Plan Review Details - Permit 03061862
Plan Review Stops For Permit 03061862
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-07 Cont ID  
Sent By jwitmer Date 2004-06-07 Time 13:00 Rev Time 2.55
Received By jwitmer Date 2004-06-07 Time 13:00 Sent To PC
Notes
2004-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061862
 ADD: 819 HANSEN ST
 CONT:SJE DESIGN & CONSTRUCTION
 TEL: (561)478-5670
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED, EXPIRED, NO WORK WITHIN
 6 MONTHS
  
 NOTE: THE ELECTRIC / BUILDING REVIEWS
 HAVE BEEN COMPLETED BUT A NEW PERMIT
 WILL HAVE TO BE APPLIED FOR, WPB
 ADMINISTRATIVE CODE 104.1.6 TIME LIMIT-
 ATIONS.
  
 1) PLANS ARE TO INDIATE WHAT CRITERIA
 THE BUILDING IS TO BE BUILT:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 THE TRUSS DESIGN CRITERIA HAS THIS INFOR
 MATION, BUT NO WHERE DOES THE STRUCTURE
 INDICATE THE SAME CRITERIA WAS USED.
  
 IN THE TRUSS DESIGN CRITERIA NO BOTTOM
 CHORD LIVE LOAD IS GIVEN, TABLE 1604.1
 ATTICS WITHOUT STORAGE REQUIRE 10 LBS.
  
 2)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 3) PRODUCT APPROVALS: SINCE THE NEWLY
 APPLIED FOR PERMIT WILL HAVE A DATE
 AFTER OCT.1 2003 THE STATEWIDE PRODUCT
 APPROVAL SYSTEM IS IN AFFECT.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) SOME PRODUCT APPROVALS SUBMITTED ARE
 DUPLICATE FOR THE SAME USE, ROOFING
 PULL THE REPORT NOT TO BE USED.
  
 5) UNDER THE NEW STATEWIDWE PRODUCT
 APPROVAL SYSTEM THE TRUSS ANCHORS ARE
 ALSO REQUIRED TO HAVE THE STATE LISTING.
 ONCE YOU HAVE THE PRODUCT APPROVALS AND
 STATE LISTING HIGHLIGHT EACH ANCHOR TO
 BE USED.
  
 6) THERE HAS BEEN NO PRODUCT TESTING
 REPORT FOR THE GARAGE DOOR.
  
 7) STORM SHUTTERS PROVIDE THE FOLLOWING:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.SEE SAMPLE ATTACHED.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.ALSO WILL RE
 QUIRE STATE APPROVAL.
  
 9)2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 10)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-15 Cont ID  
Sent By btrobaug Date 2004-05-28 Time 11:41 Rev Time 1.50
Received By jwitmer Date 2003-09-15 Time 19:27 Sent To  
Notes
2003-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061862
 ADD: 819 HANSEN STREET
 CONT:SUINGLIO ESPEJO
 TEL: (561)305-0244
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
  
 1) THE FOURTH QUESTION FROM THE FIRST RE
 VIEW, SHEET A-1 SHOWS THAT THE CATEGORY
 ISTHEN THERE IS A "B" AND "C", EITHER
 CIRCLE OR "X" OUT THE ONE NOT USED.
 DO THE SAME FOR "SATUS"!!!!!!!!!!!!!
  
 2) SHEET A-2 NOT THE BOTTOM OF THE
 FOUNDATION TO BE 8" BELOW GRADE.WRONG!
 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SLIDING GLASS DOOR
 B) PAIR OF FRENCH DOORS W/ SIDELITES
  
 4) MISSING BEAM INFORMATION, NO LAYOUT
 OF BARS REQUIRED OR SIZE, STIRRUPS ETC?
 SAME COMMENT AS 1ST REVIEW!
  
 5) SECOND FLOOR ALSO MISSING INFORMATION
 AS TO WHAT MATERIAL IT IS MADE FROM?
 NO 2ND STORY FRAMING PLAN, THE SECTION
 PROVIDED FOR FIRST FLOOR REFER TO BOND
 BEAM SCHEDULE? WHERE?
 STRAPING NOTE SEE DETAIL 1/S2? WHERE?
 SAME COMMENTS FROM 1ST REVIEW!!!
 UPLIFT STRAPS FEFER TO ROOF FRAMING
 PLAN? WHERE?
 ROOF NAILING NOT TO CITY W. P. B.
 TABLE 2306.1 6" EDGE/ 6" INTERMEDIATES!
  
 6) 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 INDICATE ON THE ROOF FRAMING PLAN THIS
 INFORMATION.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 7) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 8) PROVIDE (2) COPIES OF ENERGY SHEETS,
 ALL PRODUCT APPROVALS TO BE SUBMITTED.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 PLANS REQUIRE COUNTY STAMP REVIEWED!!!!!
  
 10)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-28 Cont ID  
Sent By pkrauss Date 2003-09-02 Time 13:50 Rev Time 1.50
Received By jwitmer Date 2003-07-28 Time 17:24 Sent To  
Notes
2003-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061862
 ADD: 819 HANSEN STREET
 CONT: SUINGLIO ESPEJO
 TEL: (561)305-0244
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 THIS BUILDING IS INDICATING BEING DESIGN
 ED FOR BOTH A B & C CATEGORY, AND AS
 OPEN OR ENCLOESED. AS STATED IN (5)
 ABOVE INCLUDE THE POS. & NEGATIVE WIND
 PRESSURES FOR THE MOST RESTRICTIVE.
 MISSING IS THE INTERNAL PRESSURE
 COEFFICIENT.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SLIDING GLASS DOORSIN THE KITCHEN &
 FAMILY ROOM.
 B) ROOFING REPORTS FOR CLAY TILE &
 SHINGLES? BOTH ARE IN PACKAGE.
  
 6) MISSING BEAM INFORMATION, NO LAYOUT
 OF NUMBER OF BARS REQUIRED, SIZE OR IF
 STIRRUPS ARE REQUIRED?
  
 7) SECOND FLOOR ALSO MISSING INFORMATION
 AS TO WHAT MATERIAL IT IS MADE FROM?
 NO CUT SECTION GIVING INFORMATION. IF
 WOOD NO ANCHOR BOLT INFO., NO STAPPING
 OF STUDS, OR STUDS TO TO TRUSSES.
  
 8)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 9) MISSING INFORMATION OF TRUSSES, NO
 TRUSS LAYOUT GIVINGUPLIFT PRESSURE.
 1606.2.4 MAIN WIND FORCE RESISTING SYS-
 TEM, ALL ELEMENTS AND CONNECTIONS OF THE
 MAINFORCE RESISTING SYSTEM SHALL BE
 DESIGNED FOR VERTICAL AND HORIZONTAL
 LOADS BASED ON THE COMBINED LEEWARD AND
 WINDWARD WALL PRESSURES AND ROOF PRES
 SURES DETERMINED FROM TABLE 1606.2A.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-05-28 Cont ID  
Sent By btrobaug Date 2004-05-28 Time 11:41 Rev Time 0.50
Received By btrobaug Date 2004-05-28 Time 10:54 Sent To B
Notes
2004-05-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3. 20 AMP.
  
 2} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 3} THE SMALL APPLIANCE CIRCUITS MUST BE
 20 AMP #12 WIRE PER 210.52(B)(1), ALSO
 THE DINING ROOM, SAME ARTICLE.
  
 4} THERE MUST BE A RECEPTACLE ADDED TO
 THE KITCHEN COUNTERTOP TO COMPLY WITH
 210.52(C)(1).
  
 5} THE SMOKE DETECTOR IN THE UPSTAIR
 HALL MUST BE 3'FROM THE BATH DOOR. SEE
 8-1.4.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-08-26 Cont ID  
Sent By csiegber Date 2004-05-27 Time 13:10 Rev Time 1.00
Received By btrobaug Date 2003-08-22 Time 10:03 Sent To M
Notes
2003-08-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} ENGINEERS # MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002(2).
  
 2} CHANGES TO ENGINEERED PLANS MUST BE
 MADE BY THE ENGINEER OF RECORD,AND
 INITIALED BY SAME.THE CHANGES TO THIS
 PLAN AND CALCULATIONS RENDER PARTS OF
 IT ILLEGIBLE.PLEASE REDRAW THE PLANS
 LEAVING ONLY PERTINENT INFORMATION PER
 104.2.1 FBC & LOCAL AMMENDMENTS.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE NOTE PER 250.50 ALL ITEMS
 AVAILABLE MUST BE USED TO FORM THE GEC
 SYSTEM.IG: FOOTER STEEL & CWP.
  
 5} PLEASE RECALCULATE THE LOAD PER
 ARTICLE 220.THE SERVICE APPEARS TO BE
 TOO SMALL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-15 Cont ID  
Sent By dbaxter Date 2003-08-15 Time 13:28 Rev Time 0.50
Received By btrobaug Date 2003-07-15 Time 11:23 Sent To P
Notes
2003-07-15 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.ALSO PLEASE
 INITIAL ALL CHANGES.
  
 PLEASE NOTE THAT THE GROUNDING ELECTRODE
 SYSTEM MUST USE ALL ITEMS AVAILABLE PER
 250-50(A)-(D).
  
 PLEASE SHOW ALL WIRE AND BREAKER SIZES
 ON THE PANEL SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-05-27 Time 13:10 Rev Time 0.00
Received By csiegber Date 2004-05-27 Time 13:09 Sent To E
Notes
2004-05-27 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-15 Cont ID  
Sent By dbaxter Date 2003-08-15 Time 13:28 Rev Time 0.00
Received By dbaxter Date 2003-08-15 Time 13:28 Sent To E
Notes
2003-08-15 00:00:00TO BTROBAUGH DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-15 Time 10:01 Rev Time 0.00
Received By shernand Date 2003-07-15 Time 10:01 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-11 Cont ID  
Sent By mmclean Date 2003-07-14 Time 12:45 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 16:50 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-26 Cont ID  
Sent By mmclean Date 2003-07-01 Time 09:19 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 10:49 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-09-02 Cont ID  
Sent By pkrauss Date 2003-09-02 Time 13:49 Rev Time 0.20
Received By pkrauss Date 2003-09-02 Time 13:49 Sent To B
Notes
2003-09-02 00:00:00MECHANICAL PERMIT REQUIRED.
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW. ENERGY AND MANUAL J CALCULATIONS
 ONLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-15 Cont ID  
Sent By btrobaug Date 2003-08-26 Time 10:54 Rev Time 0.25
Received By hmoser Date 2003-07-15 Time 17:41 Sent To B
Notes
2003-07-15 00:00:00MECHANICAL CONTRACTOR MUST HAVE
 ENERGY CALCULATIONS,MANUAL (J),AND PLANS
 WITH APPLICATION
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-15 Cont ID  
Sent By pkrauss Date 2003-09-02 Time 13:50 Rev Time 0.33
Received By jleech Date 2003-07-15 Time 17:11 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-07-14 Cont ID  
Sent By mmclean Date 2003-07-14 Time 12:45 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:50 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-07-01 00:00:006/30/2003 DENIED, NEED 2 COPY OF SURVEY
 CALLED CONTR MM