Plan Review Stops For Permit 03052278 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2003-09-03 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-09-03 |
Time |
15:40 |
Rev Time |
1.00 |
Received By |
sthyng |
Date |
2003-09-03 |
Time |
15:40 |
Sent To |
|
|
Notes |
2003-09-03 00:00:00 | PROVISO - SUBMIT MULLION PRODUCT | | APPROVALS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2003-08-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-09-03 |
Time |
06:50 |
Rev Time |
3.00 |
Received By |
sthyng |
Date |
2003-08-08 |
Time |
17:03 |
Sent To |
M |
|
Notes |
2003-08-08 00:00:00 | ******CORRECTIONS******* | | | | 1.)SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALC, WHEN A CORRECT ENERGY CALC | | IS SUBMITTED. | | | | 2.)THE SPEC SHEETS ARE MISSING FROM | | THE RESIDENTIAL STEEL DOOR PRODUCT | | APPROVAL. | | | | 3.)THE GLASS BLOCK PRODUCT APPROVAL | | IS ILLEGIBLE. | | | | 4.)THE GARAGE DOOR SPEC SHEETS ARE | | ILLEGIBLE. | | | | 5.)PROVIDE A HURRICANE SHUTTER | | ATTACHMENT SCHEDULE AND TWO LEGIBLE | | PRODUCT APPROVALS.PRODUCT APPROVALS | | SUBMITTED ARE MISSING SHEETS.IF THE | | ATTACHMENT SCHEDULE AND TWO COMPLETE, | | LEGIBLE PRODUCT APPROVALS ARE NOT | | SUBMITTED, A SEPARATE PERMIT FOR | | HURRICANE SHUTTERS MAY BE APPLIED FOR | | LATER. | | | | 6.)SEE PREVIOUS CORRECTION LIST, ITEM | | 15.PLEASE EXPLAIN HOW A TWO STORY | | HOUSE HAS THE SAME SQUARE FOOT AREA | | UNDER AIR AS UNDER ATTIC. | | | | 7.)ONLY ONE SINGLE HUNG PRODUCT | | APPROVAL WAS SUBMITTED.SUBMIT A SECOND | | COPY. | | | | 8.)A COMMENT WAS MADE IN REGARDS TO | | THE FIXED GLASS WINDOW PRODUCT APPROVAL | | ON THE PREVIOUS LIST, ITEM #18.NONE | | WAS SUBMITTED THIS TIME.EITHER SUBMIT, | | OR A SEPARATE PERMIT WILL BE REQUIRED. | | | | 9.) THERE ARE TWO ADJACENT WALLS ON THE | | ENERGY CALC; SHOULD ONE BE EXTERIOR? | | | | 10.) ROOF PRODUCT APPROVALS WERE NOT | | SUBMITTED.SUBMIT, OR A SEPARATE PERMIT | | WILL BE REQUIRED. | | | | 11.) SEE PREVIOUS CORRECTION NOTICE | | REGARDING PRODUCT APPROVALS.ALSO, SOME | | WHICH WERE IN THE PACKAGE PREVIOUSLY | | APPEAR TO BE NO LONGER IN THE PACKAGE. | | ANY PRODUCT APPROVALS NOT SUBMITTED | | BEFORE THE TIME THE PERMIT IS ISSUED | | WILL REQUIRE THAT A SEPARATE PERMIT FOR | | THOSE ITEMS WILL BE NEEDED. | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-07-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2003-08-07 |
Time |
18:55 |
Rev Time |
3.00 |
Received By |
sthyng |
Date |
2003-07-08 |
Time |
14:56 |
Sent To |
|
|
Notes |
2003-07-08 00:00:00 | ******CORRECTIONS******** | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2.)THE ORIGINAL RECEIPT SHOWING THAT | | IMPACT FEES HAVE BEEN PAID MUST BE | | ATTACHED TO THE APPLICATION. | | | | 3.)THE AREA CALCULATIONS SHOULD SHOW | | SUBTOTALS FOR CONDITIONED AND UNCONDIT. | | SPACE.IMPACT FEES WERE PAID ON A | | SQUARE FOOTAGE LESS THAN THE TOTAL A/C | | SQUARE FOOTAGE.CALL 233-5025 TO | | DETERMINE WHETHER OR NOT IMPACT FEES | | NEED TO BE ADJUSTED. | | | | 4.)THE TOTAL CONDITIONED FLOOR AREA | | ON THE ENERGY CALC IS INCORRECT. | | | | 5.)ADDITIONAL FEES ARE DUE (VALUE | | ADJUSTMENT); $755.07. | | | | 6.)PROVIDE A SOILS INVESTIGATION | | REPORT. | | | | 7.)THE 2ND FLOOR BATHROOM WINDOW MUST | | COMPLY WITH FBC 2405.1 (SAFETY GLASS). | | | | 8.)PROVIDE DETAILS FOR THE GUARDRAIL | | AND THE STAIR RAIL, GIVING ALL | | DIMENSIONS AND SHOWING COMPLIANCE WITH | | FBC 1608.2. | | | | 9.)PROVIDE A ROOF SHEATHING ATTACHMENT | | SCHEDULE. | | | | 10.) SHOW THE FIRESTOP FOR THE FRAME | | WALL, FBC 705.3. | | | | 11.)THE ENERGY CALC DOES NOT SHOW THE | | 2X6 EXTERIOR FRAME WALL.PROVIDE A | | WALL LEGEND. | | | | 12.)FOR CLARIFICATION, EXPLAIN THE | | DIFFERENCE BETWEEN COLUMN A AND COLUMN | | B.THE TEXT DESCRIPTIONS ARE THE SAME. | | (SHEET 6). | | | | 13.)THE 2ND FLOOR PLAN (SHEET 4) SHOWS | | FRENCH DOORS AT THE OPEN AREA.SHEET | | 7 SHOWS S/H WINDOWS AT THAT LOCATION. | | | | 14.)SHOW INSULATION FOR THE ADJACENT | | WALL, SHEET 6. | | | | 15.)THE SQUARE FOOTAGE FOR 10A ON THE | | ENERGY CALC IS INCORRECT. | | | | 16.)THE FOLLOWING PRODUCT APPROVALS | | ARE NOT LEGIBLE: | | PREMDOOR | | GARAGE DOOR | | SHUTTERS | | PROVIDE TWO LEGIBLE COPIES.SEE | | ATTACHED FOR INSTRUCTIONS TO OBTAIN | | PRODUCT APPROVALS ONLINE. | | | | 17.)THE FOLLOWING PRODUCT APPROVALS | | ARE REQUIRED BUT WERE NOT SUBMITTED: | | DOUBLE FRENCH DOOR (UNLESS PREMDOOR | | IS USED IN ALL OF THE LOCATIONS) | | SINGLE FRENCH DOOR | | GLASS BLOCK | | MULLIONS | | EXTERIOR SIDE DOOR | | | | 18.)THE REPORT FOR THE FIXED GLASS | | WINDOWS USED ASTM E330-90 AS THE | | STRUCTURAL TEST.FBC35 SPECIFIES | | ASTM E330-84.SUBMIT TWO COPIES OF | | PRODUCT APPROVALS FOR THE FIXED GLASS | | WINDOW. | | | | WHEN RESUBMITTING, REPLACE ANY SHEETS | | WHICH HAVE CHANGED WITH NEW SHEETS. | | SUBMIT THE OLD SHEETS SEPARATELY, | | MARKED.SUBMIT THIS CORRECTION LIST | | WITH A WRITTEN EXPLANATION AS TO HOW | | EACH ITEM WAS ADDRESSED.ALL CHANGES | | SHOULD BE CLEARLY MARKED WITH EITHER | | CLOUDS OR TRIANGLES. | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2004-03-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-03-30 |
Time |
14:52 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-03-30 |
Time |
14:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-08-05 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-25 |
Time |
14:48 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-08-01 |
Time |
15:35 |
Sent To |
P |
|
Notes |
2003-08-01 00:00:00 | THE REVISED ELECTRICAL SHEETS WERE OMIT | | TED FROM THE SET.CALLED RODNEY TO BRING | | THEM IN AND CHANGE OUT. | | | | WRT 8/1/03 3:41 PM. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-06-13 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-07-25 |
Time |
09:51 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-06-13 |
Time |
11:25 |
Sent To |
P |
|
Notes |
2003-06-13 00:00:00 | FAILED | | ~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE NECESSARY CHANGES ON | | PLANS AND RESUBMIT FOR REVIEW. | | | | 1}NOTE THAT THERE ARE TWO AHU'S ON THE | | PANEL SCHEDULE AND ONLY ONE LISTED IN | | THE CALCULATIONS. | | | | 2}PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 3}PLEASE NOTE THAT DISCONNECTS MUST | | COMPLY WITH 110-26. | | | | 4}PLEASE NOTE FRONT AND REAR | | RECEPTS REQ'D PER 210-52E. | | | | 5}PLEASE SHOW THE REQ'D BATH(S) | | RECEPTACLES PER 210-52(D). | | | | 6}THE AHU CLOSET IS MISSING IN THE ATTIC | | STORAGE ROOM. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2004-03-25 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-25 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-25 |
Time |
14:46 |
Sent To |
E |
|
Notes |
2004-03-25 00:00:00 | TO BT DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2003-11-17 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-11-17 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-11-17 |
Time |
14:37 |
Sent To |
M |
|
Notes |
2003-11-17 00:00:00 | TO PK BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2003-08-27 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-27 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
dbaxter |
Date |
2003-08-27 |
Time |
14:25 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-07-25 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-07-25 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2003-07-25 |
Time |
09:51 |
Sent To |
E |
|
Notes |
2003-07-25 00:00:00 | TO BT DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-06-04 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-04 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-04 |
Time |
15:30 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-06-02 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-02 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-02 |
Time |
09:21 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2003-12-01 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2003-12-01 |
Time |
16:57 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2003-12-01 |
Time |
16:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2003-09-03 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-11-17 |
Time |
14:37 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2003-09-03 |
Time |
06:49 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2003-08-12 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-27 |
Time |
14:25 |
Rev Time |
0.15 |
Received By |
pkrauss |
Date |
2003-08-12 |
Time |
08:12 |
Sent To |
|
|
Notes |
2003-08-12 00:00:00 | DENIED: | | | | COMMENTS FROM HAROLD MOSER DATED 6-21-03 | | WERE NOT ADDRESSED. PLANS WITH ENGINEERS | | TITLE BLOCK SHALL BE SIGNED, DATED AND | | SEALED AS PER FAC 61G15-23.002. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-06-21 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-08-08 |
Time |
17:04 |
Rev Time |
0.25 |
Received By |
hmoser |
Date |
2003-06-21 |
Time |
12:01 |
Sent To |
B |
|
Notes |
2003-06-21 00:00:00 | PLAN DENIED | | PLAN IS ON ENGINEER PAPPER,PLAN MUST BE | | STAMPED BY ENGINEER. | | PLAN REVIEW BY HAROLD MOSER | | (561)805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-08-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-09-03 |
Time |
06:49 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2003-08-07 |
Time |
18:54 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-06-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-08-05 |
Time |
11:01 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2003-06-21 |
Time |
10:20 |
Sent To |
M |
|
Notes |
2003-06-21 00:00:00 | DENIED; | | RISER DIAGRAM DOES NOT MATCH FLOOR PLAN | | AND IS NOT TO CODE. | | 1.SECOND FLOOR BATHROOM REQUIRES IT'S | | OWN WASTE STACK IT CANNOT DUMP INTO | | VENT STACK FOR FIRST FLOOR BATHROOM. | | 2.FLOOR PLAN SHOWS TUB ON SECOND FLOOR | | NOT SHOWER. | | 3.FIRST FLOOR OFFICE BATHROOM FLOOR PLAN | | SHOWS TUB RISER DIAGRAM SHOWS SHOWER. | | 4.MASTER BATHROOM, RISER DIAGRAM SHOWS | | 2- SHOWERS AND 3- LAVS. FLOOR PLAN | | SHOWS 1-TUB, 1-SHOWER AND 2-LAVS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-06-04 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-02 |
Time |
09:21 |
Rev Time |
1.00 |
Received By |
mmclean |
Date |
|
Time |
|
Sent To |
E |
|
Notes |
|
|