Plan Review Details - Permit 03070117
Plan Review Stops For Permit 03070117
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By rbrown Date 2003-09-02 Time 14:46 Rev Time 0.00
Received By rbrown Date 2003-09-02 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By rbrown Date 2003-08-07 Time 08:04 Rev Time 0.00
Received By rbrown Date 2003-08-07 Time 08:04 Sent To  
Notes
2003-08-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 11-4.17.6 TOILET STALL GRAB BARS,
 SHEET A-1.1.THE GRAB BAR ON THE SIDE
 WALL SHALL BE MIN. 42" LONG AND
 POSITIONED SO THAT THE FRONT END IS
 MIN. 54" FROM THE REAR WALL.AMEND THE
 PLAN VIEW OF 'TYPICAL H.C. RESTROOM'
 (REF. FIG. 29).
  
 2) FBC 11-4.19ACCESSIBLE LAVATORIES,
 SHEET A-1.1.THE RIM OF THE LAVATORY
 SHALL BE NO HIGHER THAN 34" ABOVE
 FINISHED FLOOR LEVEL.THE HOT WATER AND
 DRAIN PIPES UNDER THE LAVATORIES SHALL
 BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT.ANNOTATE THE
 'TYPICAL H.C. RESTROOM' ELEVATION TO
 DEMONSTRATE COMPLIANCE (REF. FIG. 31).
  
 3) FBC 11-4.24BREAK ROOM, SHEET A-1.0.
 THE BREAK ROOM SINK SHALL BE MOUNTED
 WITH THE RIM NO HIGHER THAN 34" ABOVE
 FINISHED FLOOR LEVEL WITH KNEE CLEARANCE
 AT LEAST 27" HIGH, 30" WIDE AND 19" DEEP
 UNDER THE SINK.THE SINK SHALL BE MAX.
 6-1/2" DEEP.ANY EXPOSED HOT WATER AND
 DRAIN PIPES SHALL BE INSULATED OR
 OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.ANNOTATE THE BREAK ROOM PLAN
 TO DEMONSTRATE COMPLIANCE.
  
 4) FBC 11-4.8.7NEW CONCRETE RAMP AND
 LANDING.THE RAMP AND LANDING SHALL
 HAVE CURBS (MIN. 2" HIGH - FIG. 17),
 WALLS, RAILINGS OR PROJECTING SURFACES
 AS EDGE PROTECTION.THE REQUIRED 18"
 CLEARANCE SHOWN BETWEEN THE EDGE OF THE
 LANDING AND THE LEADING EDGE OF THE DOOR
 SHALL BE ADJUSTED AS NECESSARY TO
 MAINTAIN MIN. 18" CLEAR BETWEEN THE
 CURB, WALL ETC AND THE LEADING EDGE OF
 THE DOOR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-29 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 18:40 Rev Time 0.75
Received By dpalmer Date 2003-09-29 Time 18:40 Sent To  
Notes
2003-09-29 00:00:00************** NOTES/REVISION *********
  
 1)NOTE: PLEASE SEE THAT NOTE #1 FROM
 FIRST REVIEW WAS NOT FULLY ADDRESSED.
 PLANS REDLINED FOR COMPLIANCE W/ 700.12E
  
  
 PLEASE SUBMIT THE ABOVE REVISED PLANS
 AND ANY OTHER ITEMS REVISED BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 08:26 Rev Time 0.50
Received By dpalmer Date 2003-07-17 Time 06:12 Sent To  
Notes
2003-07-17 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE W/ PANEL SCHEDULE(S).
 PLEASE CLARIFY NOTE MENTION ALL FIXTURES
 BEING FED THROUGH CONTACTOR EXCEPT
 NIGHT LITES. ? EXIT AND EM LT WON'T BE
 FED THIS WAY? PLEASE SEE 700-12E FOR
 CIRCUITING THESE FIXTURES.
  
 2)NOTE: PLEASE SHOW RECEPTS FOR ROOFTOP
 EQUIPMENT AS GFI. 210-63/210-8
  
 3)NOTE: PLEASE SHOW MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAINS AND
 PANELS. 250-110/250-122
  
 4)NOTE: PLEASE SHOW AIC RATINGS FOR ALL
 NEW EQUIPMENT BEING INSTALLED. MAINS/
 PANELS/BRKRS ARE ALL TO BE RATED FOR THE
 AVAILABLE FUALT CURRENT. 110-9
  
 5)NOTE: PLEASE SHOW SIZING OF CONDUCTORS
 FROM GUTTER TO MAINS.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-05 Cont ID  
Sent By mcarsill Date 2003-09-05 Time 16:08 Rev Time 0.00
Received By mcarsill Date 2003-09-05 Time 16:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By mcarsill Date 2003-07-17 Time 16:02 Rev Time 0.00
Received By mcarsill Date 2003-07-17 Time 16:02 Sent To  
Notes
2003-07-17 00:00:001) NEW HANDICAPPED RAMP REQUIRES
 HANDRAILS ON BOTH SIDES.
  
 2) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 3) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-28 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 08:25 Rev Time 0.00
Received By dbaxter Date 2003-08-28 Time 08:25 Sent To E
Notes
2003-08-28 00:00:00TO COMM BD. #10.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 15:55 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 15:55 Sent To  
Notes
2003-07-07 00:00:00COMM BOARD #28

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By pkrauss Date 2003-09-24 Time 10:36 Rev Time 0.35
Received By pkrauss Date 2003-09-24 Time 10:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-15 Cont ID  
Sent By pkrauss Date 2003-07-15 Time 11:01 Rev Time 0.40
Received By pkrauss Date 2003-07-15 Time 11:01 Sent To  
Notes
2003-07-15 00:00:00DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3.
  
 2.EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS AS PER 2001 FBC(M) 401.5.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-30 Cont ID  
Sent By kstevens Date 2003-09-30 Time 13:36 Rev Time 1.00
Received By kstevens Date 2003-09-30 Time 13:36 Sent To  
Notes
2003-09-30 00:00:00PASSED/PROVISO
  
 DOOR SHALL NOT SWING INTO CLEAR FLOOR
 SPACE OR TURNING CIRCLE 11-4.22.2
 TOILET ROOM BY BREAK ROOM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By kstevens Date 2003-07-17 Time 12:51 Rev Time 0.75
Received By kstevens Date 2003-07-17 Time 12:51 Sent To  
Notes
2003-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHOW CLEAR FLOOR SPACE FOR ALL HDCP
 FIXTURES. W/C'S 11-4.16.2, LAV'S 4.19.3,
 URNAL 4.18.3, BRK RM SINK 4.24.5.
 2) SUBMIT DETAIL FOR BREAK ROOM SINK.
 SHOW COMPLIANCE WITH 11-4.24 AND ALL
 SUBSECTIONS.
 3) DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF THE TURNING CIRCLE. SEC
 11-4.22.2. (TOILET ROOM BY BRK RM)
 4) SHOW TURNING CIRCLES IN TOILET ROOMS.
 THEY ARE NOT REQUIRED IN STALLS. SECTION
 11-4.22.3
 5) SHTS A-3.0 & A-3.2, SANITARY PLUMBING
 PLAN AND SANITARY RISER DIAGRAM. SECTION
 909.1, ONLY THE FIXTURES WITHIN THE BATH
 ROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. - THE BREAK
 ROOM SINK SHALL TIE IN DOWNSTREAM OF THE
 BATHROOM GROUP.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692