Plan Review Details - Permit 03060103
Plan Review Stops For Permit 03060103
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-06-10 Cont ID  
Sent By btrobaug Date 2003-06-10 Time 12:05 Rev Time 0.75
Received By lsmith Date 2003-06-10 Time 12:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-06-10 Cont ID  
Sent By kstevens Date 2003-06-09 Time 18:43 Rev Time 0.50
Received By btrobaug Date 2003-06-10 Time 11:30 Sent To B
Notes
2003-06-10 00:00:00~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE THAT AN ELECTRICAL PERMIT IS
 NEEDED FOR THIS WORK,NO ELECTRICAL
 CONTRACTOR IS SIGNED ON THE APPLICATION
 AND THEREFORE MUST APPLY SEPARATELY.
  
 PLEASE PROVIDE THE FOLLOWING WITH
 ELECTRICAL APPLICATION:
  
 1} LOAD CALCULATIONS FOR THE SERVICE AND
 THE SIZE OF THE EXISTING SERVICE.
  
 2} A RISER DIAGRAM IF A NEW SERVICE IS
 BEING INSTALLED.
  
 3} A DRAWING INDICATING THE LOCATION OF
 THE NEW EQUIPMENT AND THE SIZE OF THE
 WIRE ,CONDUIT AND OCP SUPPLYING THE NEW
 EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 10:09 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 10:09 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-06-16 Cont ID  
Sent By pkrauss Date 2003-06-16 Time 08:33 Rev Time 0.25
Received By pkrauss Date 2003-06-16 Time 08:33 Sent To  
Notes
2003-06-16 00:00:001. AS PER CONVERSATION WITH DICK BOWEN
 (INSPECTOR) - FIELD CONDITIONS WILL NOT
 ALLOW FOR THE 4" CLEARANCE AROUND THE
 AHU. THIS WILL BE ACCEPTABLE
  
 THIS DETERMINATION WAS MADE AT THE
 REQUEST OF NAT HEALY IN COORIDANTION
 WITH THE CONTRACTOR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-06 Cont ID  
Sent By shernand Date 2003-06-03 Time 10:09 Rev Time 0.30
Received By pkrauss Date 2003-06-06 Time 07:17 Sent To P
Notes
2003-06-06 00:00:00PLEASE NOTE THE FOLLOWING INFORMATION:
  
 1.RETURN OR TRANSFER AIR REQUIRED FROM
 BEDROOM AREAS.2001 FBC(M) 601.4
  
 2.A MINIMUM OF 4" CLEARANCE AROUND
 AHU IS REQUIRED. 2001 FBC(M) 603.1.3
  
 3.EXHAUST FAN REQUIRED FROM BATHROOM
 AREAS.2001 FBC(M) 402.3.1
  
 4.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE.
 2001 FBC 1503.4.4

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-06-09 Cont ID  
Sent By pkrauss Date 2003-06-06 Time 07:27 Rev Time 0.25
Received By kstevens Date 2003-06-09 Time 18:42 Sent To E
Notes
2003-06-09 00:00:00NO PLUMBING PLANS SUBMITTED