2003-06-27 00:00:00 | BUILDING DENIED |
| |
| 1) SUBMIT SOIL BORING TEST REPORT AS |
| REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| THE ONE SUBMITTED IS FOR THE WRONG |
| PARCEL. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| FLOOD ZONE AN ELEVATION CERTIFICATE |
| WILL BE REQUIRED PRIOR TO C.O. |
| |
| 3) ONE HOUR FIRE RATED GLASS BLOCK IS |
| REQUIRED AT THE ZERO LOT LINE. FBC |
| TABLE600 REQUIRES ONE HOUR RATED WALL |
| WITH NOOPENINGS WITHIN 3' OF PROPERTY |
| LINE. GLASS BLOCK IS CONSIDER A WALL |
| COMPONENT AND NOT AN OPENING IF IT HAS |
| A MIN. ONE HOUR FIRE RATING. SUBMIT |
| MANUFACTURER'S SPECIFICATIONS & LISTING |
| INFORMATION FOR ONE HOUR RATED GLASS |
| BLOCK. |
| |
| 4) FBC 1606.1.7 REQUIRES SPECIFIC DESIGN |
| WINDLOAD INFORMATION ON THE PLANS. |
| PLEASE INDICATE THE INTERNAL PRESSURE |
| COEFFICENT ON S-3. |
| |
| 5) THE DOUBLE FRONT DOOR DOES NOT COMPLY |
| WITH EGRESS REQUIREMENTS. EXIT DOOR MUST |
| BE OF THE SIDE SWINGING TYPE WITH A MIN. |
| CLEAR OPENING OF 32". SEE FBC TABLE 1004 |
| AND SECTIONS 1003.2.3.1 AND 1012.1. |
| |
| 6) INDICATE THE LOCATIONS AND MATERIALS |
| FOR THE DRAFTSTOPPING THAT IS REQUIRED |
| AT THE FLOOR/CEILING ASSEMBLY. SEE FBC |
| 2305.2.2. |
| |
| 7) DETAIL 2 ON S-5 AND SECTION D-D ON |
| S-5 FOR THE GIRDER HANGER APPEAR TO BE |
| IN ERROR. THE CEILING HEIGHT (BOTTOM OF |
| GIRDER) IS 10' THE TOP OF THE BOND BEAM |
| IS AT 10'-8". THE TOP ANCHOR HOLE IS AT |
| 11',WHICH WILL BE ABOVE THE BOND BEAM. |
| SHEET S-1 INDICATES FILLED CELLS BELOW |
| THE BOND BEAM BUT NOT ABOVE IT. PLEASE |
| CORRECT. |
| |
| 8) FBC 1609.4 NO LONGER ALLOWS THE ONE- |
| THIRD INCREASE ON STEEL CALCULATIONS. |
| PLEASE REVISE THE CONNECTOR SCHEDULE ON |
| SHEET S-3. THE VALUES FOR THE SIMPSON |
| H-16, HETAL20, META16, AND USP RT24T ARE |
| INCORRECT. SEE THE 2003 USP AND 2002 |
| SIMPSON HIGH-WIND RESISTANT CONSTRUCTION |
| CATALOGS. |
| |
| 9)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - THE FIXED GLASS TOMBSTONE (K) AND |
| ROUND (N) WINDOWS. |
| - HORIZONTAL SLIDING WINDOW (EXPIRED ON |
| 3-17-03) |
| - GARAGE DOOR (THE REQUIRED NEGATIVE |
| PRESSURE LISTED ON THE PLANS EXCEEDS |
| THE DESIGN PRESSURE ON THE PRODUCT |
| APPROVAL) |
| - THE DOUBLE FRONT DOOR (THE REQUIRED |
| NEG. PRESSURE EXCEEDS THE PRODUCT |
| DESIGN PRESSURE) |
| |
| 10) SUBMIT AN INSTALLATION SCHEDULE AND |
| A KEY PLAN FOR THE STORM PANELS. SPECIFY |
| THE CONNECTION TYPE. NOTE: HOLLOW |
| CONCRETE BLOCK WITH POWERS CALK-IN |
| ANCHORS ARE NOT ALLOWED FOR SOME |
| CONNECTION TYPES. SEE SHEET 8 OF THE |
| PRODUCT APPROVAL. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |