Plan Review Details - Permit 03060668
Plan Review Stops For Permit 03060668
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-01-15 Cont ID  
Sent By rmcdouga Date 2004-01-15 Time 07:32 Rev Time 0.50
Received By rmcdouga Date 2004-01-15 Time 07:32 Sent To  
Notes
2004-01-15 00:00:00SUBMITAL OF PRODUCT APPROVAL FOR
 HORIZONTAL SLIDING WINDOW MEETING
 REQUIRED PRESSURES IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-13 Cont ID  
Sent By rmcdouga Date 2004-01-13 Time 07:48 Rev Time 0.50
Received By rmcdouga Date 2004-01-13 Time 07:48 Sent To  
Notes
2004-01-13 00:00:00SUBMITTED KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-29 Cont ID  
Sent By rmcdouga Date 2003-08-29 Time 13:41 Rev Time 1.50
Received By rmcdouga Date 2003-08-29 Time 12:00 Sent To  
Notes
2003-08-29 00:00:00PROVISO
  
 1) SUBMIT A STORM PANEL KEY PLAN AND
 INSTALLATION SCHEDULE PRIOR TO
 INSTALLING STORM PANELS.
  
 2) SUBMIT PRODUCT APPROVAL FOR A 5040
 HORIZONTAL SLIDING WINDOW WITH DESIGN
 PRESSURES OF +36 AND -38.2 PSF AS
 SPECIFIED ON THE PLANS, PRIOR TO
 INSTALLING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By pkrauss Date 2003-08-27 Time 07:18 Rev Time 4.00
Received By rmcdouga Date 2003-07-17 Time 17:11 Sent To  
Notes
2003-07-17 00:00:00DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMENDMENTS TO FBC
 1804.2.2.
  
 4) THE CONTRACTOR'S SIGNATURE ON THE
 PERMIT APPLICATION IS NOT NOTARIZED.
  
 5) SAFETY GLAZING IS REQUIRED IN THE
 BATHROOM WINDOWS PER FBC 2405.2.1.
  
 6) THE 34 ROLLING WINDOW IN THE MASTER
 BEDROOM MUST COMPLY WITH FBC 1005.4.4
 FOR EMERGENCY ESCAPE AND RESCUE. SUBMIT
 THE CLEAR OPENING DIMENSIONS FOR THIS
 WINDOW.
  
 7) PROVIDE PRODUCT APPROVALS FOR THE
 HORIZONTAL SLIDING WINDOW.
  
 8) THE WIRE MESH IN THE SLAB IS REQUIRED
 TO BE SUPPORTED PER FBC 1909.3.
  
 9) REVISE NOTE #11 ON SHEET 3. INTERIOR
 DRYWALL FASTENER SPACING FOR 1-3/8" AND
 1-1/2" DRYWALL NAILS IS 7" O.C. ON
 CEILINGS AND 8" O.C. ON WALLS PER FBC
 TABLE 2306.1.
  
 10) INDICATE ON PLANS THAT THE FINISH
 FLOOR ELEVATION AT HABITABLE AREAS IS A
 MINIMUM OF 4" ABOVE FINISH GRADE PER
 CITY AMENDMENTS TO FBC 1804.1.7.
  
 12) SPECIFY ON PLAN THAT THE BOTTOM OF
 FOOTINGS IS REQUIRED TO BE A MINIMUM OF
 12" BELOW FINAL GRADE PER FBC 1804.1.
  
 13) PROVIDE A BUCK DETAIL FOR THE SIDE
 SWING EXTERIOR FRONT DOOR.
  
 14) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE CONNECTION TYPE AND ANCHOR TYPES ON
 THE PRODUCT APPROVAL THAT WILL BE USED.
  
 15) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALCULATION FORM
 600A.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-21 Cont ID  
Sent By btrobaug Date 2003-08-21 Time 17:17 Rev Time 0.50
Received By btrobaug Date 2003-08-21 Time 16:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-20 Cont ID  
Sent By alange Date 2003-08-14 Time 15:31 Rev Time 0.75
Received By btrobaug Date 2003-06-20 Time 06:55 Sent To P
Notes
2003-06-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE FOLLOWING FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} ADD RECEPTACLE IN THE GREAT ROOM TO
 COMPLY WITH 210-52(A)(2)(A).
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED, DATED
 AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-14 Cont ID  
Sent By alange Date 2003-08-14 Time 15:31 Rev Time 0.00
Received By alange Date 2003-08-14 Time 15:31 Sent To E
Notes
2003-08-14 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-12 Cont ID  
Sent By mmclean Date 2003-06-13 Time 09:03 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 08:19 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-27 Cont ID  
Sent By pkrauss Date 2003-08-27 Time 07:17 Rev Time 0.25
Received By pkrauss Date 2003-08-27 Time 07:17 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-28 Cont ID  
Sent By kstevens Date 2003-08-23 Time 09:38 Rev Time 0.50
Received By rregueir Date 2003-06-28 Time 09:08 Sent To B
Notes
2003-06-28 00:00:00DENIED
 ---------------------------------------
 1. EQUIPMENT LISTED DOES NOT MATCH BTUH
 SHOWN ON ENERGY CALCS
  
 2. R/A BACK TO AHU NOT SHOWN ON PLAN
  
 3. MIN. 4" CLEARANCE REQUIRED AT AHU
 PER FBC,M 603.1.3
  
 4. EQUIP. IN GARAGE TO BE PROTECTED
 FROM VEHICLE DAMAGE PER FBC,M 303.4
  
 5. DRYER EXHAUST REQUIRED PER FBC,M
 504.1
 ----------------------------------------
 REVIEWED BY: RONALD J REGUEIRO
 ANY QUESTIONS PLEASE CALL 561-805-6734

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-23 Cont ID  
Sent By pkrauss Date 2003-08-27 Time 07:17 Rev Time 0.33
Received By kstevens Date 2003-08-23 Time 09:38 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-24 Cont ID  
Sent By btrobaug Date 2003-08-21 Time 17:18 Rev Time 0.50
Received By jleech Date 2003-06-24 Time 19:26 Sent To M
Notes
2003-06-24 00:00:00DENIED;
 1.NOTE 1, PLUMBING CODE USED IS 2001
 FLORIDA BUILDING CODE, PLUMBING. NO
 COUNTY OR CITY AMENDMENTS.
 2.WET VENTS FOR BATHROOMS SHALL COMPLY
 WITH 909.1. THE VENT SHOULD BE UP
 STREAM OF THE TOILET AND TUB.
 3.HORIZONTAL DRY VENTS ARE NOT PERMITED.
 MASTER BATH.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-12 Time 08:19 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***