Plan Review Details - Permit 03061112
Plan Review Stops For Permit 03061112
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-09 Cont ID  
Sent By dpalmer Date 2003-07-08 Time 14:24 Rev Time 0.50
Received By lsmith Date 2003-07-09 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-08 Cont ID  
Sent By kstevens Date 2003-07-07 Time 15:01 Rev Time 0.25
Received By dpalmer Date 2003-07-08 Time 14:24 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-15 Cont ID  
Sent By dbaxter Date 2003-08-15 Time 13:41 Rev Time 0.00
Received By dbaxter Date 2003-08-15 Time 13:41 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-23 Cont ID  
Sent By alange Date 2003-07-23 Time 10:31 Rev Time 0.00
Received By alange Date 2003-07-23 Time 10:31 Sent To P
Notes
2003-07-23 00:00:00TO KEN STEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 13:33 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 13:33 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-16 Cont ID  
Sent By shernand Date 2003-06-16 Time 15:28 Rev Time 0.00
Received By shernand Date 2003-06-16 Time 15:28 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-29 Cont ID  
Sent By kstevens Date 2003-07-29 Time 08:17 Rev Time 0.50
Received By kstevens Date 2003-07-29 Time 08:17 Sent To  
Notes
2003-07-29 00:00:00 
  
  
  
 FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By alange Date 2003-07-23 Time 10:31 Rev Time 0.50
Received By kstevens Date 2003-07-07 Time 14:54 Sent To E
Notes
2003-07-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 4) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-03 Cont ID  
Sent By dbaxter Date 2003-08-15 Time 13:41 Rev Time 1.00
Received By mmclean Date   Time   Sent To P
Notes
***NONE***