Plan Review Details - Permit 03051786
Plan Review Stops For Permit 03051786
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-17 Cont ID  
Sent By sthyng Date 2003-09-17 Time 16:02 Rev Time 0.50
Received By sthyng Date 2003-09-17 Time 16:02 Sent To  
Notes
2003-09-17 00:00:00REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-10 Cont ID  
Sent By jwitmer Date 2003-07-10 Time 10:06 Rev Time 2.25
Received By jwitmer Date 2003-07-10 Time 10:06 Sent To  
Notes
2003-07-10 00:00:00********BUILDING PROVISO*******
 PERMIT: 03051786
 ADD: 2415 CURLEY CUT
 CONT: SIERRA
 TEL: (561)616-9686
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE DESIGNER OF RECORD TO PROVIDE THE
 CORRECTED WIND PRESSURES (FOR "B" ZONE)
 BEFORE WINDOW & DOOR BUCK INSPECTION.
  
 2) CORRECT A/C SQ FT AREA FOR ENERGY
 EFFICIENCY CODE ( SAME AS PLANS)
  
 3) STORM SHUTTERS:
 A) PROVIDE KEY PLAN TO CORRELATE TO THE
 SHUTTER SCHEDULE.
 B) BOTTOM FASTENER CAULK-IN, THE VALUE
 TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK!
 THIS FASTENER MAY NOT BE USED IN BLOCK,
 OR IF THIS IS USED IN FILLED CELL, THE
 CAULK-IN MUST BE IN 2500 PSI CONCRETE
 (FILLED CELL). OTHER ALTERNATIVE IS A
 DIFFERENT FASTENER FOR BLOCK.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By hmoser Date 2003-06-19 Time 19:15 Rev Time 2.00
Received By jwitmer Date 2003-07-09 Time 13:44 Sent To  
Notes
2003-07-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051786
 ADD: 2415 CURLEY CUT
 CONT: SIERRA CONST
 TEL: (561)616-9686
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY:FLOOR AREA, PLANS VS. ENERGY
 CALCULATIONS.
  
 2)R-3 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.R-3 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
 1012.1.7 REQUIRED EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WITHOUT THE USE
 OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR
 EFFORT. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE PROHIBITED. ALL HARD-
 WARE MUST BE DIRECT ACTING REQUIRING NO
 MORE THAN ONE OPERATION.
  
 3) ZERO LOT LINE, GLASS BLOCK: TABLE
 600, ZERO % OPENING WALL RATING 1HR
 FOR GLASS BLOCK, NOT 3/4 HR OPENING PRO-
 TECTIVES.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 (2) THE WIND IMPORTANCE FACTOR IS
 ACTUALLY A "B" DROPPING THE REQUIRED
 PRESSURES, SOME MODELS THIS EFFECT THE
 PRODUCT APPROVALS!!!!SEE DOOR# 6.
 (4) MISSING THE INTERNAL PRESSURE
 COEFFICIENT +- .18
  
 6)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 THE CONNECTOR SCHEDULE, VALUES HIGH
 FOR THE :
 SIMPSONHETAL 201365 NOT 1890
 SIMPSONLTS 16720 NOT775
  
 7) STORM SHUTTERS:
 A) KEY PLAN
 B) BOTTOM FASTENER CAULK-IN, THE VALUE
 TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK!
 THIS FASTENER MAY NOT BE USED IN BLOCK,
 OR IF THIS IS USED IN FILLED CELL, THE
 CAULK-IN MUST BE IN 2500 PSI CONCRETE
 (FILLED CELL). OTHER ALTERNATIVE IS A
 DIFFERENT FASTENER FOR BLOCK.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-31 Cont ID  
Sent By dpalmer Date 2003-10-31 Time 09:30 Rev Time 0.33
Received By dpalmer Date 2003-10-31 Time 09:30 Sent To  
Notes
2003-10-31 00:00:00REV FOR FAN SYMBOL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-30 Cont ID  
Sent By dpalmer Date 2003-09-30 Time 07:01 Rev Time 0.33
Received By dpalmer Date 2003-09-30 Time 07:01 Sent To  
Notes
2003-09-30 00:00:00*** NOTE REDLINED, ACTUAL INSTALLATION
 TO CORRELATE WITH LTR. NOT OPT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:44 Rev Time 0.25
Received By dpalmer Date 2003-09-16 Time 13:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-03 Cont ID  
Sent By bstaples Date 2003-08-19 Time 09:07 Rev Time 0.50
Received By btrobaug Date 2003-06-03 Time 14:48 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:44 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 16:44 Sent To E
Notes
2003-09-24 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-19 Cont ID  
Sent By bstaples Date 2003-08-19 Time 09:07 Rev Time 0.00
Received By bstaples Date 2003-08-19 Time 09:07 Sent To E
Notes
2003-08-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-23 Time 15:45 Rev Time 0.00
Received By shernand Date 2003-05-23 Time 15:44 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-19 Cont ID  
Sent By jleech Date 2003-06-17 Time 19:09 Rev Time 0.25
Received By hmoser Date 2003-06-19 Time 19:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-17 Cont ID  
Sent By btrobaug Date 2003-06-03 Time 15:30 Rev Time 0.25
Received By jleech Date 2003-06-17 Time 19:09 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-27 Cont ID  
Sent By shernand Date 2003-05-23 Time 15:45 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***