2003-06-05 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT PAID RECEIPT FOR COUNTY IMPACT |
| FEES. |
| |
| 3) SUBMIT A SOIL BORING TEST REPORT AS |
| REQUIRED BY FBC 1804.2.2. |
| |
| 4) SUBMIT A SURVEY. |
| |
| 5) REVISE/CLARIFY NOTE #1 ON SHEET A-4. |
| HANDRAIL AND GUARDRAIL ARE NOT THE SAME. |
| SEE FBC 1007.5.1 FOR HANDRAIL HEIGHT. |
| |
| 6) REVISE STUCCO NOTES ON A5. SPECIFY |
| THE FASTENER SIZE IN NOTE 3. INDICATE IN |
| NOTE 7 THAT 3/8" METAL LATH IS REQUIRED |
| TO BE FASTENED AT EVERY RIB (4"O.C.). |
| NOTES 4 AND 5 ARE THE SAME. |
| |
| 7) REVISE THE GARAGE WALL SECTION ON A4. |
| UPDATE THE STUD TO PLATE CONNECTORS TO |
| TO "USP" SPT6 OR SPTH6 FOR 2X6 WALLS. |
| SEE 2003 USP CATALOG FOR NAILING REQUIRE |
| MENTS. REVISE THE UPLIFT CAPACITY OF THE |
| HDPT2 CONNECTOR. SPECIFY CONNECTORS FOR |
| ATTACHING THE TOP OF THE FIRST FLOOR TO |
| THE FLOOR TRUSSES. |
| |
| 8) SPECIFY THE FLOOR TRUSS TO WALL |
| CONNECTOR ON DETAIL 1 ON S2. |
| |
| 9) REVISE DETAIL C ON S2 TO INDICATE A |
| BUCKET THAT ATTACHES TO THE WALL AT AN |
| ANGLE AS SHOWN ON THE LOWER ROOF PLAN. |
| |
| 10) REVISE DETAIL 4 ON S2 TO MATCH THE |
| FLOOR PLAN WHICH SHOWS TWO GIRDERS |
| MEETING AT 90 DEGREE ANGLES. |
| |
| 11) SPECIFY THE LENGTH/EMBEDDMENT DEPTH |
| OF THE 1/2" DIAMETER EXP. ANCHORS AT THE |
| WOOD FRAME TO CONCRETE WALL DETAIL ON A5 |
| AND UPDATE THE SEMCO CONNECTORS. SEMCO |
| WAS PURCHASED BY USP. |
| |
| 12) DETAIL E ON S-3 IS INCORRECTLY |
| SPECIFIED FOR THE TRUSS ABOVE THE MASTER |
| BEDROOM. THIS WALL IS MASONRY AND NOT |
| WOOD FRAME. PLEASE CORRECT. |
| |
| 13) REVISE THE UPLIFT CAPACITIES FOR THE |
| TRUSS CONNECTORS TO REFLECT VALUES THAT |
| DO NOT HAVE STRESS INCREASES FOR THE |
| STEEL CALCULATIONS. SEE FBC 1609.4.3 AND |
| AND 2003 USP CATALOG. |
| |
| 14) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SLIDING GLASS DOORS |
| - OVERHEAD GARAGE DOOR |
| - ARCHED TO FIXED GLASS WINDOW |
| |
| 15) THE OWNER AND CONTRACTOR INFORMATION |
| ON THE ENERGY CALCULATIONS DOES NOT |
| MATCH THE APPLICATION OR CITY RECORDS. |
| |
| 16) THE OWNER INFORMATION LISTED ON THE |
| APPLICATION DOES NOT MATCH THE OWNER OF |
| RECORD WITH THE CITY OR COUNTY. |
| |
| 17) OWNER/AGENT IS REQUIRED TO SIGN THE |
| ENERGY CALCULATION FORM. |
| |