Plan Review Details - Permit 03060455
Plan Review Stops For Permit 03060455
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-03 Time 11:57 Rev Time 3.00
Received By lhatten Date 2003-07-06 Time 18:36 Sent To  
Notes
2003-07-07 00:00:00REVIEWED & STAMPED PLANS 07/06/2003

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-10 Cont ID  
Sent By btrobaug Date 2003-07-10 Time 18:07 Rev Time 0.50
Received By btrobaug Date 2003-07-10 Time 18:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-07-10 Time 11:42 Rev Time 0.50
Received By btrobaug Date 2003-06-20 Time 05:30 Sent To P
Notes
2003-06-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 ALL CHANGES TO PLANS MUST COMPLY WITH
 481.221(4) FS.STATUTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-10 Cont ID  
Sent By shernand Date 2003-07-10 Time 11:42 Rev Time 0.00
Received By shernand Date 2003-07-10 Time 11:42 Sent To E
Notes
2003-07-10 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-06 Cont ID  
Sent By mmclean Date 2003-06-12 Time 10:36 Rev Time 0.00
Received By shernand Date 2003-06-06 Time 14:15 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-03 Cont ID  
Sent By pkrauss Date 2003-07-03 Time 11:56 Rev Time 0.20
Received By pkrauss Date 2003-07-03 Time 11:55 Sent To B
Notes
2003-07-03 00:00:00AS PER CONVERSATION WITH NORMAN (MECH
 CONTRACTOR) - ENERGY CALCS INDICATE
 "SENSIBLE" BTU INSTEAD OF "TOTAL" AS TO
 BETTER MATCH & PROVE THEY ARE WITHIN THE
 20 PERCENT REQUIRED PER CODE. PLANS OK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-24 Cont ID  
Sent By pkrauss Date 2003-06-24 Time 07:16 Rev Time 0.25
Received By pkrauss Date 2003-06-24 Time 07:16 Sent To P
Notes
2003-06-24 00:00:00DENIED:MECHANICAL PERMIT 03060465
  
 ENERGY CALCULATIONS INDICATE 2721 SQ FT
 OF CONDITIONED FLOOR SPACE THE COOLING
 SYSTEM INDICATES ONLY A 3 1/2 TON SYSTEM
 WHEREAS THE EQUIPMENT SCHEDULE ON THE
 PLAN INDICATES A 5 TON SYSTEM.A 3 1/2
 TON SYSTEM FOR THIS SQ FOOTAGE SEEMS
 INADEQUATE.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-24 Cont ID  
Sent By pkrauss Date 2003-06-24 Time 07:16 Rev Time 0.25
Received By jleech Date 2003-06-24 Time 17:34 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-06 Time 14:15 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***