Plan Review Details - Permit 03052278
Plan Review Stops For Permit 03052278
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-03 Cont ID  
Sent By sthyng Date 2003-09-03 Time 15:40 Rev Time 1.00
Received By sthyng Date 2003-09-03 Time 15:40 Sent To  
Notes
2003-09-03 00:00:00PROVISO - SUBMIT MULLION PRODUCT
 APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-08-08 Cont ID  
Sent By pkrauss Date 2003-09-03 Time 06:50 Rev Time 3.00
Received By sthyng Date 2003-08-08 Time 17:03 Sent To M
Notes
2003-08-08 00:00:00******CORRECTIONS*******
  
 1.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, WHEN A CORRECT ENERGY CALC
 IS SUBMITTED.
  
 2.)THE SPEC SHEETS ARE MISSING FROM
 THE RESIDENTIAL STEEL DOOR PRODUCT
 APPROVAL.
  
 3.)THE GLASS BLOCK PRODUCT APPROVAL
 IS ILLEGIBLE.
  
 4.)THE GARAGE DOOR SPEC SHEETS ARE
 ILLEGIBLE.
  
 5.)PROVIDE A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE AND TWO LEGIBLE
 PRODUCT APPROVALS.PRODUCT APPROVALS
 SUBMITTED ARE MISSING SHEETS.IF THE
 ATTACHMENT SCHEDULE AND TWO COMPLETE,
 LEGIBLE PRODUCT APPROVALS ARE NOT
 SUBMITTED, A SEPARATE PERMIT FOR
 HURRICANE SHUTTERS MAY BE APPLIED FOR
 LATER.
  
 6.)SEE PREVIOUS CORRECTION LIST, ITEM
 15.PLEASE EXPLAIN HOW A TWO STORY
 HOUSE HAS THE SAME SQUARE FOOT AREA
 UNDER AIR AS UNDER ATTIC.
  
 7.)ONLY ONE SINGLE HUNG PRODUCT
 APPROVAL WAS SUBMITTED.SUBMIT A SECOND
 COPY.
  
 8.)A COMMENT WAS MADE IN REGARDS TO
 THE FIXED GLASS WINDOW PRODUCT APPROVAL
 ON THE PREVIOUS LIST, ITEM #18.NONE
 WAS SUBMITTED THIS TIME.EITHER SUBMIT,
 OR A SEPARATE PERMIT WILL BE REQUIRED.
  
 9.) THERE ARE TWO ADJACENT WALLS ON THE
 ENERGY CALC; SHOULD ONE BE EXTERIOR?
  
 10.) ROOF PRODUCT APPROVALS WERE NOT
 SUBMITTED.SUBMIT, OR A SEPARATE PERMIT
 WILL BE REQUIRED.
  
 11.) SEE PREVIOUS CORRECTION NOTICE
 REGARDING PRODUCT APPROVALS.ALSO, SOME
 WHICH WERE IN THE PACKAGE PREVIOUSLY
 APPEAR TO BE NO LONGER IN THE PACKAGE.
 ANY PRODUCT APPROVALS NOT SUBMITTED
 BEFORE THE TIME THE PERMIT IS ISSUED
 WILL REQUIRE THAT A SEPARATE PERMIT FOR
 THOSE ITEMS WILL BE NEEDED.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By jleech Date 2003-08-07 Time 18:55 Rev Time 3.00
Received By sthyng Date 2003-07-08 Time 14:56 Sent To  
Notes
2003-07-08 00:00:00******CORRECTIONS********
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THE ORIGINAL RECEIPT SHOWING THAT
 IMPACT FEES HAVE BEEN PAID MUST BE
 ATTACHED TO THE APPLICATION.
  
 3.)THE AREA CALCULATIONS SHOULD SHOW
 SUBTOTALS FOR CONDITIONED AND UNCONDIT.
 SPACE.IMPACT FEES WERE PAID ON A
 SQUARE FOOTAGE LESS THAN THE TOTAL A/C
 SQUARE FOOTAGE.CALL 233-5025 TO
 DETERMINE WHETHER OR NOT IMPACT FEES
 NEED TO BE ADJUSTED.
  
 4.)THE TOTAL CONDITIONED FLOOR AREA
 ON THE ENERGY CALC IS INCORRECT.
  
 5.)ADDITIONAL FEES ARE DUE (VALUE
 ADJUSTMENT); $755.07.
  
 6.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 7.)THE 2ND FLOOR BATHROOM WINDOW MUST
 COMPLY WITH FBC 2405.1 (SAFETY GLASS).
  
 8.)PROVIDE DETAILS FOR THE GUARDRAIL
 AND THE STAIR RAIL, GIVING ALL
 DIMENSIONS AND SHOWING COMPLIANCE WITH
 FBC 1608.2.
  
 9.)PROVIDE A ROOF SHEATHING ATTACHMENT
 SCHEDULE.
  
 10.) SHOW THE FIRESTOP FOR THE FRAME
 WALL, FBC 705.3.
  
 11.)THE ENERGY CALC DOES NOT SHOW THE
 2X6 EXTERIOR FRAME WALL.PROVIDE A
 WALL LEGEND.
  
 12.)FOR CLARIFICATION, EXPLAIN THE
 DIFFERENCE BETWEEN COLUMN A AND COLUMN
 B.THE TEXT DESCRIPTIONS ARE THE SAME.
 (SHEET 6).
  
 13.)THE 2ND FLOOR PLAN (SHEET 4) SHOWS
 FRENCH DOORS AT THE OPEN AREA.SHEET
 7 SHOWS S/H WINDOWS AT THAT LOCATION.
  
 14.)SHOW INSULATION FOR THE ADJACENT
 WALL, SHEET 6.
  
 15.)THE SQUARE FOOTAGE FOR 10A ON THE
 ENERGY CALC IS INCORRECT.
  
 16.)THE FOLLOWING PRODUCT APPROVALS
 ARE NOT LEGIBLE:
 PREMDOOR
 GARAGE DOOR
 SHUTTERS
 PROVIDE TWO LEGIBLE COPIES.SEE
 ATTACHED FOR INSTRUCTIONS TO OBTAIN
 PRODUCT APPROVALS ONLINE.
  
 17.)THE FOLLOWING PRODUCT APPROVALS
 ARE REQUIRED BUT WERE NOT SUBMITTED:
 DOUBLE FRENCH DOOR (UNLESS PREMDOOR
 IS USED IN ALL OF THE LOCATIONS)
 SINGLE FRENCH DOOR
 GLASS BLOCK
 MULLIONS
 EXTERIOR SIDE DOOR
  
 18.)THE REPORT FOR THE FIXED GLASS
 WINDOWS USED ASTM E330-90 AS THE
 STRUCTURAL TEST.FBC35 SPECIFIES
 ASTM E330-84.SUBMIT TWO COPIES OF
 PRODUCT APPROVALS FOR THE FIXED GLASS
 WINDOW.
  
 WHEN RESUBMITTING, REPLACE ANY SHEETS
 WHICH HAVE CHANGED WITH NEW SHEETS.
 SUBMIT THE OLD SHEETS SEPARATELY,
 MARKED.SUBMIT THIS CORRECTION LIST
 WITH A WRITTEN EXPLANATION AS TO HOW
 EACH ITEM WAS ADDRESSED.ALL CHANGES
 SHOULD BE CLEARLY MARKED WITH EITHER
 CLOUDS OR TRIANGLES.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-30 Cont ID  
Sent By btrobaug Date 2004-03-30 Time 14:52 Rev Time 0.50
Received By btrobaug Date 2004-03-30 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-05 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:48 Rev Time 0.50
Received By btrobaug Date 2003-08-01 Time 15:35 Sent To P
Notes
2003-08-01 00:00:00THE REVISED ELECTRICAL SHEETS WERE OMIT
 TED FROM THE SET.CALLED RODNEY TO BRING
 THEM IN AND CHANGE OUT.
  
 WRT 8/1/03 3:41 PM.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-13 Cont ID  
Sent By alange Date 2003-07-25 Time 09:51 Rev Time 0.50
Received By btrobaug Date 2003-06-13 Time 11:25 Sent To P
Notes
2003-06-13 00:00:00FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 PLANS AND RESUBMIT FOR REVIEW.
  
 1}NOTE THAT THERE ARE TWO AHU'S ON THE
 PANEL SCHEDULE AND ONLY ONE LISTED IN
 THE CALCULATIONS.
  
 2}PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3}PLEASE NOTE THAT DISCONNECTS MUST
 COMPLY WITH 110-26.
  
 4}PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210-52E.
  
 5}PLEASE SHOW THE REQ'D BATH(S)
 RECEPTACLES PER 210-52(D).
  
 6}THE AHU CLOSET IS MISSING IN THE ATTIC
 STORAGE ROOM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:47 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 14:46 Sent To E
Notes
2004-03-25 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-17 Time 14:37 Rev Time 0.00
Received By csiegber Date 2003-11-17 Time 14:37 Sent To M
Notes
2003-11-17 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-27 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 14:25 Rev Time 0.00
Received By dbaxter Date 2003-08-27 Time 14:25 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-25 Cont ID  
Sent By alange Date 2003-07-25 Time 09:51 Rev Time 0.00
Received By alange Date 2003-07-25 Time 09:51 Sent To E
Notes
2003-07-25 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-04 Time 15:30 Rev Time 0.00
Received By shernand Date 2003-06-04 Time 15:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-02 Time 09:21 Rev Time 0.00
Received By shernand Date 2003-06-02 Time 09:21 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-12-01 Cont ID  
Sent By hmoser Date 2003-12-01 Time 16:57 Rev Time 0.50
Received By hmoser Date 2003-12-01 Time 16:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-11-17 Time 14:37 Rev Time 0.25
Received By pkrauss Date 2003-09-03 Time 06:49 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 14:25 Rev Time 0.15
Received By pkrauss Date 2003-08-12 Time 08:12 Sent To  
Notes
2003-08-12 00:00:00DENIED:
  
 COMMENTS FROM HAROLD MOSER DATED 6-21-03
 WERE NOT ADDRESSED. PLANS WITH ENGINEERS
 TITLE BLOCK SHALL BE SIGNED, DATED AND
 SEALED AS PER FAC 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-21 Cont ID  
Sent By sthyng Date 2003-08-08 Time 17:04 Rev Time 0.25
Received By hmoser Date 2003-06-21 Time 12:01 Sent To B
Notes
2003-06-21 00:00:00PLAN DENIED
 PLAN IS ON ENGINEER PAPPER,PLAN MUST BE
 STAMPED BY ENGINEER.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-07 Cont ID  
Sent By pkrauss Date 2003-09-03 Time 06:49 Rev Time 0.50
Received By jleech Date 2003-08-07 Time 18:54 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-21 Cont ID  
Sent By btrobaug Date 2003-08-05 Time 11:01 Rev Time 0.50
Received By jleech Date 2003-06-21 Time 10:20 Sent To M
Notes
2003-06-21 00:00:00DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN
 AND IS NOT TO CODE.
 1.SECOND FLOOR BATHROOM REQUIRES IT'S
 OWN WASTE STACK IT CANNOT DUMP INTO
 VENT STACK FOR FIRST FLOOR BATHROOM.
 2.FLOOR PLAN SHOWS TUB ON SECOND FLOOR
 NOT SHOWER.
 3.FIRST FLOOR OFFICE BATHROOM FLOOR PLAN
 SHOWS TUB RISER DIAGRAM SHOWS SHOWER.
 4.MASTER BATHROOM, RISER DIAGRAM SHOWS
 2- SHOWERS AND 3- LAVS. FLOOR PLAN
 SHOWS 1-TUB, 1-SHOWER AND 2-LAVS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-02 Time 09:21 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***