2003-07-31 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE SURVEY INCORRECTLY LISTS FLOOD |
| ZONE AS B. CITY RECORDS SHOW THAT THE |
| PROPERTY IS LOCATED IN AN "AO" FLOOD |
| ZONE. PLEASE CORRECT. AN ELEVATION |
| CERTIFICATE WILL BE REQUIRED. |
| |
| 3) FBC 1609.4 NO LONGER ALLOWS THE ONE- |
| THIRD INCREASE IN THE STEEL CALCULATIONS |
| FOR TRUSS CONNECTORS. THE TRUSS ANCHOR |
| SCHEDULE ON SHEET 2 LISTS INCORRECT |
| UPLIFT VALUES. PLEASE REVISE. |
| THE "USP" RT STRAPS REQUIRE THE NAILS TO |
| BE EQUALLY DISTRIBUTED ON BOTH SIDES OF |
| THE CONNECTION. SEE 2003 USP CATALOG. |
| |
| 4) SHEET 2 WHICH CONTAINS STRUCTURAL |
| INFORMATION AND THE ENGINEER'S TITLE |
| BLOCK IS NOT SIGNED AND SEALED BY THE |
| ENGINEER. FAC 61G15-23.002 |
| |
| 5) PLEASE REVISE DETAIL 1 ON SHEET 4. |
| THE BUCK IS REQUIRED TO EXTEND BEYOND |
| THE INTERIOR FACE OF THE WINDOW OR DOOR |
| FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.) |
| |
| 6) SPECIFY THE SIZE OF THE COLUMN AT THE |
| REAR PORCH. |
| |
| 7) SPECIFY THE CONNECTOR FOR THE WOOD |
| BEAM AT THE REAR PORCH WHERE IT CONNECTS |
| TO THE WALL AT THE MASTER BEDROOM. |
| |
| 8) THE ENERGY CALCULATIONS DO NOT STATE |
| THAT THEY ARE WORST CASE AND THEREFORE |
| CAN NOT BE USED GENERICALLY, DUE TO THE |
| DIFFERENT ORIENTATIONS OF THE STRUCTURES |
| ON THE LOTS. PLEASE CORRECT. SEE FBC |
| CHAPTER 13. |
| |
| 9) THE NORANDEX SITE SPECIFIC PRODUCT |
| APPROVALS ARE REQUIRED TO BE SEALED BY |
| THE DESIGNER OF RECORD. THE ENGINEER'S |
| NAME, ADDRESS AND NUMBER ARE REQUIRED TO |
| BE ON THE FORM. SEE FAC 61G15-23.002. |
| |
| 10) PLEASE REVIEW THE LISTED DESIGN |
| PRESSURES FOR THE GARAGE DOOR ON SHEET |
| 3C, THEY APPEAR TO BE INCORRECT. |
| |
| 11) THE PRESSURES FOR THE GARAGE DOOR ON |
| SHEET 3A ARE BOTH NGATIVE. PLEASE |
| CORRECT. |
| |
| 12) THE PRODUCT APPROVALS FOR THE STORM |
| PANELS ARE ILLEGIBLE AND TH CIRCLED |
| INSTALLATION INFORMATION DOES NOT APPEAR |
| DOES NOT APPEAR TO CORRESPOND WITH THE |
| STORM PANEL CONNECTION DETAILS ON SHEET |
| 2 OF THE PLANS. THE STORM PANEL DRAWINGS |
| ARE STAMPED FOR ONE PERMIT ONLY. AN |
| ORIGINAL SIGNED AND SEALED COPY OF THE |
| DRAWING IS REQUIRED. SUBMIT KEY PLAN AND |
| INSTALLATION SCHEDULE. |
| |
| 13) THE PRODUCT APPROVAL FOR THE OUT- |
| SWING DOOR WITH SIDELITE IS ILLEGIBLE. |
| SUBMIT CLEAR COPIES. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |