Plan Review Details - Permit 03060377
Plan Review Stops For Permit 03060377
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-06-05 Time 14:42 Rev Time 0.00
Received By shernand Date 2003-06-05 Time 14:42 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-31 Cont ID  
Sent By pschmitz Date 2006-05-31 Time 10:15 Rev Time 0.00
Received By pschmitz Date 2006-05-31 Time 10:15 Sent To  
Notes
2006-05-31 00:00:00ALL INFORMATION FOR GENERATOR, LOCATION
 ,SPECIFICATIONS ON PERMIT
 #02061002 CATALFUMO GC

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-05 Time 14:42 Rev Time 0.33
Received By kstevens Date 2003-06-12 Time 18:32 Sent To  
Notes
2003-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692