Plan Review Details - Permit 03061290
Plan Review Stops For Permit 03061290
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-07 Cont ID  
Sent By jwitmer Date 2003-08-07 Time 14:42 Rev Time 1.05
Received By jwitmer Date 2003-08-07 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-14 Cont ID  
Sent By jwitmer Date 2003-07-14 Time 07:43 Rev Time 0.75
Received By jwitmer Date 2003-07-14 Time 07:43 Sent To  
Notes
2003-07-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061290
 ADD: 2491 OKEECHOBEE BLVD SIUTE "E"
 CONT: LEIGHTEN MCGINN
 TEL: (561)722-9696
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 INFORMATION ON THE SECURITY GRILL, MAN-
 UFCTURERS SPEC. LBS/ FT
  
 2)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 PLANS INDICATE (1) NEW DOOR IN THE FRONT
 AND (1) NEW DOOR TO THE REAR.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) NEW FRONT DOOR GLAZED
 B) NEW REAR DOOR
  
 5) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By jwitmer Date 2003-07-07 Time 06:31 Rev Time 0.50
Received By jwitmer Date 2003-07-07 Time 06:31 Sent To  
Notes
2003-07-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061290
 ADD: 2491 OKEECHOBEE BLVD
 CONT: LEIGHTON MCGINN
 TEL: (561)722-9696
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 1025.1(3) SINGLE EXIT, MAXIMUM TRAVEL
 DISTANCE OF TRAVEL TO THE EXIT DOES NOT
 EXCEED 50 FT.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE ADDITIONAL INFORMATION ON SECUR-
 ITY GRILLE, MANUFACTURERS SPEC. LBS/ FT.
  
 3)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORT:
 A) FRONT ENTRY DOOR.
 B) LARGE MISSLEIMPACT TESTING FOR NEW
 DOOR OR STORM SHUTTER
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-06 Cont ID  
Sent By dpalmer Date 2003-08-06 Time 07:15 Rev Time 0.33
Received By dpalmer Date 2003-08-06 Time 07:15 Sent To  
Notes
2003-08-06 00:00:00*********** NOTE ************
 PLEASE STILL SEE REDLINE FOR 250-24
 PLEASE ALSO SEE NOTE FROM PREVIOUS
 REVIEW: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND HAVE TWO CLEAN COMPLETE SETS
 FOR REVIEWING AND STAMPING.
 OLD SHEETS TO BE SEPARATE AND ONLY ONE
 SET OF THOSE SHEETS MAY BE NEEDED BY
 OTHER PLAN REVIEWERS?
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-28 Cont ID  
Sent By dpalmer Date 2003-07-28 Time 10:24 Rev Time 0.33
Received By dpalmer Date 2003-07-28 Time 10:24 Sent To  
Notes
2003-07-28 00:00:00PLEASE TAKE OUT OLD/VOIDED SHEETS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-02 Cont ID  
Sent By dpalmer Date 2003-07-02 Time 07:56 Rev Time 0.33
Received By dpalmer Date 2003-07-02 Time 07:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-08-08 Cont ID  
Sent By nmccray Date 2003-08-08 Time 11:24 Rev Time 0.00
Received By nmccray Date 2003-08-08 Time 11:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-29 Cont ID  
Sent By mcarsill Date 2003-07-29 Time 17:24 Rev Time 0.00
Received By mcarsill Date 2003-07-29 Time 17:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-08 Cont ID  
Sent By nmccray Date 2003-07-08 Time 14:54 Rev Time 0.00
Received By nmccray Date 2003-07-08 Time 14:54 Sent To  
Notes
2003-07-08 00:00:00*************PROVISO********************
 SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 08:33 Rev Time 0.00
Received By alange Date 2003-07-31 Time 08:33 Sent To  
Notes
2003-07-31 00:00:00TO COMM BD #4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 15:23 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 15:23 Sent To  
Notes
2003-07-11 00:00:00COMM BOARD #2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-17 Cont ID  
Sent By shernand Date 2003-06-17 Time 16:20 Rev Time 0.00
Received By shernand Date 2003-06-17 Time 16:20 Sent To  
Notes
2003-06-17 00:00:00COMM BOARD #27

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-07 Time 11:00 Rev Time 0.40
Received By pkrauss Date 2003-07-07 Time 10:36 Sent To  
Notes
2003-07-07 00:00:00MECHANICAL PERMIT 03061294

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-26 Cont ID  
Sent By kstevens Date 2003-07-26 Time 08:21 Rev Time 0.33
Received By kstevens Date 2003-07-26 Time 08:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-02 Cont ID  
Sent By kstevens Date 2003-07-02 Time 16:50 Rev Time 0.50
Received By kstevens Date 2003-07-02 Time 16:50 Sent To  
Notes
2003-07-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 1, ADMIN. CODE
  
 1) SHT A-1 TABLE 403.1 A DRINKING FOUNT-
 AIN IS REQUIRED. SEE TABLE 410.1 ALSO.
 2) SHT A-2 SECTION 909.1 ONLY THE FIX-
 TURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. (SEE RED LINE CORRECTIONS SHT A-2)
 3) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692