Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-25 Cont ID  
Sent By kstevens Date 2003-07-25 Time 14:11 Rev Time 1.00
Received By kstevens Date 2003-07-25 Time 14:11 Sent To  
Notes
2003-07-25 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) TABLES SUBMITTED WITH PLANS ARE NOT
 APPROVED.
 2) PLEASE INDICATE MANUFACTURE OF PE
 PIPE AND SUBMIT MANUF SHEETS. MANUF.
 INFORMATION REQUIRED FOR SIZING, CHART
 FROM MANUFACTURE REQUIRED.
 3) DISTANCE FROM METER AND SIZE OF PIPE
 SHOW THAT A 1/2 POUND SYSTEM WILL BE
 INSUFFICIENT. EITHER 2" PIPE WILL BE RE-
 QUIRED OR INCREASE DELIVERY PRESSURE TO
 A 2 LB SYSTEM WITH REGULATORS.
 4) CUT SHEET WILL BE REQUIRED FOR REG-
 ULATORS IF 2 LB SYSTEM IS USED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-07-21 Time 10:50 Rev Time 1.00
Received By kstevens Date 2003-06-20 Time 09:03 Sent To  
Notes
2003-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692