Plan Review Details - Permit 03061730
Plan Review Stops For Permit 03061730 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2003-07-14 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-07-21 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2003-07-12 |
Time |
12:58 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-07-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-07-18 |
Time |
15:53 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2003-07-18 |
Time |
15:53 |
Sent To |
FIRE |
|
Notes |
2003-07-18 00:00:00 | ************* REVISION/PROVISO ****** | | | | 1)NOTE: PLANS ARE STILL NOT CLEAR FOR | | ALL ITEMS THAT ARE NEW AND WHICH IS | | EXISTING. CONTRACTOR MENTIONS MANY ITEMS | | AS EXISTING AND PLANS SHOW AS NEW. | | PLEASE HAVE PLANS COMPLETELY REVISED TO | | SHOW WHAT IS NEW AND WHAT IS EXISTING. | | PLEASE SEE THAT UNDER ADMIM CODE VALUE | | FOR SCOPE OF WORK SHOULD BE INCREASED | | EVEN IF OWNER SUPPIED. 104.6.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-07-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-18 |
Time |
08:42 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-07-07 |
Time |
11:51 |
Sent To |
|
|
Notes |
2003-07-07 00:00:00 | ************ UNSAT *************** | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITS ON | | PLANS AND CORRELATE W/ THE SUBMITTED | | PANEL SCHEDULE. ALSO SEE 700-12E | | | | 2)NOTE: PLEASE CLARFIY NEW OR EXISTING | | SHOW WINDOW RECEPTS. 210-62 | | | | 3)NOTE: | | | | | | 4)NOTE: PLEASE SEE 220-12 FOR TRACK | | LIGHTING LOAD CALCS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-07-21 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-07-21 |
Time |
14:03 |
Sent To |
B |
|
Notes |
2003-07-21 00:00:00 | *************PROVISO******************** | | THE CURTAINS SHALL BE FIRE RETARDANT | | TREATED. PLEASE PROVIDE PROOF FOR THE | | FIRE INSPECTOR. | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2003-07-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-07-18 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-07-16 |
Time |
14:00 |
Sent To |
|
|
Notes |
2003-07-16 00:00:00 | 1) NO EXIT SIGNS AND EMERGENCY LIGHTS | | SHOWN. | | | | 2) NO INTERIOR FINISH CLASSIFICATION | | NOTED ON PLANS. | | | | 3) DRESSING ROOM DOORS OPEN INFRONT | | OF EXIT DOORS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-07-18 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-18 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-18 |
Time |
08:42 |
Sent To |
E |
|
Notes |
2003-07-18 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-06-24 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-24 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-24 |
Time |
16:45 |
Sent To |
|
|
Notes |
2003-06-24 00:00:00 | COMM BOARD #18 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2003-07-22 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-07-22 |
Time |
12:28 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|