Plan Review Details - Permit 03060182
Plan Review Stops For Permit 03060182
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-19 Cont ID  
Sent By rmcdouga Date 2003-06-19 Time 13:37 Rev Time 3.00
Received By rmcdouga Date 2003-06-19 Time 13:37 Sent To  
Notes
2003-06-19 00:00:00BUILDING PROVISO
  
 SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2
 PRIOR TO POURING THE FOUNDATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-06 Cont ID  
Sent By sgraham Date 2003-06-06 Time 11:54 Rev Time 4.00
Received By rmcdouga Date 2003-06-06 Time 14:30 Sent To  
Notes
2003-06-06 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT RECEIPT FOR IMPACT FEES.
  
 3) SUBMIT A SOIL BORING TEST REPORT.
  
 4) REVISE/CLARIFY NOTE #1 ON SHEET A-5.
 HANDRAIL AND GUARDRAIL ARE NOT THE SAME.
 SEE FBC 1007.5.1 FOR HANDRAIL HEIGHT.
  
 5) REVISE NOTE #7 UNDER SOFFIT SPECS. TO
 INDICATE THAT 3/8" HIGH RIB LATH IS
 REQUIRED TO BE ATTACHED AT EVERY RIB
 (4"O.C.) PER ASTM C 1063. ALSO NOTES 4
 AND 5 ARE THE SAME.
  
 6) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 1/2" DIA. EXPANSION ANCHOR ON THE WOOD
 FRAME TO CONCRETE WALL DETAIL ON A6.
 UPDATE THE SEMCO STUD TO PLATE CONNECTOR
 TO "USP" SPT OR SPTH OR EQUAL.
  
 7) CLARIFY THE C2 COLUMN SPECIFIED ON
 S1. THE SCHEDULE LISTS (2) 2X4 AND THE
 NOTE ON THE FOUNDATION PLAN SPECIFIES
 (3).
  
 8) THE 2003 USP CATALOG DOES NOT LIST A
 TP6X STUD TO PLATE CONNECTOR. PLEASE
 REVISE DETAILS 3/S1 AND E/S3 TO "USP"
 SPT OR SPTH OR EQUALS.
  
 9) THE STEEL COLUMN AT THE GARAGE IS
 SHOHN ON THE LOWER ROOF PLAN ON S-2
 CARRYING CARRYING (2) GIRDERS AT 90
 DEGREE ANGLES. DETAIL 4 DOES NOT ADDRESS
 THIS CONFIGURATION. PLEASE CLARIFY.
  
 10) SPECIFY THE FLOOR TRUSS TO CONC.
 WALL CONNECTOR ON DETAIL 1/S2.
  
 11) CLARIFY THE CONNECTION OF THE (2)
 GIRDER TRUSSES ON S2 THAT MEET ON AN
 ANGLE AT THE CORNER ABOVE THE FAMILY
 ROOM AND NOOK. DETAIL D/S2 IS SPECIFIED.
  
 12) REVISE THE ROOF SHEATHING NAILING
 DIAGRAM ON S3 TO INDICATE THAT THE
 GABLES AT THE ENTRY AND GARAGE ARE
 ZONE 3.
  
 13) REVISE TRUSS CONNECTOR UPLIFT
 CAPACITIES TO VALUES THAT DO NOT INCLUDE
 A ONE-THIRD INCREASE IN THE STEEL
 CALCULATIONS. THIS INCREASE IS NOT
 ALLOWED BY FBC 1609.4.3. SEE 2003 USP
 CATALOG.
  
 14) THE PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS EXPIRED 5/1/03.
  
 15) THE LOCATION OF THE JOB IS REQUIRED
 ON THE SITE SPECFIC ENGINEERING FORM.
  
 16) THE OWNER AND CONTRACTOR INFORMATION
 ON THE ENERGY CALCS. AND THE APPLICATION
 DO NOT MATCH CITY AND COUNTY RECORDS.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-02 Cont ID  
Sent By dpalmer Date 2003-10-02 Time 07:07 Rev Time 0.50
Received By dpalmer Date 2003-10-02 Time 07:07 Sent To  
Notes
2003-10-02 00:00:00REDLINED 210.8 KITCHEN
 210.52 BED RM.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-06 Cont ID  
Sent By csiegber Date 2003-09-23 Time 16:43 Rev Time 0.50
Received By btrobaug Date 2003-06-06 Time 08:16 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-23 Time 16:43 Rev Time 0.00
Received By csiegber Date 2003-09-23 Time 16:43 Sent To E
Notes
2003-09-23 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-16 Cont ID  
Sent By shernand Date 2003-06-16 Time 12:57 Rev Time 0.00
Received By shernand Date 2003-06-16 Time 12:57 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By pkrauss Date 2003-06-04 Time 10:15 Rev Time 0.25
Received By pkrauss Date 2003-06-04 Time 10:15 Sent To B
Notes
2003-06-04 00:00:00MECHANICAL PERMIT 03060226

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-19 Cont ID  
Sent By rmcdouga Date 2003-06-19 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2003-06-19 Time 13:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By kstevens Date 2003-06-04 Time 16:26 Rev Time 0.33
Received By kstevens Date 2003-06-04 Time 16:26 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-06 Cont ID  
Sent By shernand Date 2003-06-16 Time 12:57 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-04 Cont ID  
Sent By mmclean Date 2003-06-04 Time 08:30 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-04 00:00:006/4/03 DENIED, NEED COPY OF 2 SURVEY
 CALL CONTR GIVEN TO BILL STAPLES MM