Plan Review Details - Permit 03060806
Plan Review Stops For Permit 03060806
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 11:33 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 11:33 Sent To P
Notes
2003-09-29 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 09:03 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 09:03 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-11 Cont ID  
Sent By kstevens Date 2003-10-11 Time 06:19 Rev Time 0.50
Received By kstevens Date 2003-10-11 Time 06:19 Sent To  
Notes
2003-10-11 00:00:00REVISION OK - CHANGED BTU'S & PIPE SIZE
 W/HEATER.
  
  
  
  
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-17 Cont ID  
Sent By csiegber Date 2003-09-29 Time 11:33 Rev Time 0.50
Received By kstevens Date 2003-06-17 Time 14:53 Sent To  
Notes
2003-06-17 00:00:00 
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED. MIN.
 1,100 CU. FT. REQUIRED.