Plan Review Details - Permit 03062223
Plan Review Stops For Permit 03062223
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-06-30 Time 16:08 Rev Time 0.00
Received By rbrown Date 2003-07-01 Time 11:26 Sent To FIRE
Notes
2003-07-01 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 FBC 1204.2BATHROOM WALL TILE.THE
 'SCOPE' ON THE PLAN REFERS TO REMOVAL OF
 WALL TILE IN BOTH BATHROOM.THE TILE
 SHALL NOT BE REMOVED UNLESS THE WALLS
 ARE LINED WITH NON-ABSORBENT MATERIAL
 (E.G. NEW TILE) TO A HEIGHT OF 4 FT
 ABOVE THE FLOOR.
  
 --PROVISO--
 FBC 11-4.13.6THE DOOR TO THE TRAINING
 ROOM SHALL HAVE AT LEAST 18" CLEARANCE
 BETWEEN THE LEADING EDGE OF THE DOOR AND
 ADJACENT PERPENDICULAR WALL ON THE PULL-
 SIDE AND 12" CLEARANCE BETWEEN THE DOOR
 AND THE ADJACENT WALL ON THE PUSH-SIDE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-01 Cont ID  
Sent By rbrown Date 2003-07-01 Time 12:05 Rev Time 0.00
Received By nmccray Date 2003-07-01 Time 15:14 Sent To  
Notes
2003-07-01 00:00:00***************PROVISO******************
 THE INTERIOR WALL FINISH SHALL BE CLASS
 A OR CLASS B.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-06-30 Time 16:08 Rev Time 0.00
Received By shernand Date 2003-06-30 Time 16:08 Sent To B
Notes
2003-06-30 00:00:00RBROWN DESK PER REQUEST.