Plan Review Details - Permit 03060496
Plan Review Stops For Permit 03060496
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-01-09 Cont ID  
Sent By jwitmer Date 2004-01-09 Time 10:49 Rev Time 0.75
Received By jwitmer Date 2004-01-09 Time 10:49 Sent To  
Notes
2004-01-09 00:00:00BLDG REV# 2 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-12-31 Cont ID  
Sent By jwitmer Date 2003-12-31 Time 08:51 Rev Time 1.00
Received By jwitmer Date 2003-12-31 Time 08:44 Sent To  
Notes
2003-12-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060496
 ADD: 215 S. OLIVE AVE
 CONT: RAYMOND H. NORDINE
 TEL: (561)252-1662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BOTH THE PLANS AND COMMENT SHEET FROM
 THE ARCHITECT ARE TO BE SIGNED AND SEAL-
 ED.
 2) FIRE REVIEWER COMMENTS THAT ADDITION-
 AL SMOKE DETECTORS SOUTH RESIDENTIAL
 UNIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-09 Cont ID  
Sent By jwitmer Date 2003-09-09 Time 07:23 Rev Time 0.55
Received By jwitmer Date 2003-09-09 Time 07:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-08-21 Cont ID  
Sent By jwitmer Date 2003-08-21 Time 15:25 Rev Time 2.25
Received By jwitmer Date 2003-08-21 Time 14:06 Sent To  
Notes
2003-08-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060496
 ADD: 215 S OLIVE AVE
 CONT: RAYMOND NORDINE
 TEL: (561)252-1662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) MEANS OF EGRESS- FOURTH FLOOR IS THE
 BUSINESS OCCUPANCY, MEETS THE REQUIRE-
 MENT FOR SINGLE EXIT SECTION 1020.1.
  
 PROBLEM: 1026.1 SINGLE EXIT RESIDENTIAL,
 FOR R-1, R-2,
 1) MUST MEET THE MAXIMUM TRAVEL DIS-
 TANCE TO REACH AN EXIT FROM THE ENTRANCE
 DOOR TO ANY DWELLING UNIT SHALL NOT
 EXCEED 30 FEET.OK
 2) MAXIMUM NUMBER OF UNITS PER FLOOR
 SHALL NOT EXCEED (4). OK
 3) MAXIMUM GROSS AREA SERVED BY THE
 DWELLING UNIT DOES NOT EXCEED 3,500 FT.
 PER FLOOR. OK
 4) MAXIMUM BUILDING HEIGHT SHALL BE
 ONE STORY ABOVE THE LEVEL OF EXIT
 DISCHARGE. THIS IS THE AREA WHERE WE DO
 NOT MEET THE CODE, MAKING A SECOND MEANS
 OF EGRESS REQUIRED.THE CIRCULAR STAIRS
 MAY MEET THE SECOND MEANS OF EGRESS,
 BUT NOT WITH THE RISE INDICATED ON SHEET
 A.2 NOTE# 5, RISE OF 8.92" EACH RISER.
  
 TO BE USED AS A MEANS OF EGRESS
 ALL SECTIONS OF 1007.8.2.1 (1-6) MUST BE
 MET! PROVIDE UPDATED INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-30 Cont ID  
Sent By alange Date 2003-08-08 Time 16:00 Rev Time 3.00
Received By jwitmer Date 2003-06-30 Time 13:02 Sent To  
Notes
2003-06-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060496
 ADD: 215 S OLIVE AVE
 CONT: RAYMOND NORDINE
 TEL: (561)252-1662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) F 103.1 EXISTING BUILDINGS WITHIN THE
 FIRE DISTRICT.
 AN EXISTING BUILDING SHALL NOT BE HERE-
 AFTER BE INCREASED IN HEIGHT OR AREA
 UNLESS IT IS OF THE TYPE OF CONSTRUCTION
 PERMITTED FOR NEW BUILDINGS WITHIN THE
 FIRE DISTRICT OR IS ALTERED TO COMPLY
 WITH THE REQUIREMENTS FOR SUCH TYPE OF
 CONSTRUCTION. NOR SHALL ANY BUILDING BE
 HEREAFTER EXTENDED ON ANY SIDE, NOR
 SQUARE FOOTAGE OR FLOORS ADDED WITHIN
 THE EXISTING BUILDING UNLESS SUCH MODIF-
 ICATIONS ARE OF A TYPE OF CONSTRUCTION
 PERMITTED FOR NEW BUILDINGS WITHIN THE
 FIRE DISTRICT.A-2 NOTE 18.
  
 2) 1012.1.4 DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL LEAVE UNOBSTR
 UCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY,
 OR LANDING, NOR PROJECT MORE THAN 7" IN-
 TO THE REQUIRED WIDTH OF AN AISLE, CORRI
 DOR, PASSAGEWAY OR LANDING, WHEN FULLY
 OPEN, SEE ENTRY DOOR (A).FIFTH FLOOR
 LANDING OF MAIN STAIR.
  
 3)SHEET A-4 STAIR PLAN TO ROOF DETAIL(2)
 INDICATES A 8" RISE, 1007.3.` MAXIMUM OF
 7"RISE, TREADS A MINIMUM OF 11".
  
 4)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 5) SOUTH TENANT INDICATES A WORK/ LOFT
 WITH THE FOURTH FLOOR BEING BUSINESS,
 THE BATHROOM IS ELEVATED FROM THE MAIN
 FLOOR BY THREE RISERS, PROVIDE INFORMA-
 TION FOR VERTICAL ACCESSIBILITY.11-4.1.6
  
 6) THIS SAME BATHROOM REQUIRES A FLOOR
 THE SAME LEVELAAS THE BATH, 1007.2.4.,
 IF THIS IS CONSIDERED BUSINESS. NO EXCEP
 TION AS IN R-3.
  
 7) SPIRAL STAIRWAY: PROVIDE MANUFACTURER
 INFORMATION, THAT THE SPIRAL STAIR COM-
 PLIES WITH ALL SECTIONS OF 1007.8.2.3 &
 1007.8.3. STAIRWAY & HANDRAIL & GUARD-
 RAIL SYSTEMS.
  
 8) SHEET S-1 LIVE LOADS, ARE TO BE TAKEN
 FOR THE OCCUPANCY THE FOURTH FLOOR IS
 CONSIDERED THE WORK FLOOR OF THE WORK/
 LIVE LOFT THE FLOOR LIVE LOAD MINIMUM
 FOR OFFICE IS 50 PSF WITHOUT FILE
 CABINETS ? THE FIFTH FLOOR FOR LIVING
 AREAS SHOULD BE 40 PSF ONLY SLEEPING
 ROOMS IS 30 PSF. NO MENTION AS TO THE
 LOADING FOR THE ATTIC STORAGE PSF?
  
 9)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 MISSING THE DESIGN WIND PRESSURES FOR
 THE NEW ROOF SYSTEM,SEE FIGURE 1606.2(C)
 FOR INTERIOR ZONES, EDGE AND ZONE 3.
 PROVIDE THE MEAN ROOF HEIGTH?
 ALSO GIVE PRESSURES FOR THE NEW EXTERIOR
 DOOR AND SKYLIGHTS?
  
 10)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS FOR
 A) EXTERIOR DOOR
 B) SKYLIGHTS
 C) ROOFING ASSEMBLIES (FIRE DISTRICT)
 PROVIDE MAN SPEC FOR ROOF AND INSU
 LATION FOR FIRE TYPE A OR B AND
 ATTACHMENT.
  
 11)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 12)1006.1.3.1 PENETRATIONS INTO AND
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR THE INDEPENDENT STAIR PRESSURIZATION
 SPRINKLER PIPING, STANDPIPES AND ELECTRI
 CALCONDUIT SERVING THE STAIRWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO
 TECTED IN ACCORDANCE WITH 705.4
  
 13)1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 14)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 15)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 16)3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 17)3003.6.3 THE AREA OF THE VENTS
 SHALL BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-02-27 Cont ID  
Sent By dpalmer Date 2004-02-27 Time 07:15 Rev Time 0.33
Received By dpalmer Date 2004-02-27 Time 07:15 Sent To  
Notes
2004-02-27 00:00:00**** REDLINED OCP SHOWN FOR 9.2KW AHU.
 PLEASE SEE NEC 424.3B, MIN OCP 125%.
 SHOWN AS 2P-40, SHOULD BE A MIN OF 2P-
 50.
 PLEASE VERIFY LOAD AND RATING ON NAME-
 -PLATE OF UNIT.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-25 Time 10:25 Rev Time 0.50
Received By dpalmer Date 2004-02-13 Time 06:14 Sent To  
Notes
2004-02-13 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SEE PLANS, HAND DRAWN
 CHANGES HAVE BEEN MADE TO PLANS. PLANS
 CONTAIN WHITE-OUT.
 PLANS MUST BE REPRINTED AND AND THEN
 SIGNED, DATED AND SEALED BY THE ENGINEER
 OF RECORD.
 PREVIOUSLY NOTED.
  
 2)NOTE: PLEASE HAVE PLANS "SIGNED" BY
 THE ENGINEER WITH A COMPLETE "SIGNATURE"
 AS REQ'D UNDER FS 471.025 AND FAC 61G15-
 -23.002. PER RULING OF FBPE'S IN OCT 03,
 INITIALS ARE NOT ACCEPTABLE UNLESS
 PE LICENSE FROM STATE WAS SIGNED LIKE
 THIS. IF WHAT APPEARS TO BE INITIALS
 ARE INDEED "SIGNATURE" PLEASE PROIDE
 COPY OF FL PE LICENSE AND DRIVERS LIC.,
 CONTAINING SIGNATURE.
  
 3)NOTE: PLEASE SEE SD NOTE: ON E-1,
 DOES NOT SEEM TO CORRELATE WITH PLANS
 AND CIRCUITING.
 PLEASE SEE NFPA-72 8-1.4.2, SD' THAT
 ARE W/IN 20' OF COOKING APPLIANCE MUST
 BE EQUIPPED WITH AN ALARM SILENCING
 MEANS OR OF THE PHOTOELECTRIC TYPE.
  
 4)NOTE: PLEASE CORRELATE LOADS SHOWN
 FOR A/C. PANEL SHOWS ONE AND LOAD CALCS
 SHOW ANOTHER.
 PLEASE CLARIFY NO A/C IN OTHER UNIT??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-02-11 Time 09:14 Rev Time 0.33
Received By dpalmer Date 2004-01-07 Time 05:58 Sent To  
Notes
2004-01-07 00:00:00REV OK

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-12-09 Cont ID  
Sent By dpalmer Date 2003-12-09 Time 11:40 Rev Time 0.75
Received By dpalmer Date 2003-12-09 Time 11:15 Sent To  
Notes
2003-12-09 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SEE THAT HAND DRAWN/
 WRITTEN CHANGES MUST BE REPRINTED AND
 THEN PLANS ARE TO BE SIGNED AND SEALED.
 PLEASE ALSO NOTE, PLANS ARE REQ'D TO
 HAVE A SIGNATURE. FS 471.025 AND FAC
 61G15-23.002. PLEASE NOTE: THIS OFFICE
 HAS BEEN INFORMED BY THE BOARD OF PE'S
 THAT SIGNATURE MUST CONTAIN A MIN OF
 FIRST AND LAST NAME. INITIALS ARE NOT
 PERMITTED.
  
 2)NOTE: PLEASE REDO LOAD CALCULATIONS.
 LOADS ARE DIFFERENT ON EACH AND YET
 COME UP WITH THE SAME LOAD??
  
 PLEASE SEE THAT THIS IS REQ'D ON ALL
 SHEETS WEATHER OR NOT A COMMENT FROM
 THE REVIEWER.
  
 PAEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-02 Cont ID  
Sent By dpalmer Date 2003-09-02 Time 15:10 Rev Time 0.50
Received By dpalmer Date 2003-09-02 Time 15:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-08-25 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 09:07 Rev Time 1.00
Received By dpalmer Date 2003-08-25 Time 07:20 Sent To  
Notes
2003-08-25 00:00:00******* UNSAT ************
  
 1)NOTE: PLEASE SEE ADDITIONAL LOAD
 CALCULATIONS SUBMITTED PER HAY VINH LY
 P.E. PLEASE SEE EXISTING SERVICE SHOWN
 AS 350A AND RISER DIAGRAM ON E-2 SHOWS
 600A. PLEASE VERIFY. SERVICE CONDUCTOR
 SIZE DOES NOT SEEM TO SUPPORT A 600A
 MAIN? PLEASE VERIFY ACTUAL FEEDER SIZE.
 310.16/215.5
  
 2)NOTE: PLEASE VERIFY SIZE OF HEAT FOR
 AHU'S, SHOWN AS 9.2 KW ON ELEC AND 8KW
 ON MECH? PLEASE CORRELATE.
  
 PLEASE SEE THAT MOST NOTES WERE ADDRESS-
 ED FROM FIRST REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-25 Cont ID  
Sent By dpalmer Date 2003-06-25 Time 07:30 Rev Time 2.00
Received By dpalmer Date 2003-06-25 Time 07:27 Sent To  
Notes
2003-06-25 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE, SD`S ARE REQ'D TO
 BE 5' FROM RETURN AIR. IT IS NOTED
 3' FROM ALL OTHERS WHICH IS CORRECT.
 NFPA-72 8-1.4
  
 2)NOTE: MISSING TWO SMALL APPLIANCE
 CIRCUITS FOR EACH UNIT.
 A MIN OF TWO REQ`D PER 210-52/ 210-11C-1
  
 3)NOTE: PLEASE CLARIFY MISSING MIN REQ`D
 WASHER IN SOUTH UNIT? 210-11C-2
 210-52
  
 4)NOTE: PLEASE SEE 424-3 FOR 125% MIN
 OCP FOR AHU'S.
  
 5)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR EXISTING SERVICE AND
 SHOW ANY NEW LOADS ADDED.
 PLEASE ALSO SEE PLANS, SHOWS ELECTRICAL
 ROOM ON GROUND FLOOR? PLEASE VERIFY
 IF ROOM HAS MOVED FROM MEZZ LEVEL,2ND
 FLR?
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW DISC`S. 110-9/215-5
  
 7)NOTE: PLEASE REDO LOAD CALCULATIONS
 FOR MIN LOADS REQ`D UNDER 220.
 PLEASE ALSO SEE MIN LOADS FOR RANGE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE ALSO NOTE VALUE OF WORK TO BE
 UPGRADED DUE TO WORK BEING DONE.
 VALUE SHOWN AT 10,000 NOW IS WAY UNDER-
 -VALUED. 104.6.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-01-09 Cont ID  
Sent By mcarsill Date 2004-01-09 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2004-01-09 Time 12:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 14:02 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 14:02 Sent To  
Notes
2003-12-12 00:00:001) SMOKE DETECTOR REQUIRED IN SOUTH
 RESIDENTIAL AREA IN ADDITION TO THE
 ONE SHOWN WITHIN THE SPIRAL STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 07:44 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 07:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-08-27 Cont ID  
Sent By mcarsill Date 2003-08-27 Time 09:13 Rev Time 0.00
Received By mcarsill Date 2003-08-27 Time 09:13 Sent To  
Notes
2003-08-27 00:00:001) FAILED, SEE BUILDING PLAN REVIEW
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By nmccray Date 2003-07-07 Time 13:42 Rev Time 0.00
Received By nmccray Date 2003-07-07 Time 13:42 Sent To  
Notes
2003-07-07 00:00:001) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 2) PLEASE REF NFPA 101 LIFE SAFETY CODE
 2000 EDITION CHAPTER 7.2.2.2.3 SPIRAL
 STAIRS.
  
 3)SEPARATE SHOP DRAWING AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE ALARM
 SYSTEM AND FIRE SPRINKLER SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 11:43 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 11:43 Sent To P
Notes
2004-02-25 00:00:00TO KS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-05-05 Time 15:42 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 10:25 Sent To  
Notes
2004-02-25 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 09:14 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 09:14 Sent To E
Notes
2004-02-11 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-01-06 Time 16:37 Rev Time 0.00
Received By csiegber Date 2004-01-06 Time 16:30 Sent To  
Notes
2004-01-06 00:00:00TO COMM BD#20

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 16:34 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 16:34 Sent To  
Notes
2003-11-26 00:00:00TO COMM BD#28

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-28 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 09:07 Rev Time 0.00
Received By dbaxter Date 2003-08-28 Time 09:07 Sent To E
Notes
2003-08-28 00:00:00TO COMM. BD. #50.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 16:00 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:00 Sent To B
Notes
2003-08-08 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-09 Time 09:05 Rev Time 0.00
Received By shernand Date 2003-06-09 Time 09:05 Sent To  
Notes
2003-06-09 00:00:00COMM BOARD #54

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2004-01-08 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-05 Cont ID  
Sent By pkrauss Date 2003-12-05 Time 07:03 Rev Time 0.33
Received By pkrauss Date 2003-12-05 Time 07:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-21 Cont ID  
Sent By pkrauss Date 2003-08-21 Time 06:35 Rev Time 0.40
Received By pkrauss Date 2003-08-21 Time 06:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-03 Cont ID  
Sent By pkrauss Date 2003-07-03 Time 07:29 Rev Time 0.40
Received By pkrauss Date 2003-07-03 Time 07:04 Sent To  
Notes
2003-07-03 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.INDICATE WHAT TYPE OF STANDS WILL
 THE CONDENSER UNITS MOUNTED ON.PROVIDE
 INFORMATION ON HOW STANDS ARE ATTACHED
 TO THE ROOF.STANDS OR CURBS SHALL
 COMPLY WITH 2001 FBC 1511.7.PLEASE
 NOTE, EQUIPMENT LOCATED ON THE ROOF
 SHALL COMPLY WITH WEST PALM BEACH CITY
 CODE ARTICLE IV SECT 94-107 (E)(9),
 EQUIPMENT SHALL BE HIDDEN BY PARAPET
 WALL OR BE ENCLOSED BY SCREEN.

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-02-28 Cont ID  
Sent By kstevens Date 2004-02-28 Time 16:26 Rev Time 0.50
Received By kstevens Date 2004-02-28 Time 16:25 Sent To  
Notes
2004-02-28 00:00:00REVISION OK - MOVED LOCATION OF TWO LAVS

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-12-15 Cont ID  
Sent By csiegber Date 2004-02-25 Time 11:43 Rev Time 0.75
Received By kstevens Date 2003-12-15 Time 08:18 Sent To  
Notes
2003-12-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHT P-1 WATER ISOMETRIC, AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE FROM
 ISOMETRIC. 604.9
 2) SHT P-1 SANITARY ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN. (SEE W/M - SINK)
 104.2.1
 3) ENGINEERS SIGNATURE REQUIRED ON SEAL
 OF PLANS. FAC 61G15-23.002(1) AND FS
 471.025. PER FBPE RULING AND BUILDING
 OFFICIAL, INITALS ARE NOT APPROVED ON
 THE SEAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-08-25 Cont ID  
Sent By kstevens Date 2003-08-27 Time 08:33 Rev Time 0.50
Received By kstevens Date 2003-08-25 Time 08:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-08-19 Cont ID  
Sent By kstevens Date 2003-08-19 Time 09:23 Rev Time 1.00
Received By kstevens Date 2003-08-19 Time 09:23 Sent To  
Notes
2003-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 SANITARY RISER DIAGRAM.
 SECTION 909.1 WASH MACHINE SHALL CONNECT
 DOWNSTREAM OF THE WET VENT. (SEE RED
 LINE)
 2) SHT P-1 WATER RISER DIAGRAM, ALL AIR
 CHAMBERS SHALL BE DELETED. NOT APPROVED.
 SECTION 604.9
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-27 Cont ID  
Sent By kstevens Date 2003-06-27 Time 17:35 Rev Time 1.50
Received By kstevens Date 2003-06-27 Time 17:35 Sent To  
Notes
2003-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A.2 BATHROOM SHALL COMPLY SECTION
 11-4.23 AND ALL SUBSECTIONS. PROVIDE
 DETAILS. 4TH FLOOR BUSINESS TENANT.
 2) SHT A.2 FOURTH FLOOR BUSINESS TENANT,
 PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. ALSO SEE SECTION 410.1
 3) SHT A.2 5TH FLOOR SOUTH RESIDENTIAL,
 PER TABLE 403.1 A WASH MACHINE CONNECT-
 ION IS REQUIRED.
 4) SHT A.2 ROOF PLAN, SUBMIT CALCULAT-
 IONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS. SHOW 1/2 AREA FOR ALL VERTICAL
 WALLS INCLUDING PARAPETS. SHOW SLOP OF
 ROOF TO DRAINS. SECTIONS 1106 & 1107 AND
 ALL SUBSECTIONS.
 5) SHT P-1 KEY NOTES: #11, THE RELIEF
 VALVE SHALL DISCHARGE FULL SIZE. SECTION
 504.7.1. - #9 MINIMUM EMERGENCY PAN
 DRAIN SIZE IS 3/4". SECTION 504.8.1
 SHT P-1 WATER RISER DIAGRAM, AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER AR-
 RESTORS REQUIRED BY 604.9 SHALL BE LOCA-
 TED AT WASH MACHINES, ICE MAKERS, AND
 DISHWASHERS.
 6) ALL ABANDONED/DEMO'ED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING.
 7) SHT P-1 GENERAL NOTES: #16, AIR
 CHAMBERS ARE NOT APPROVED. DELETE REFER-
 ENCE.
 8) SHT P-1 SUBMIT RISERS FOR THE RELIEF
 VALVE DISCHARGE LINE AND THE EMERGENCY
 PAN DRAIN LINE. SHOW PIPE SIZE, TYPE OF
 MATERIAL, AND TERMINATION POINT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved