Plan Review Details - Permit 03060493
Plan Review Stops For Permit 03060493
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-28 Cont ID  
Sent By sthyng Date 2003-07-28 Time 13:29 Rev Time 1.00
Received By sthyng Date 2003-07-28 Time 13:29 Sent To  
Notes
2003-07-28 00:00:00PROVISO
 SUBMIT WINDOW PRODUCT APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-26 Cont ID  
Sent By sthyng Date 2003-06-25 Time 18:07 Rev Time 2.50
Received By sthyng Date 2003-06-25 Time 18:07 Sent To  
Notes
2003-06-25 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)BEDROOMS ARE REQUIRED TO HAVE
 EMERGENCY EGRESS FBC1005.4.A 38" HIGH
 SINGLE HUNG WINDOW DOES NOT COMPLY.
  
 2.)THE WINDOW AT THE TUB LOCATION
 MUST COMPLY WITH FBC2405.2.
  
 3.)ADDITIONS OVER 25% MUST COMPLY
 WITH FBC 3401.7.1.2.1.
  
 4.)SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR MULLIONS AND SHINGLES.
 THE SHINGLE PRODUCT APPROVAL MAY BE
 SUBMITTED WITH THE ROOF PERMIT
 APPLICATION.
  
 5.)SEPARATE PERMITS REQUIRED.
  
 6.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 7.)HOW IS THE BASE PLATE ATTACHED
 TO THE CONCRETE?GIVE ATTACHMENT SIZE
 AND TYPE, EMBEDMENT, DISTANCE.
  
 8.)PROVIDE A ROOF SHEATHING ATTACHMENT
 SCHEDULE.
  
 9.)IT IS UNCLEAR WHICH HETA ATTACHMENT
 IS SPECIFIED ON THE WALL SECTION. REVISE
 AND GIVE DESIGN UPLIFT FOR ALL
 ATTACHMENTS WITH STRUCTURAL CALCULATIONS
 OR SEALED BY AN ENGINEER, FBC104.3.1.1.
  
 10.)FIRESTOP REQUIRED FBC 705.3.
  
 11.)ATTIC ACCESS REQUIRED FBC2309.6.
  
 12.)ADDITIONAL FEES REQUIRED, $4.48.
  
 13.)PROVIDE A ROOF FRAMING PLAN.
  
 14.)DESIGN INFORMATION IS REQUIRED
 TO BE ON THE PLAN, FBC 1606.1.7.
  
 15.)THE SECOND SHEET HAS A BLANK
 TITLE BLOCK.
  
 16.)ALL CHANGES MUST BE APPROVED BY
 HISTORIC BEFORE RESUBMITTAL.
  
 CLOUD ALL CHANGES BEFORE RESUBMITTAL.
 PROVIDE A WRITTEN RESPONSE TO ALL ITEMS
 EXPLAINING HOW IT HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2003-10-31 Cont ID  
Sent By btrobaug Date 2003-10-31 Time 14:50 Rev Time 0.50
Received By btrobaug Date 2003-10-31 Time 14:06 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-25 Cont ID  
Sent By csiegber Date 2003-10-28 Time 16:33 Rev Time 0.50
Received By btrobaug Date 2003-07-23 Time 17:19 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-11 Cont ID  
Sent By alange Date 2003-07-22 Time 16:30 Rev Time 0.50
Received By btrobaug Date 2003-06-11 Time 12:12 Sent To M
Notes
2003-06-11 00:00:00UNSAT
 ~~~~~
 `~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE SCOPE OF THIS WORK REQUIRES AN
 ELECTRICAL PERMIT AND NONE WAS APPLIED
 FOR.
 PLEASE HAVE ELECTRICAL CONTRACTOR SUBMIT
 THE FOLLOWING WITH THE APPLICATION.
  
 1} SIZE OF THE EXISTING SERVICE WITH
 LOAD CALCULATIONS INCLUDING ALL NEW
 ADDED LOADS.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-10-28 Time 16:32 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 16:32 Sent To E
Notes
2003-10-28 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-22 Cont ID  
Sent By alange Date 2003-07-22 Time 16:30 Rev Time 0.00
Received By alange Date 2003-07-22 Time 16:22 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-09 Time 14:35 Rev Time 0.00
Received By shernand Date 2003-06-09 Time 14:35 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-06 Cont ID  
Sent By mmclean Date 2003-06-09 Time 12:27 Rev Time 0.00
Received By shernand Date 2003-06-06 Time 16:10 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-11-05 Cont ID  
Sent By pkrauss Date 2003-11-05 Time 13:42 Rev Time 0.25
Received By pkrauss Date 2003-11-05 Time 13:42 Sent To  
Notes
2003-11-05 00:00:00PROVISO:
 PLEASE NOTE AS PER 2001 FBC(M) 601.4,
 RETURN AIR DUCT TO BE EQUAL TO THE
 SUPPLY AIR PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-25 Cont ID  
Sent By btrobaug Date 2003-10-31 Time 14:50 Rev Time 0.20
Received By pkrauss Date 2003-07-25 Time 15:28 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-16 Cont ID  
Sent By btrobaug Date 2003-06-11 Time 12:26 Rev Time 0.25
Received By pkrauss Date 2003-06-16 Time 15:56 Sent To P
Notes
2003-06-16 00:00:00PLEASE PROVIDE INFORMATION AS TO THE
 SIZE AND MATERIAL OF THE DUCTWORK.
 INDICATE SIZE OF GRILLES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-25 Cont ID  
Sent By btrobaug Date 2003-07-25 Time 15:51 Rev Time 0.33
Received By kstevens Date 2003-07-25 Time 15:50 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-06 Time 16:10 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***