Plan Review Details - Permit 03070443
Plan Review Stops For Permit 03070443
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-24 Cont ID  
Sent By rmcdouga Date 2003-09-24 Time 14:32 Rev Time 3.00
Received By rmcdouga Date 2003-09-24 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-16 Time 11:57 Rev Time 2.00
Received By rmcdouga Date 2003-09-08 Time 13:47 Sent To  
Notes
2003-09-08 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SURVEY INDICATES THE STRUCTURE IS
 LOCATED IN A "B" ZONE. THE CITY'S RECORD
 INDICATES THAT IT IS IN AN "AO" ZONE.
 PLEASE CORRECT THE SURVEY.
  
 3) SHEET 2 OF THE PLANS CONTAINS
 STRUCTURAL INFORMATION AND THE TITLE
 BLOCK OF THE ENGINEER. THE ENGINEER IS
 REQUIRED TO SIGN AND SEAL THIS SHEET.
 SEE FAC 61G15-23.002.
  
 4) THE REVISED DETAIL 1 ON SHEET 4, IS
 STILL INCORRECT. FBC 1707.4.4.2 REQUIRES
 THE BUCK TO EXTEND BEYOND THE INTERIOR
 FACE OF THE WINDOW OR DOOR FRAME SUCH
 THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED.
  
 5) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SEALED BY
 THE DESIGNER OF RECORD. IF THE DESIGNER
 OF RECORD DOES NOT WISH TO SEAL THE FORM
 A SIGNED AND SEALED LETTER FROM THE
 DESIGNER SPECIFYING THE PRODUCT AND THE
 LOCATION OF THE STRUCTURE, STATING THAT
 THE PRODUCT HAS BEEN REVIEWED AND IS
 ACCEPTABLE FOR USE IN THE STRUCTURE.
  
 6) THE PRODUCT APPROVAL FOR THE STORM
 PANELS ARE ILLEGIBLE. SUBMIT CLEAR
 COPIES. THE DRAWINGS FOR THE STORM
 PANELS HAVE A STAMP ON THEM THAT
 INDICATES THEY ARE FOR ONE PERMIT ONLY.
 THIS MEANS THAT A SIGNED AND SEALED
 COPY OF THE DRAWINGS IS REQUIRED FOR
 EACH PERMIT. SUBMIT A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS.
  
 7) THE PRODUCT APPROVAL FOR THE OUTSWING
 DOOR WITH A SIDELITE IS ILLEGIBLE.
 SUBMIT CLEAR COPIES ALONG WITH THE
 APPROVED DRAWINGS (# S-2188).
  
 IF YOU HAVE QUESTIONS, PLEASE CALL.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-31 Cont ID  
Sent By csiegber Date 2003-09-04 Time 15:48 Rev Time 4.00
Received By rmcdouga Date 2003-07-31 Time 14:32 Sent To  
Notes
2003-07-31 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SURVEY INCORRECTLY LISTS FLOOD
 ZONE AS B. CITY RECORDS SHOW THAT THE
 PROPERTY IS LOCATED IN AN "AO" FLOOD
 ZONE. PLEASE CORRECT. AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 3) FBC 1609.4 NO LONGER ALLOWS THE ONE-
 THIRD INCREASE IN THE STEEL CALCULATIONS
 FOR TRUSS CONNECTORS. THE TRUSS ANCHOR
 SCHEDULE ON SHEET 2 LISTS INCORRECT
 UPLIFT VALUES. PLEASE REVISE.
 THE "USP" RT STRAPS REQUIRE THE NAILS TO
 BE EQUALLY DISTRIBUTED ON BOTH SIDES OF
 THE CONNECTION. SEE 2003 USP CATALOG.
  
 4) SHEET 2 WHICH CONTAINS STRUCTURAL
 INFORMATION AND THE ENGINEER'S TITLE
 BLOCK IS NOT SIGNED AND SEALED BY THE
 ENGINEER. FAC 61G15-23.002
  
 5) PLEASE REVISE DETAIL 1 ON SHEET 4.
 THE BUCK IS REQUIRED TO EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.)
  
 6) SPECIFY THE SIZE OF THE COLUMN AT THE
 REAR PORCH.
  
 7) SPECIFY THE CONNECTOR FOR THE WOOD
 BEAM AT THE REAR PORCH WHERE IT CONNECTS
 TO THE WALL AT THE MASTER BEDROOM.
  
 8) THE ENERGY CALCULATIONS DO NOT STATE
 THAT THEY ARE WORST CASE AND THEREFORE
 CAN NOT BE USED GENERICALLY, DUE TO THE
 DIFFERENT ORIENTATIONS OF THE STRUCTURES
 ON THE LOTS. PLEASE CORRECT. SEE FBC
 CHAPTER 13.
  
 9) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SEALED BY
 THE DESIGNER OF RECORD. THE ENGINEER'S
 NAME, ADDRESS AND NUMBER ARE REQUIRED TO
 BE ON THE FORM. SEE FAC 61G15-23.002.
  
 10) PLEASE REVIEW THE LISTED DESIGN
 PRESSURES FOR THE GARAGE DOOR ON SHEET
 3C, THEY APPEAR TO BE INCORRECT.
  
 11) THE PRESSURES FOR THE GARAGE DOOR ON
 SHEET 3A ARE BOTH NGATIVE. PLEASE
 CORRECT.
  
 12) THE PRODUCT APPROVALS FOR THE STORM
 PANELS ARE ILLEGIBLE AND TH CIRCLED
 INSTALLATION INFORMATION DOES NOT APPEAR
 DOES NOT APPEAR TO CORRESPOND WITH THE
 STORM PANEL CONNECTION DETAILS ON SHEET
 2 OF THE PLANS. THE STORM PANEL DRAWINGS
 ARE STAMPED FOR ONE PERMIT ONLY. AN
 ORIGINAL SIGNED AND SEALED COPY OF THE
 DRAWING IS REQUIRED. SUBMIT KEY PLAN AND
 INSTALLATION SCHEDULE.
  
 13) THE PRODUCT APPROVAL FOR THE OUT-
 SWING DOOR WITH SIDELITE IS ILLEGIBLE.
 SUBMIT CLEAR COPIES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-18 Cont ID  
Sent By dpalmer Date 2003-07-18 Time 16:23 Rev Time 0.33
Received By dpalmer Date 2003-07-18 Time 16:23 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-16 Time 11:57 Rev Time 0.00
Received By csiegber Date 2003-09-16 Time 11:57 Sent To B
Notes
2003-09-16 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 15:48 Rev Time 0.00
Received By csiegber Date 2003-09-04 Time 15:48 Sent To B
Notes
2003-09-04 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-08 Cont ID  
Sent By mmclean Date 2003-07-11 Time 13:05 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 11:05 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-26 Cont ID  
Sent By pkrauss Date 2003-07-26 Time 11:54 Rev Time 0.25
Received By pkrauss Date 2003-07-26 Time 11:54 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By rmcdouga Date 2003-09-24 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2003-09-24 Time 14:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-29 Cont ID  
Sent By pkrauss Date 2003-07-26 Time 11:54 Rev Time 0.25
Received By jleech Date 2003-07-29 Time 20:10 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-08 Time 11:05 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***