Plan Review Details - Permit 03052313
Plan Review Stops For Permit 03052313
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-16 Cont ID  
Sent By jwitmer Date 2004-07-16 Time 09:24 Rev Time 0.75
Received By jwitmer Date 2004-07-16 Time 09:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-12 Cont ID  
Sent By jwitmer Date 2004-03-12 Time 16:39 Rev Time 6.00
Received By jwitmer Date 2004-03-12 Time 16:39 Sent To PC
Notes
2004-03-12 00:00:00BUILDING PLAN REVIEW
 PERMIT:03052313
 ADD: 2000 A. E. ISAACS AV
 CONT: DON CLAY
 TEL: (561)683-0609
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT #4 FROM 1ST REVIEW:
 STAIRS AT EXISTING DOOR 114B ARE MISSING
 LANDING AT DOOR! 1007.4.2 STAIRS SHALL
 HAVE FLOOR OR LANDING AT THE DOOR OPEN-
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-25 Cont ID  
Sent By jwitmer Date 2003-06-25 Time 10:31 Rev Time 3.50
Received By jwitmer Date 2003-06-25 Time 10:31 Sent To  
Notes
2003-06-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03052313
 ADD: 2000-6 AE ISAACS AVE
 CONT: PLAN REVIEW
 CONTACT PERSON: REGINALDA COX
 TEL: (561)573-1131
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE!!!!!!
 THE REQUIREMENTS OF THE FLORIDA ACCESS-
 IBILITY ACT MAY NOT REGULATE "CHURCHES"
 DEPENDING ON THE ACTIVITY OF THE BUILD-
 ING. SS 553.505 (1995) CH. 97-76 FL
 LAWS, RELIEVED BUILDINGS USED FOR COMMUN
 IAL RELIGIOUS OBSERVENCES FROM THE
 ACCESSIBILITY REQUIREMENTS OF THE ACT.
 FROM MEMO 8/16/98 ALFRED BRAGG III,
 ASSISTANT GENERAL COUNSEL
  
 IT APPEARS THAT THE DESIGNER IS TRYING
 TO MEET THE HANDICAPPED REQUIREMENTS,
 IN THIS REVIEW I WILL INDICATE ANY
 DISCPENANCIES TO THE FL ACCESSIBILITY
 CODE WITH (***) BEFORE THE COMMENT EVEN
 THOUGH IT MAY NOT BE ENFORCED.
  
 ACTION : DENIED
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS INDICATE 2 HR WALLS SEPERATING
 ASSEMBLY AREAS FROM THE EXIT ACCESS
 CORRIDORS TABLE 704.2.4 FOR UNSPRINKLER-
 ED BUILDINGS INDICATE A 1 HR RATING.
  
 3) 1019.7.2 GROUP A OCCUPANCY, EACH DOOR
 IN A MEANS OF EGRESS FROM AN AREA OF
 GROUP A OCCUPANCY MAY BE PROVIDED WITH A
 LATCH OR LOCK ONLY IF IT IS PANIC HARD-
 WARE OR FIRE EXIT HARDWARE.
 DOORS MISSING PANIC HARDWARE, 101,102,
 105,107,107B, 114 & 114B.
  
 4) STAIRS AT DOOR 114B MISSING LANDING
 AT DOOR! 1007.4.2 STAIRS SHALL HAVE
 FLOORS OR LANDINGS AT DOOR OPENINGS.
  
 5)1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.EXTERIOR STAIRS AS
 WELL AS INTERIOR.
  
 6)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
  
 7)1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 8) STAIRWELL SHAFT ENCLOSURE: TABLE
 705.1.2. SECOND FLOOR, (BUSINESS OCC)
 REQUIRES 1 HR.,MISSING AT FIRST FLOOR &
 DOOR 104, 705.2.3. ALSO SEE 1006.1.3.2
 FOR WINDOWS OPENINGS WITHIN 10' OF
 STAIRWELL SHAFTS, 3/4 HR OPENING PROTECT
 IVES.
  
 *** 9) PLATFORM # 099
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 *** 10) MANEUVERING CLEARENCES AT DOOR
 NUMBER 103, 107A, 109,& 114A.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 *** 11) COMPANION SEATING 11-4.1.6(3)
 (F)(I) EACH ACCESSIBLE SEATING AREA
 SHALL HAVE PROVISIONS FOR COMPANION SEAT
 ING AND SHALL BE LOCATED ON AN ACCESS-
 IBLE ROUTE THAT ALSO SERVES AS A MEANS
 OF EMERGENCY EGRESS.
  
 12) HANDRAILS FOR THE HANDICAPPED RAMP:
 TO COMPLY WITH TABLE 1004, 44" CLEAR BE
 TWEEN HANDRAILS, ALSO SEE EDGE PROTEC-
 TION (***) 11-4.8.8 FOR RAMP. NOTE ALSO
 SEE GUARDRAILS IN NOTE# 7 ABOVE.
  
 ****13) 11-4.4.8.4(3) HANDICAPPED RAMPS
 / LANDINGS, IF RAMPS CHANGE DIRECTION AT
 LANDINGS, A MIIMUM LANDING SIZE SHALL BE
 60"X60"(INSIDE OF THE HANDRAILS/ GUARD-
 RAIL SYSTEM NOT A OVERALL MEASUREMENT!
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-07-08 Cont ID  
Sent By dpalmer Date 2004-07-08 Time 14:42 Rev Time 0.75
Received By dpalmer Date 2004-07-08 Time 14:41 Sent To  
Notes
2004-07-08 00:00:00****** NOTE REDLINED ********
  
 1)NOTE: MISSING EQUIPMENT GRNDING
 AFTER THE FIRST MEANS OF DISCONNECT PER
 250.24,250.122

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-03-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 13:50 Rev Time 1.00
Received By dpalmer Date   Time   Sent To  
Notes
2004-03-03 00:00:00******** UNSAT *************
  
 1)NOTE: PLANS ARE NOW IN FOR PLAN REVIEW
 THE ELECTRICAL CODE HAS NOW CHANGED TO
 THE 2002 NEC AS OF JULY 1ST, 2003.
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS. THIS WAS ON FIRST
 REVIEW NOTES.
  
 3)NOTE: PLEASE CLARIFY LIGHTING IN MAIN
 SANCTUARY. NEW OR EXISTING? LS 101
  
 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 12 MONTH LOAD IS SHOWN, HOWEVER, HOW
 CAN THIS BE ACURATE DUE TO ADDITION OF
 NEW ELECTRICAL AND/ PANEL/LOADS??
 LOAD IS ALREADY SHOWN AT 196 A'S
 PLEASE DO LOAD CALCULATIONS PER ABOVE.
  
 5)NOTE: PLEASE SEE AN EQUIPMENT GROUND-
 -ING CONDUCTOR IS SHOWN FROM FPL TO
 MAIN?? PLEASE SEE 250.6, 250.24 THIS IS
 PARALLELING THE NEUTRAL.
 PLEASE VERIFY.
  
 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 61G1-16.004. PLEASE INCLUDE ALL INFORMAT
 -ION ON TITLE BLOCKS FOR ARCH/ ENG.
 THIS IS REQUIRED FOR ALL TRADES AND
 ALL SHEETS WEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 PLEASE INCLUDE CERTIFICATE OF AUTHORIZ-
 ATION REQ'D PER FS 471.023, 481.221
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By dpalmer Date 2003-06-10 Time 13:51 Rev Time 0.50
Received By dpalmer Date 2003-06-10 Time 13:51 Sent To  
Notes
2003-06-10 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS SUND CORRELATE W/ A SUBMITTED
 PANEL SCHEDULE.
 PLEASE CIRCUIT ANY EM/ EXT LTS PER
 700-12E
  
 2)NOTE: PLEASE NOTE, LATEST ELECTRICAL
 EDITION OF NEC CURRENTLY ADOPTED BY
 CITY OF WPB IS 99.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By nmccray Date 2004-07-08 Time 16:17 Rev Time 0.00
Received By nmccray Date 2004-07-08 Time 16:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-13 Cont ID  
Sent By mcarsill Date 2003-06-13 Time 08:01 Rev Time 0.00
Received By mcarsill Date 2003-06-13 Time 08:01 Sent To  
Notes
2003-06-13 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) IT APPEARS DOORS 103, AND 106 ARE
 LOCATED IN RATED FIRE WALLS. DOORS
 ACCORDING TO SCHEDULE ARE NOT RATED.
  
 3) DOORS 101, 107, 107B, 114, 114B IF
 SUBJECT TO A 100 OR MORE PERSONS SHALL
 BE EQUIPPED WITH PANIC HARDWARE.
  
 4) IT DOES NOT APPEAR THAT DOOR 201
 NEEDS PANIC HARDWARE.
  
 5) DOES THE EXISTING STAIR OPPOSITE OF
 DOOR 114B HAVE HANDRAILS ON BOTH SIDES.
  
 6) ARE THE NEW STORAGE ROOM WALLS
 108 AND 113 RATED OR NON RATED.
  
 7) HOW IS PLATFORM 099 HANDICAP
 ACCESSIBLE.
  
 8) PROVIDE DETAILS ON RISE, RUN, AND
 TREAD DEPTH AND STAIR WIDTH FOR STAIR
 # 104.
  
 9) ENSURE BUILDING ADDRESS. MINIMUM 6"
 HIGH ON PROPER ELEVATION.
  
 10) ARE EMERGENCY LIGHTS PRESENT IN
 MAIN SEATING AREA.
  
 11) PLEASE INDICATE LOCATIONS OF
 HANDICAPPED SEATING IN CHAPEL 100.
  
 12) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 13) DOOR 104 DOES NOT NEED PANIC
 HARDWARE.
  
 14) ALL NEW STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 15) PLEASE INDICATE EXISTING FIRE
 SPRINKLER OR FIRE ALARM SYSTEM
 EQUIPMENT CONTAINED WITHIN THE
 BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-06-30 Time 15:09 Rev Time 0.00
Received By csiegber Date 2004-06-30 Time 15:09 Sent To  
Notes
2004-06-30 00:00:00TO COMM BD#49

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 16:28 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 16:28 Sent To  
Notes
2003-05-30 00:00:00COMM BOARD #7

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-27 Cont ID  
Sent By lmartine Date 2004-07-27 Time 11:58 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-07-27 00:00:00SUBMITTAL OK PER PHONE CONVERSATION WITH
 PATTYLM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-07-09 Cont ID  
Sent By pkrauss Date 2004-07-09 Time 09:00 Rev Time 0.40
Received By pkrauss Date 2004-07-09 Time 08:02 Sent To  
Notes
2004-07-09 00:00:00DENIED:2ND REQUEST
 COMMENT FROM REVIEW DATED 3-4-04:
 PLANS INDICATE DUCT PENETRATING RATED
 WALLS.FIRE DAMPERS ARE NOT INDICATED
 ON THE PLAN.PER 2001 FBC(M) 607.6,
 FIRE DAMPERS AND ACCESS DOORS ARE TO
 BE INDENTIFIED ON THE PLAN.PROVIDE
 DETAIL FOR FIRE DAMPER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-04 Cont ID  
Sent By pkrauss Date 2004-03-04 Time 06:40 Rev Time 0.55
Received By pkrauss Date 2004-03-04 Time 06:40 Sent To  
Notes
2004-03-04 00:00:00DENIED:
 PLANS INDICATE DUCTS PENETRATING RATED
 WALLS.FIRE DAMPERS ARE NOT INDICATED
 ON THE PLAN.PER 2001 FBC(M) 607.6,
 SPECIFIC LOCATION OF FIRE DAMPERS AND
 ACCESS DOOR ARE TO BE INDENTIFIED ON
 THE PLAN.
  
 EXEMPTIONS FOR FIRE DAMPERS SHALL COMPLY
 WITH 2001 FBC(M) 607.1.3 #3 ITEMS 1 THR
 OUGH 4.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-07-27 Cont ID  
Sent By kstevens Date 2004-07-27 Time 11:49 Rev Time 0.50
Received By kstevens Date 2004-07-27 Time 11:49 Sent To  
Notes
2004-07-27 00:00:00 
  
  
  
  
 PASSED/PROVISO - REVISION REQUIRED FOR
 SANT. RISER DIAGRAM FOR ROOM 103 SHOWING
 SERVICE SINK ADDED TO FLOOR PLAN. TO BE
 SUBMITTED BY 8-4-4 KSTEVENS
  
  
  
  
  
  
  
  
  
  
  
 Z

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-07-20 Cont ID  
Sent By kstevens Date 2004-07-20 Time 11:12 Rev Time 1.00
Received By kstevens Date 2004-07-20 Time 11:12 Sent To  
Notes
2004-07-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEWS: A SERVICE SINK
 IS REQUIRED PER TABLE 403.1. PER CONVER-
 SATION WITH THE BUILDING OFFICIAL, THERE
 IS NO CODE REFERENCE ALLOWING MINIMUM
 FACILITIES FOR FIXTURES TO BE WAIVED BE-
 CAUSE OF CLOSE PROXIMITY TO A FIXTURE IN
 ANOTHER BUILDING. EACH BUILDING SHALL
 HAVE REQUIRED FIXTURES INSTALLED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-03-01 Cont ID  
Sent By kstevens Date 2004-03-01 Time 08:47 Rev Time 1.00
Received By kstevens Date 2004-02-26 Time 17:04 Sent To  
Notes
2004-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW, A SERVICE SINK
 IS REQUIRED PER TABLE 403.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-18 Cont ID  
Sent By kstevens Date 2003-06-18 Time 18:09 Rev Time 4.50
Received By kstevens Date 2003-06-18 Time 18:09 Sent To  
Notes
2003-06-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) A DRINKING FOUNTAIN (ALSO SEE SECTION
 410.1) AND A SERVICE SINK ARE REQUIRED
 PER TABLE 403.1.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692