Plan Review Stops For Permit 03060960 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2003-07-02 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-07-02 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2003-07-02 |
Time |
11:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-08-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-08-05 |
Time |
10:33 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2003-08-05 |
Time |
10:33 |
Sent To |
|
|
Notes |
2003-08-05 00:00:00 | ************* PROVISO/REVISION ******* | | | | PLEASE SEE NOTES FROM FIRST AND SECOND | | REVIEW. | | | | 1)NOTE: PLEASE SUBMIT COMPLETE CIRCUIT- | | -ING AND CORRELATE WITH SUBMITTED PANEL | | SCHEDULES. PLEASE SEE TWO DIFFERENT | | SETS OF PANELS ARE SHOWN. | | | | 2)NOTE: PLEASE SEE MISSING REQ'D SIGN | | CIRCUIT PER 600-5. | | | | 3)NOTE: PLEASE SEE 700-12E FOR CIRCUIT- | | -ING OF EM/ EXT LTS. | | | | 4)NOTE; PLEASE SEE THAT CIRCUITS SHOWN | | ON PLANS DO NOT CORRELATE W/ PANELS, | | EXAMPLE, A-6 FOR GEN RECEPTS ARE SHOWN | | AS A WATER HEATER CIRCUIT?? | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | INFORMATION FOR REVIEW BEFORE ANY ROUGH | | ELECTRICAL INDSPECTION IS CALLED IN. | | IF THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | PLEASE SEE THAT THREE NEW PANEL SCHEDULE | | -S SHOWN ON PLANS HAVE BEEN STRIKED | | THROUGH. PLEASE SEE THAT THESE DO NOT | | MATCH AND NUMEROUS ITEMS ON SCHEDULES | | DO NOT HAVE CORRECT OCP/AWG/ FOR LOADS | | ETC. | | PLEASE SEE PROVISO SET FORTH. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-07-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-07-01 |
Time |
14:07 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-07-01 |
Time |
13:19 |
Sent To |
|
|
Notes |
2003-07-01 00:00:00 | *************** UNSAT ************* | | | | 1)NOTE: PLEASE CLARIFY PANEL SCHEDULES. | | SHOWS 1CIRCUIT FOR PANEL "C" AND | | YET PANELS B&A SHOW CIRCUITS ON PANEL | | SCHEDULE BUT DO NOT SHOW THESE SAME | | ITEMS ON PLANS? | | PLEASE CORRELATE PANEL SCHEDULES AND | | PLANS. | | PLEASE SEE COMMENTS FROM OTHER REVIEWS | | (FIRE) THAT WILL HAVE AN AFFECT ON | | ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2003-07-03 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2003-07-03 |
Time |
09:21 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-07-03 00:00:00 | SEE PLANS FOR FIRE APPROVALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-07-29 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-07-29 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2003-07-29 |
Time |
13:04 |
Sent To |
|
|
Notes |
2003-07-29 00:00:00 | TO COMM BD # 12 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-06-13 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-13 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-13 |
Time |
14:54 |
Sent To |
|
|
Notes |
2003-06-13 00:00:00 | COMM BOARD #25 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2003-07-03 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2003-07-03 |
Time |
09:25 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-07-03 00:00:00 | NO INFORMATION PROVIDED |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-08-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-08-08 |
Time |
09:56 |
Rev Time |
2.50 |
Received By |
kstevens |
Date |
2003-08-08 |
Time |
09:56 |
Sent To |
|
|
Notes |
2003-08-08 00:00:00 | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR CORRECTIONS TO | | SANITARY RISER DIAGRAMS & TO DELETE | | DRINKING FOUNTAIN AND ADD WATER COOLER | | PER ARCHITECT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-07-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-07-01 |
Time |
10:48 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2003-07-01 |
Time |
10:03 |
Sent To |
|
|
Notes |
2003-07-01 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | FBC-2001 AMENDMENTS CHAPTER 1 | | ADMIN. CODE | | | | 1) SUBMIT A SANITARY RISER DIAGRAM AND A | | WATER RISER DIAGARAM. SHOW ALL PIPE | | SIZES AND WATER HAMMER ARRESTORS LOCATED | | PER PDI-WH 201 AND MANUF INSTALL. INSTR. | | 104.2.1 | | 2) SHT A-1 NEW KITCHENETTE - SUBMIT DE- | | TAIL FOR SINK PER 11-4.24 AND ALL SUB- | | SECTIONS. | | 3) A DRINKING FOUNTAIN IS REQUIRED PER | | TABLE 403.1. (ALSO SEE SECTION 410.1) | | 4) ALL CAPPED/DEMO'ED PIPING SHALL BE | | INSPECTED PRIOR TO COVERING. | | 5) AN RPZ BACKFLOW IS REQUIRED FOR THE | | WATER SERVICE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|
|