2003-06-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03051851 |
| ADD: 8853 S. SAN ANDROS |
| CONT: SIERRA CONST |
| TEL: (561)616-9686 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| THE TESING REPORT IS FOR ANDROS ISLES |
| PARCEL "E2" PLAT1.THE PARCEL IN QUESTION |
| IS "E2" PLAT2. |
| |
| 3) TABLE 600 ISSUE, GLASS BLOCK, PROVIDE |
| DOCUMENTATION FOR 1 HR RATING, 0-3' FROM |
| THE PROPERTY LINE. THIS IS NOT CONSIDER- |
| ED OPENING BUT WALL 1HR RATING. |
| |
| 4) PLANS INDICATE THEUSE OF STORM |
| SHUTTRS FOR WINDOWS AND SIDELITES BUT |
| NO STORM SHUTTER INFORMATION ATTACHED. |
| MISSING PRODUCT APPROVAL, KEY PLAN |
| AND INSTALLATION SCHEDULE, SEE ATTACH- |
| MENT FOR SAMPLE. |
| |
| 4) 1606.1.7 REQUIRED WIND DESIGN |
| INFORMATION, MISSING THE INTERNAL |
| PRESSURE COEFFICIENT. WITHOUT THIS IT |
| IS ONLY ASSUMED THAT IT IS A CLOSED |
| BUILDING. |
| CLOSED BUILDING+-.18 |
| PARTIAL ENCLOSED +-.55 |
| OPEN +-.0 |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |