Plan Review Details - Permit 03062006
Plan Review Stops For Permit 03062006
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-09 Cont ID  
Sent By dpalmer Date 2003-07-08 Time 16:36 Rev Time 0.50
Received By lsmith Date 2003-07-09 Time 10:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-22 Cont ID  
Sent By dpalmer Date 2003-07-22 Time 07:36 Rev Time 0.25
Received By dpalmer Date 2003-07-22 Time 07:36 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-18 Time 09:50 Rev Time 0.25
Received By dpalmer Date 2003-07-08 Time 16:36 Sent To B
Notes
2003-07-08 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS,
 SHOWING ALL NEW EQUIPMENT BEING ADDED.
 PLEASE INCLUDE HEAT PUMP ETC AND ANY
 EXISTING LOADS.
 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-18 Cont ID  
Sent By shernand Date 2003-07-18 Time 09:50 Rev Time 0.00
Received By shernand Date 2003-07-18 Time 09:50 Sent To E
Notes
2003-07-18 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-27 Cont ID  
Sent By mmclean Date 2003-07-01 Time 11:05 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 15:57 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-24 Cont ID  
Sent By kstevens Date 2003-07-24 Time 09:51 Rev Time 1.00
Received By kstevens Date 2003-07-23 Time 18:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-03 Cont ID  
Sent By dpalmer Date 2003-07-22 Time 07:36 Rev Time 1.00
Received By kstevens Date 2003-07-03 Time 15:37 Sent To E
Notes
2003-07-03 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5 (ADD TO NOTES)
 2) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-06-27 Time 15:57 Rev Time 1.00
Received By mmclean Date   Time   Sent To P
Notes
***NONE***