Plan Review Details - Permit 03060166
Plan Review Stops For Permit 03060166 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-21 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-21 |
Time |
10:49 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-06-03 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-03 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-03 |
Time |
15:56 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2003-07-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-07-25 |
Time |
14:11 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2003-07-25 |
Time |
14:11 |
Sent To |
|
|
Notes |
2003-07-25 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) TABLES SUBMITTED WITH PLANS ARE NOT | | APPROVED. | | 2) PLEASE INDICATE MANUFACTURE OF PE | | PIPE AND SUBMIT MANUF SHEETS. MANUF. | | INFORMATION REQUIRED FOR SIZING, CHART | | FROM MANUFACTURE REQUIRED. | | 3) DISTANCE FROM METER AND SIZE OF PIPE | | SHOW THAT A 1/2 POUND SYSTEM WILL BE | | INSUFFICIENT. EITHER 2" PIPE WILL BE RE- | | QUIRED OR INCREASE DELIVERY PRESSURE TO | | A 2 LB SYSTEM WITH REGULATORS. | | 4) CUT SHEET WILL BE REQUIRED FOR REG- | | ULATORS IF 2 LB SYSTEM IS USED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-06-20 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-21 |
Time |
10:50 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2003-06-20 |
Time |
09:03 |
Sent To |
|
|
Notes |
2003-06-20 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | 3. TYPE OF GAS, (LP OR NATURAL) | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|
|
|