Plan Review Details - Permit 03070026
Plan Review Stops For Permit 03070026
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-22 Cont ID  
Sent By btrobaug Date 2003-10-22 Time 15:24 Rev Time 0.33
Received By btrobaug Date 2003-10-22 Time 15:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By btrobaug Date 2003-10-09 Time 13:46 Rev Time 1.00
Received By btrobaug Date 2003-10-09 Time 13:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-14 Cont ID  
Sent By csiegber Date 2003-10-07 Time 16:02 Rev Time 0.50
Received By btrobaug Date 2003-07-14 Time 15:14 Sent To  
Notes
2003-07-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CLARIFY THE SCOPE OF WORK.IF
 THERE IS TO BE A NEW SERVICE PROVIDE
 CALCULATIONS,PANEL SCHEDULES,AIC
 RATINGS PER 110-9 AND A RISER DIAGRAM.
  
 INDICATE WHICH WORK ON THE FLOOR PLAN IS
 NEW AND WHICH IS EXISTING.IF REWIRING
 ADD SMOKE DETECTORS PER NFPA-72.
  
 PLEASE ADDRESS THESE COMMENTS AND
 RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-07 Time 16:02 Rev Time 0.00
Received By csiegber Date 2003-10-07 Time 16:02 Sent To E
Notes
2003-10-07 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 15:52 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 15:52 Sent To E
Notes
***NONE***