Permit 03070910
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-10 Cont ID  
Sent By lsmith Date 2003-09-10 Time 13:36 Rev Time 0.75
Received By lsmith Date 2003-09-10 Time 13:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-21 Cont ID  
Sent By btrobaug Date 2003-07-21 Time 13:50 Rev Time 0.75
Received By lsmith Date 2003-07-21 Time 14:58 Sent To  
Notes
2003-07-21 00:00:00**************FAILED*****************
  
 1. DRAWINGS MUST SHOW METHOD OF
 PROTECTING THE HOUSE OPENINGS TO POOL
 AREA.
 2. DETAILS FOR EQUIPMENT ANCHORING MUST
 BE SHOWN ON THE PLANS.
 3. NEED COPY OF CONTRACT TO VERIFY VALUE
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-14 Cont ID  
Sent By btrobaug Date 2003-10-14 Time 10:11 Rev Time 0.33
Received By btrobaug Date 2003-10-14 Time 09:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-21 Cont ID  
Sent By kstevens Date 2003-10-11 Time 12:39 Rev Time 0.33
Received By btrobaug Date 2003-07-21 Time 13:38 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-02 Cont ID  
Sent By csiegber Date 2003-10-02 Time 08:06 Rev Time 0.00
Received By csiegber Date 2003-10-02 Time 08:06 Sent To P
Notes
2003-10-02 00:00:00TO KS BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-19 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:10 Rev Time 0.00
Received By csiegber Date 2003-08-19 Time 15:10 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-15 Time 08:46 Rev Time 0.00
Received By shernand Date 2003-07-15 Time 08:46 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-10-11 Cont ID  
Sent By kstevens Date 2003-10-11 Time 12:39 Rev Time 1.00
Received By kstevens Date 2003-10-11 Time 12:39 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-06 Cont ID  
Sent By csiegber Date 2003-10-02 Time 08:06 Rev Time 1.00
Received By kstevens Date 2003-09-06 Time 13:36 Sent To  
Notes
2003-09-06 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 NOT ALL COMMENTS FROM THE FIRST REVIEW
 HAV NOT BEEN ADDRESSED. THE FEW THAT
 HAVE BEEN ADDRESSED ARE NOT APPROVED.
 ANY CHANGES TO A SIGNED & SEALED SET OF
 PLANS SHALL BE DATED AND INITIALED BY
 THE ENGINEER OF RECORD.
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 4) FBC-2001424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL) (TO BE DATED AND
 SIGNED BY ENGINEER OF RECORD)
 6) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES) (SIGNED &
 DATED BY ENGINEER OF RECORD)
 7) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 8) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 9) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 10) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 11) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 12) POOL LAY-OUT SHEET SHOWS 2 JETS ON
 BENCH WHICH WILL BE REQUIRED TO BE SIGN-
 ED AND DATED BY THE ENGINEER OF RECORD,
 OR NEW SHEETS. THE PIPING SCHEMATIC DOES
 NOT REFLECT THE JETS.
 13) PIPING SCHEMATIC STILL DOES NOT SHOW
 THE VACUUM LINE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-18 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:10 Rev Time 0.50
Received By kstevens Date 2003-07-18 Time 17:58 Sent To E
Notes
2003-07-18 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (DETAIL OR NOTES)
 4) FBC-2001424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 6) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 7) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 8) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 9) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 10) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 11) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 12) POOL LAY-OUT SHEET GENERAL SPECIFIC-
 ATIONS NOTES STATES 2 JETS ON BENCH.
 POOL LAYOUT AND PIPING SCHEMATIC DOES
 NOT SHOW THESE JETS. PLEASE CLAIRFY.
 13) PIPING SCHEMATIC DOES NOT REFLECT
 THE POOL LAYOUT. THERE IS NO VACUUM LINE
 SHOWN ON SCHEMATIC. (VALVE REQD 424.2.8)
 14) NO VALVE SHOWN ON SKIMMER LINE. ALL
 SUCTION LINES SHALL HAVE VALVES INSTALL-
 ED PER SECTION 424.2.8.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-15 Time 08:46 Rev Time 1.00
Received By mmclean Date   Time   Sent To P
Notes
***NONE***