Plan Review Details - Permit 03061730
Plan Review Stops For Permit 03061730
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-14 Cont ID  
Sent By nmccray Date 2003-07-21 Time 14:04 Rev Time 0.00
Received By hpiskura Date 2003-07-12 Time 12:58 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-18 Cont ID  
Sent By dpalmer Date 2003-07-18 Time 15:53 Rev Time 1.00
Received By dpalmer Date 2003-07-18 Time 15:53 Sent To FIRE
Notes
2003-07-18 00:00:00************* REVISION/PROVISO ******
  
 1)NOTE: PLANS ARE STILL NOT CLEAR FOR
 ALL ITEMS THAT ARE NEW AND WHICH IS
 EXISTING. CONTRACTOR MENTIONS MANY ITEMS
 AS EXISTING AND PLANS SHOW AS NEW.
 PLEASE HAVE PLANS COMPLETELY REVISED TO
 SHOW WHAT IS NEW AND WHAT IS EXISTING.
 PLEASE SEE THAT UNDER ADMIM CODE VALUE
 FOR SCOPE OF WORK SHOULD BE INCREASED
 EVEN IF OWNER SUPPIED. 104.6.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-18 Time 08:42 Rev Time 0.50
Received By dpalmer Date 2003-07-07 Time 11:51 Sent To  
Notes
2003-07-07 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITS ON
 PLANS AND CORRELATE W/ THE SUBMITTED
 PANEL SCHEDULE. ALSO SEE 700-12E
  
 2)NOTE: PLEASE CLARFIY NEW OR EXISTING
 SHOW WINDOW RECEPTS. 210-62
  
 3)NOTE:
  
  
 4)NOTE: PLEASE SEE 220-12 FOR TRACK
 LIGHTING LOAD CALCS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By nmccray Date 2003-07-21 Time 14:03 Rev Time 0.00
Received By nmccray Date 2003-07-21 Time 14:03 Sent To B
Notes
2003-07-21 00:00:00*************PROVISO********************
 THE CURTAINS SHALL BE FIRE RETARDANT
 TREATED. PLEASE PROVIDE PROOF FOR THE
 FIRE INSPECTOR.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-16 Cont ID  
Sent By dpalmer Date 2003-07-18 Time 16:02 Rev Time 0.00
Received By mcarsill Date 2003-07-16 Time 14:00 Sent To  
Notes
2003-07-16 00:00:001) NO EXIT SIGNS AND EMERGENCY LIGHTS
 SHOWN.
  
 2) NO INTERIOR FINISH CLASSIFICATION
 NOTED ON PLANS.
  
 3) DRESSING ROOM DOORS OPEN INFRONT
 OF EXIT DOORS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-18 Cont ID  
Sent By shernand Date 2003-07-18 Time 08:42 Rev Time 0.00
Received By shernand Date 2003-07-18 Time 08:42 Sent To E
Notes
2003-07-18 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-24 Cont ID  
Sent By shernand Date 2003-06-24 Time 16:45 Rev Time 0.00
Received By shernand Date 2003-06-24 Time 16:45 Sent To  
Notes
2003-06-24 00:00:00COMM BOARD #18

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-22 Cont ID  
Sent By hpiskura Date 2003-07-22 Time 12:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***