Plan Review Details - Permit 03060960
Plan Review Stops For Permit 03060960
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-02 Cont ID  
Sent By hpiskura Date 2003-07-02 Time 11:51 Rev Time 0.00
Received By hpiskura Date 2003-07-02 Time 11:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-05 Cont ID  
Sent By dpalmer Date 2003-08-05 Time 10:33 Rev Time 1.00
Received By dpalmer Date 2003-08-05 Time 10:33 Sent To  
Notes
2003-08-05 00:00:00************* PROVISO/REVISION *******
  
 PLEASE SEE NOTES FROM FIRST AND SECOND
 REVIEW.
  
 1)NOTE: PLEASE SUBMIT COMPLETE CIRCUIT-
 -ING AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULES. PLEASE SEE TWO DIFFERENT
 SETS OF PANELS ARE SHOWN.
  
 2)NOTE: PLEASE SEE MISSING REQ'D SIGN
 CIRCUIT PER 600-5.
  
 3)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 -ING OF EM/ EXT LTS.
  
 4)NOTE; PLEASE SEE THAT CIRCUITS SHOWN
 ON PLANS DO NOT CORRELATE W/ PANELS,
 EXAMPLE, A-6 FOR GEN RECEPTS ARE SHOWN
 AS A WATER HEATER CIRCUIT??
  
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW BEFORE ANY ROUGH
 ELECTRICAL INDSPECTION IS CALLED IN.
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLEASE SEE THAT THREE NEW PANEL SCHEDULE
 -S SHOWN ON PLANS HAVE BEEN STRIKED
 THROUGH. PLEASE SEE THAT THESE DO NOT
 MATCH AND NUMEROUS ITEMS ON SCHEDULES
 DO NOT HAVE CORRECT OCP/AWG/ FOR LOADS
 ETC.
 PLEASE SEE PROVISO SET FORTH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By dpalmer Date 2003-07-01 Time 14:07 Rev Time 0.50
Received By dpalmer Date 2003-07-01 Time 13:19 Sent To  
Notes
2003-07-01 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY PANEL SCHEDULES.
 SHOWS 1CIRCUIT FOR PANEL "C" AND
 YET PANELS B&A SHOW CIRCUITS ON PANEL
 SCHEDULE BUT DO NOT SHOW THESE SAME
 ITEMS ON PLANS?
 PLEASE CORRELATE PANEL SCHEDULES AND
 PLANS.
 PLEASE SEE COMMENTS FROM OTHER REVIEWS
 (FIRE) THAT WILL HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-03 Cont ID  
Sent By lmartine Date 2003-07-03 Time 09:21 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-07-03 00:00:00SEE PLANS FOR FIRE APPROVALS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-29 Cont ID  
Sent By alange Date 2003-07-29 Time 13:04 Rev Time 0.00
Received By alange Date 2003-07-29 Time 13:04 Sent To  
Notes
2003-07-29 00:00:00TO COMM BD # 12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-13 Time 14:54 Rev Time 0.00
Received By shernand Date 2003-06-13 Time 14:54 Sent To  
Notes
2003-06-13 00:00:00COMM BOARD #25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-03 Cont ID  
Sent By lmartine Date 2003-07-03 Time 09:25 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-07-03 00:00:00NO INFORMATION PROVIDED

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-08 Cont ID  
Sent By kstevens Date 2003-08-08 Time 09:56 Rev Time 2.50
Received By kstevens Date 2003-08-08 Time 09:56 Sent To  
Notes
2003-08-08 00:00:00PASSED/PROVISO
  
  
 REVISION REQUIRED FOR CORRECTIONS TO
 SANITARY RISER DIAGRAMS & TO DELETE
 DRINKING FOUNTAIN AND ADD WATER COOLER
 PER ARCHITECT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By kstevens Date 2003-07-01 Time 10:48 Rev Time 0.75
Received By kstevens Date 2003-07-01 Time 10:03 Sent To  
Notes
2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS CHAPTER 1
 ADMIN. CODE
  
 1) SUBMIT A SANITARY RISER DIAGRAM AND A
 WATER RISER DIAGARAM. SHOW ALL PIPE
 SIZES AND WATER HAMMER ARRESTORS LOCATED
 PER PDI-WH 201 AND MANUF INSTALL. INSTR.
 104.2.1
 2) SHT A-1 NEW KITCHENETTE - SUBMIT DE-
 TAIL FOR SINK PER 11-4.24 AND ALL SUB-
 SECTIONS.
 3) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. (ALSO SEE SECTION 410.1)
 4) ALL CAPPED/DEMO'ED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING.
 5) AN RPZ BACKFLOW IS REQUIRED FOR THE
 WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692