Plan Review Details - Permit 03060667
Plan Review Stops For Permit 03060667
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-04-12 Cont ID  
Sent By shill Date 2004-04-12 Time 16:16 Rev Time 1.00
Received By shill Date 2004-04-12 Time 16:16 Sent To  
Notes
2004-04-12 00:00:00REVISED SHEET 2, LETTER OF CLARIFICATION
 PER INSPECTOR REQUEST

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-11-29 Cont ID  
Sent By sthyng Date 2003-11-29 Time 12:27 Rev Time 1.50
Received By sthyng Date 2003-11-29 Time 12:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-11-26 Time 11:23 Rev Time 2.00
Received By sthyng Date 2003-08-21 Time 11:16 Sent To  
Notes
2003-08-21 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE NEW PRODUCT APPROVAL FOR THE
 GARAGE DOOR HAS A PRODUCT LIMITATION
 OF +30,-32.THE DESIGN PRESSURE IS
 +32,-39.
  
 2.)SEE PREVIOUS CORRECTION NOTICE #5.
 THE DIMENSIONS WERE SHOWN ON THE PLAN
 BUT THE GRAPHICS WERE NOT CHANGED.
 FOOTING DETAILS MUST COMPLY WITH
 FBC1804.1.3.
  
 3.)THE DETAIL FOR THE STORM PANEL
 INSTALLATION (SHEET 2) CONFLICTS WITH
 THE PRODUCT APPROVAL.THIS IS NOT
 REQUIRED TO BE ON THE PLAN.PREVIOUS
 CORRECTION #12 IS FOR AN ATTACHMENT
 SCHEDULE, SEE ATTACHED.
  
 4.)SPECIFY THE GIRDER ATTACHMENT
 WITH UPLIFT.
  
 5.)SPECIFY DESIGN PRESSURE FOR THE
 SLIDING GLASS DOOR.
  
 6.)SEE ATTACHED FS553.80(2)(B)
 REGARDING MANDATORY 4X FEE AFTER THIRD
 RESUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-14 Cont ID  
Sent By jleech Date 2003-08-20 Time 18:46 Rev Time 2.50
Received By sthyng Date 2003-07-14 Time 08:40 Sent To  
Notes
2003-07-14 00:00:00******CORRECTIONS******
  
 1.SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 2.)SHEET 1, STORM PROTECTION AND
 GARAGE DOOR NOTES SAY PALM BEACH COUNTY
 AMENDMENTS.IT SHOULD STATE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 3.)THE RED HEAD ATTACHMENT SCHEDULE
 FOR THE GARAGE DOOR BUCK CONFLICTS
 WITH THE PRODUCT APPROVAL (SHEET 1).
  
 4.)WINDOW L2 AT BOTH BATH TUBS ARE
 REQUIRED TO COMPLY WITH FBC2405.1.
  
 5.)ON THE TYPICAL WALL SECTION (SHEET
 1) AND MONOLITHIC WALL FOOTING (SHEET 3)
 SHOW THE 4" ABOVE GRADE AND 12" BELOW
 GRADE MINIMUMS (FBC1804.1.3, CITY OF
 WPB AMENDMENTS TO THE FBC1804.1.7).
  
 6.)FIRESTOP REQUIRED, FBC 705.3.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT, CITY OF WEST PALM BEACH AMEND.
 TO THE FBC1804.2.2.
  
 8.)SHOW THE SIZE OF THE ATTIC ACCESS;
 COMPLY WITH FBC2309.6.
  
 9.)SEPARATE PERMITS REQUIRED.
  
 10.) BEFORE A PERMIT CAN BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY.THE PLANS MUST BE STAMPED AND
 THE ORIGINAL RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 11.) PLEASE DO NOT STAPLE THE PRODUCT
 APPROVALS TO THE PLANS AS THEY MAKE
 THE PLAN AND THE PAS DIFFICULT TO READ.
  
 12.)PROVIDE A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE.
  
 13.)A NOTICE OF COMMENCEMENT MUST
 BE FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 14.)ADDITIONAL FEES DUE, $177.44.
  
 15.)GORDON F. BUCK HAS CERTIFIED THE
 DESIGN OF THE TRUSS CONNECTIONS (SHEET
 4), BUT KARPINIA IS THE CONSULTING
 ENGINEER ON THE JOB.PLEASE ADDRESS.
  
 16.)SHOW THE LATERAL BRACING IN THE
 ROOF NOTES (SHEET 4) ON THE ROOF FRAMING
 PLAN.
  
 17.)SIMPSON 2003 CATALOG SPECIFIES
 A DIFFERENT NAILING SCHEDULE (NUMBER AND
 SIZE) FOR THE HETAL16 TRUSS CONNECTOR.
 EITHER REVISE YOUR SCHEDULE TO BE
 CONSISTENT WITH THE CATALOG OR PROVIDE
 CALCULATIONS TO SHOW HOW THIS CONNECTOR
 WILL OBTAIN THE 1000# UPLIFT.ALSO
 DO THE SAME WITH H3 AND ANY OTHER
 CONNECTORS ON THE PLAN WHICH HAVE EITHER
 A DIFFERENT NUMBER OF NAILS SPECIFIED
 OR A DIFFERENT TYPE NAIL SPECIFIED THAN
 THE CATALOG.
  
 18.) SHOW THE CONNECTOR LOCATIONS ON
 THE ROOF FRAMING PLAN (SHEET 4).
  
 19.) PROVIDE PRODUCT APPROVALS FOR THE
 SLIDING GLASS DOOR.
  
 WHEN RESUBMITTING, REPLACE SHEETS WHICH
 HAVE CHANGED WITH THE NEW SHEETS. SUBMIT
 THE OLD SHEETS SEPARATELY MARKED "VOID".
 CLEARLY MARK ALL CHANGES WITH CLOUDS OR
 TRIANGLES.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By dpalmer Date 2003-08-20 Time 16:17 Rev Time 1.00
Received By dpalmer Date 2003-08-20 Time 16:17 Sent To P
Notes
2003-08-20 00:00:00PLEASE SEE REDLINES ON PLANS PERTAINING
 TO PANEL SCHEDULE. LOADS/ AWG ETC
  
 PLEASE SEE NOTE FOR 210.70
  
 ALL OPTIONS AND REVISIONS TO BE SUBMITT-
 ED BEFORE ROUGH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-20 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 15:28 Rev Time 0.50
Received By dpalmer Date 2003-06-20 Time 08:07 Sent To P
Notes
2003-06-20 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES TO ELEC.
 WORK PER PALM BEACH COUNTY. PLEASE NOTE,
 CITY OF WEST PALM BEACH.
  
 2)NOTE: PLEASE SEE 210-52D/210-11C3,
 DEDICATED BATH(S) CIRCUITS REQ`D TO BE
 #12 AWG, AND 20A.
  
 3)NOTE: PLEASE CLARIFY WASHER/LAUNDRY,
 WASHER SHOWN AT 1.2KW(1.5REQ`D) BUT
 LAUNDRY RECEPT SHOWN AT 1.5KW?
 WHICH ONE?
  
 4)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE EQUIPMENT. 110-9,215-5
 MAINS/PANELS/BRKRS ARE ALL TO RATED FOR
 THE AVAILABLE FAULT CURRENT.
  
 5)NOTE:PLEASE SEE FS/FAC PLANS CONTAIN-
 -ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. 471.025/184.221
  
 6)NOTE: PLEASE SEE 250-110,250-122, FOR
 EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 MAIN AND PANEL.
  
 THIS IS JUST A NOTE, IF A MAIN DISC IS
 INSTALLED OUTSIDE, A MCB IS NOT REQ`D IN
 SIDE.
  
 7)NOTE: PLEASE SEE WASHER RECEPT SHOWN
 AS GFI? THIS IS TO BE A SINGLE RECEPT
 AND NOT TO BE GFI.
 PLEASE CLARIFY WHERE THE LAUNDRY RECEPT
 SHOWN ON PANEL SCHEDULE IS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 11:23 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 11:23 Sent To B
Notes
2003-11-26 00:00:00TO ST DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 15:28 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 15:28 Sent To E
Notes
2003-08-14 00:00:00TO DPALMER DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-12 Cont ID  
Sent By mmclean Date 2003-06-13 Time 09:02 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 08:19 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-28 Cont ID  
Sent By jleech Date 2003-06-26 Time 16:33 Rev Time 0.50
Received By rregueir Date 2003-06-28 Time 10:25 Sent To B
Notes
2003-06-28 00:00:00PROVISO
 ---------------------------------------
 1. MIN 4" CLEARANCE AT AHU PER FBC,M
 SEC 603.1.3
  
 2. DRYER EXH REQUIRED PER FBC,M 504.6
  
 3. APPLIANCES IN GARAGE TO BE PROTECTED
 FROM DAMAGE PER FBC,M 303.4

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By jleech Date 2003-08-20 Time 18:46 Rev Time 0.33
Received By jleech Date 2003-08-20 Time 18:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-26 Cont ID  
Sent By dpalmer Date 2003-08-20 Time 16:19 Rev Time 0.50
Received By jleech Date 2003-06-26 Time 16:33 Sent To M
Notes
2003-06-26 00:00:00DENIED;
 1.NOTE 1, PLUMBING CODE USED IS 2001
 FLORIDA BUILDING CODE PLUMBING. NO
 COUNNTY OR CITY AMENDMENTS.
 2.WET VENTS FOR BATHROOMS SHALL COMPLY
 WITH 909.1. THE VENT SHOULD BE UP
 STREAM OF THE TOILET AND TUB.
 3.HORIZONTAL DRY VENTS ARE NOT PERMITED
 MASTER BATH.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 8056695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-12 Time 08:19 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***