Plan Review Details - Permit 03051875
Plan Review Stops For Permit 03051875
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-17 Cont ID  
Sent By sthyng Date 2003-09-17 Time 15:33 Rev Time 0.50
Received By sthyng Date 2003-09-17 Time 15:33 Sent To  
Notes
2003-09-17 00:00:00REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-15 Cont ID  
Sent By rmcdouga Date 2003-07-15 Time 09:17 Rev Time 3.00
Received By rmcdouga Date 2003-07-15 Time 09:17 Sent To  
Notes
2003-07-15 00:00:00BUILDING PROVISO
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) SUBMIT AN INSTALLATION SCHEDULE AND A
 KEY PLAN FOR THE STORM PANELS.
  
 3) SUBMIT REVISED WINDLOADS FOR ALL
 EXTERIOR OPENINGS BASED ON EXPOSURE
 CATEGORY B.
  
 4) SUBMIT A REVISED CONNECTOR SCHEDULE
 FOR THE TRUSSES PRIOR TO INSTALLATION.
  
 5) SUBMIT A CURRENT PRODUCT APPROVAL FOR
 THE HORIZONTAL SLIDING WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-02 Cont ID  
Sent By rmcdouga Date 2003-07-02 Time 11:26 Rev Time 5.00
Received By rmcdouga Date 2003-07-02 Time 11:25 Sent To  
Notes
2003-07-02 00:00:00BUILDING DENIED
  
 1) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED PRIOR TO C.O.
  
 2) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED AT THE ZERO LOT LINE. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION.
  
 3) THE DOUBLE FRONT DOOR DOES NOT COMPLY
 WITH EGRESS REQUIREMENTS. EXIT DOOR MUST
 BE OF THE SIDE SWINGING TYPE WITH A MIN.
 CLEAR OPENING OF 32". SEE FBC TABLE 1004
 AND SECTIONS 1003.2.3.1 AND 1012.1.
  
 4) INDICATE THE LOCATIONS AND MATERIALS
 FOR THE DRAFTSTOPPING THAT IS REQUIRED
 AT THE FLOOR/CEILING ASSEMBLY. SEE FBC
 2305.2.2.
  
 5) DETAIL 2 ON S-5 AND SECTION D-D ON
 S-5 FOR THE GIRDER HANGER APPEAR TO BE
 IN ERROR. THE CEILING HEIGHT (BOTTOM OF
 THE GIRDER) IS 10'AND THE TOP OF THE
 BOND BEAM IS AT 10'-8". THE TOP ANCHOR
 HOLE IS AT 11', WHICH WILL BE ABOVE THE
 BOND BEAM. SHEET S-1 INDICATES FILLED
 CELLS BELOW THE BOND BEAM, BUT NOT ABOVE
 IT. PLEASE CORRECT.
  
 6) SAFETY GLAZING IS REQUIRED IN THE
 MASTER BATHROOM WINDOW PER FBC 2405.2.
 PLEASE INDICATE THIS ON PLANS.
  
 7) WALL SECTION 1 ON A1.02 INCORRECTLY
 SPECIFIES THAT THE ROOF SHEATHING IS
 NAILED AT 16" O.C. SEE CITY AMENDMENTS
 TO FBC TABLE 2306.1. PLEASE CORRECT.
  
 8) FBC 1609.4 NO LONGER ALLOWS THE ONE-
 THIRD INCREASE ON STEEL CALCULATIONS.
 PLEASE REVISE THE CONNECTOR SCHEDULE ON
 SHEET S-3. THE VALUES FOR THE SIMPSON
 H-16, HETAL20, META16 AND USP RT24T ARE
 INCORRECT. SEE THE 2003 USP AND 2002
 SIMPSON HIGH-WIND RESISTANT CONSTRUCTION
 CATALOGS.
  
 9) SUBMIT A KEY PLAN FOR THE STORM
 PANELS. THE INSTALLATION SCHEDULE HAS
 SOME ERRORS. THE PANELS ARE SPECIFIED AS
 ALL BEING MOUNTED VERTICALLY, HOWEVER,
 THE SHUTTER SPANS LISTED INDICATE THEY
 ARE MOUNTED HORIZONTALLY. TABLE 5 ON THE
 PRODUCT REQUIRE A MINIMUM PANEL LENGTH
 OF 46",HOWEVER,SEVERAL PANELS ARE LESS
 THAN 46". THE CALK-IN ANCHORS WILL NOT
 WORK IN THE HOLLOW BLOCK THAT IS HIGH
 LIGHTED ON THE PRODUCT APPROVAL. PLEASE
 CORRECT.
  
 10) SHEET A1.01 LISTS TOTAL A/C AREA AS
 1888 SQFT, HOWEVER, THE TOTAL FOR THE
 1ST AND 2ND FLOOR A/C AREAS THAT ARE
 LISTED TOTALS 1960 SQFT. THE ENERGY CALC
 LISTS CONDITIONED AREA AS 1888 SQFT.
 PLEASE CORRECT.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - THE FIXED GLASS TOMBSTONE (K) AND
 ROUND (N) WINDOWS
 - HORIZONTAL SLIDING WINDOWS (EXPIRED ON
 3-17-03)
 - GARAGE DOOR (DOES NOT MEET REQUIRED
 PRESSURES)
 - DOUBLE OUTSWING FRONT DOOR (DOES NOT
 MEET THE REQUIRED PRESSURES)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-31 Cont ID  
Sent By dpalmer Date 2003-10-31 Time 15:26 Rev Time 0.33
Received By dpalmer Date 2003-10-31 Time 15:26 Sent To  
Notes
2003-10-31 00:00:00REV FOR FAN SYMBOL ONLY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-17 Cont ID  
Sent By dpalmer Date 2003-09-17 Time 07:35 Rev Time 0.25
Received By dpalmer Date 2003-09-17 Time 07:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-10 Cont ID  
Sent By bstaples Date 2003-08-19 Time 09:27 Rev Time 0.50
Received By btrobaug Date 2003-06-10 Time 07:04 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-19 Cont ID  
Sent By bstaples Date 2003-08-19 Time 09:27 Rev Time 0.00
Received By bstaples Date 2003-08-19 Time 09:27 Sent To E
Notes
2003-08-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-27 Cont ID  
Sent By shernand Date 2003-05-27 Time 09:14 Rev Time 0.00
Received By shernand Date 2003-05-27 Time 09:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-01 Cont ID  
Sent By jleech Date 2003-06-21 Time 12:02 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-07-01 00:00:00OK PER H. MOSER 6-21-03

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-21 Cont ID  
Sent By btrobaug Date 2003-06-10 Time 08:04 Rev Time 0.25
Received By jleech Date 2003-06-21 Time 12:02 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-27 Cont ID  
Sent By shernand Date 2003-05-27 Time 09:14 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***