Plan Review Details - Permit 03051657
Plan Review Stops For Permit 03051657
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-04-09 Cont ID  
Sent By lmartine Date 2004-04-09 Time 15:42 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-04-06 Cont ID  
Sent By shill Date 2004-04-06 Time 16:25 Rev Time 1.00
Received By shill Date 2004-04-06 Time 16:13 Sent To  
Notes
2004-04-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #3.THE
 NEW WOOD BEAM ON SHEET A1 DATED 11/6/3
 REFERS TO STRUCTURALS WHICH ARE NOT
 ON THE PLAN.PLEASE PROVIDE A
 STRUCTURAL DETAIL.
  
 2.)SEE THE PREVIOUS LIST, ITEM #4.
 THE BRAILLE FLOOR DESIGNATION (AT THE
 ELEVATOR) IS TO BE ON BOTH JAMS AND TO
 COMPLY WITH FBC11-4.10.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-02-05 Cont ID  
Sent By shill Date 2004-02-05 Time 16:28 Rev Time 4.00
Received By shill Date 2004-02-05 Time 16:28 Sent To  
Notes
2004-02-05 00:00:00*****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEE OTHER PLAN REVIEWER'S COMMENTS
 IN REGARDS TO INFORMATION REQUIRED ON
 THE TITLE BLOCK.
  
 2.)SHEET A3 DOES NOT AGREE WITH SHEET
 S8 IN REGARDS TO THE ROOF TOP UNITS.
  
 3.)THE NEW WOOD BEAM ON SHEET A1
 DATED 11/6/03 REFERS TO STRUCTURALS
 WHICH ARE NOT ON THE PLAN.PROVIDE A
 STRUCTURAL DETAIL.
  
 4.)THE BRAILLE FLOOR DESIGNATION IS
 TO BE ON BOTH JAMBS AND TO COMPLY WITH
 FBC11-4.10.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-08-25 Cont ID  
Sent By hpiskura Date 2003-08-25 Time 10:52 Rev Time 0.00
Received By hpiskura Date 2003-08-25 Time 10:04 Sent To  
Notes
2003-08-25 00:00:00PROVISO:COMPLETE STRUCTURAL
 CALCULATIONS FOR THE SECOND FLOOR ARE
 REQUIRED BEFORE WORK IN THAT AREA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-08-13 Cont ID  
Sent By alange Date 2003-08-19 Time 09:48 Rev Time 0.00
Received By hpiskura Date 2003-08-13 Time 15:22 Sent To  
Notes
2003-08-13 00:00:00THE PLANS CAN HAVE ONLY ONE ENGINEER OF
 RECORD.THE REQUESTED STRUCTURAL
 CALCULATIONS FOR THE FLOOR LOADING
 ADDRESS ONLY A PORTION OF THE BUILDING.
  
 THE THOMAS J. TWOMEY, PE LETTER IS NOT
 SUFFICIENT FOR THE OTHER PORTION OF THE
 BUILDING.
  
 SEE CHAPTERS 61G15-27 AND 61G15-31 OF
 THE FLORIDA ADMINISTRATIVE CODE FOR
 PROCEDURES FOR THE ADOPTION OF ANOTHER
 ENGINEER'S WORK AND RESPONSIBILITY
 RULES COMMON TO ALL ENGINEERS IN THE
 AREA OF DELEGATED RESPONSIBILITY.
  
 THE 6/25/03 REQUEST FOR PERMIT
 VALUATIONJUSTSIFICATION HAS NOT BEEN
 PROVIDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-22 Cont ID  
Sent By hpiskura Date 2003-07-22 Time 10:45 Rev Time 0.00
Received By hpiskura Date 2003-08-13 Time 15:22 Sent To  
Notes
2003-07-22 00:00:00SHEET A2 DATED 7/1103 SHOWS A 3' WIDE
 LANDING ON THE MAIN STAIRS IN THE
 DIRECTION OF TRAVEL.FBC 1007.4.2
 REQUIRES A MINIMUM OF 4'.PLEASE
 REVISE AS NECESSARY.
  
 FBC 1007.5.7 REQUIRES HANDRAILS WITHIN
 30" OF ALL PORTIONS OF THE STAIRS
 REQUIRED FOR EGRESS.PLEASE REVISE AS
 NECESSARY.
  
 THE STRUCTURAL SHEETS ARE THE SAME,
 CONSEQUENTLY SO ARE THE PREVIOUS
 COMMENTS.THE LIST PROVIDED ON
 6/25/03 IS ATTACHED AGAIN.
  
 SHEET S1 DECLARES AN IMPORTANCE FACTOR
 OF 1.0.THIS BUILDING WILL HAVE >300
 PEOPLE IN ONE ROOM SO WILL BE A
 CATEGORY III, TABLE 1-1, ASCE 7-98 AND
 REQUIRES AN
 IMPORTANCE FACTOR OF 1.15, SEE TABLE
 6-1.
  
 THE PLANS MUST BE REVIEWED BY THE COUNTY
 FOR IMPACT FEES. AND THE PERMIT
 VALUATION ACCOUNTED FOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-25 Cont ID  
Sent By hpiskura Date 2003-06-25 Time 10:12 Rev Time 0.00
Received By hpiskura Date 2003-06-23 Time 13:17 Sent To  
Notes
2003-06-25 00:00:00SHEET EX-2 CALLS FOR THE REMOVAL OF A
 PORTION OF A BEARING WALL IN TWO PLACES.
 WHAT WILL BE SUBSTITUTED FOR IT?FBC
 104.2.
  
 PLEASE PROVIDE AN ENGINEERING ANALYSIS
 OF THE SECOND FLOOR CERTIFYING IT IS
 CAPABLE OF SUPPORTING 100 LB. LIVE
 LOADS.SEE FBC T-1604 AND 106.1.2.
  
 THE MAIN ENTRY STAIR SHOWN ON SHEET A1,
 SECTION 5/A4, AND ELSEWHERE IS REQUIRED
 TOBE ENCLOSED IN TWO HOUR FIRE RATED
 CONSTRUCTION.SEE FBC 1006.1.1, FBC
 1006.1.3 AND FBC 1010. THE OTHER TWO
 STAIRS MUST ALSO BE TWO HOUR FIRE RATED.
  
 THE AREA OF THE MEZZANINES SHOULD BE
 MEASURED AS GROSS AREA NOT NET.PLEASE
 REVISE AS NECESSARY.SEE FBCTABLE
 1003.1, NOTE #3 AND FBC 202 AREA, GROSS
 AND AREA, NET.
  
 THE FIRE SUPPRESSION SYSTEM
 INFORMATION,SPRINKLERS, IS REQUIRED BY
 FBC 104.3.1.1TO BE ON THE PERMIT PLANS.
 NOTE THAT ENTIRE BUILDING MUST HAVE
 FIRE SPRINKLER PROTECTION AS PROVIDED
 FOR IN FBC 903.7.2.4.
  
 SHEET A5, THE DOOR IN ROOM 205, MARTINI
 BAR, MUST SWING IN THE DIRECTION OF EXIT
 TRAVEL.FBC 1012.1.2.
  
 SHEET A7, DOORS SHOWN AS (E) REQUIRE
 PANIC HARDWARE AND CANNOT HAVE FLUSH
 LOCKING BOLTS AS NOTED IN THE SCHEDULE.
 SEE FBC1012.1.8 AND 1019.7.2.
  
 SHEET S1.THE DECLARED LIVE LOAD OF 60
 PSF FOR STORAGE IS NOT IN COMPLIANCE
 WITH FBC T-1604 (125 PSF FOR LIGHT
 STORAGE)ALSO, SHOW THE DESIGN LOAD FOR
 THE GUARD RAIL/WALL OF THE DJ BOOTHS.
 FBC 1608.2.2.
  
 SHEET S3, WHAT ARE THE DIMENSIONS OF
 FOOTING F1 FOR THE LIFT?
  
 SHEET S5. DETAIL C1, IS THIS AN EXISTING
 OR PROPOSED CONDITION?IF NEW,
 PROVIDE DESIGN INFORMATION SUCH AS
 CONNECTIONS AND BEARING AREAS.SECTION
 CC, AND DD, WHERE IS THE REINFORCING TO
 BE ACCOMPLISHED SHOWN?SEE FBC 104.2.
  
 SHEET S6, PLEASE PROVIDE A BETTER
 SPECIFICATION FOR THE "I BEAMS" IN THE
 NOMENCLATURE OF THE AISC.SEE FBC
 2203.1
  
 SHEET S6, PLEASE PROVIDE A DETAIL FOR
 THE ATTACHMENT/SUPPORT OF THE 6"
 CONCRETE SLAB TO THE EXISTING WALL AND
 A DETAIL FOR THE WOOD FLOOR JOISTS TO
 THE "I BEAM"FBC 104.2.
  
 SHEET S7 STUCTURAL PLAN 2ND FLOOR
 MEZZANINE, HAS VERY LITTLE STRUCTURAL
 INFORMATION FOR THE MEZZANINES.WHERE
 IS THE "EXISTING COLUMN" LOCATED THAT
 IS SHOWN IN THE DETAIL?WHAT SUPPORTS
 THE AREA THAT IS SHOWN AS "2X8 CEILING
 BELOW"?
  
 SHEET S8 STRUCTURAL PLAN - ROOF FRAMING.
 WHAT IS INTENDED TO BE SHOWN HERE?
  
 SHEET S9, SECTION A/S4.IS THAT
 SECTION 4/A4?WHAT WILL THE A/C
 SUPPORTS ATTACH TO AND HOW?FBC 104.2.
  
 SHEET S10.WHAT IS THE INTENDED DEPTH
 OF EMBEDMENT FOR THE VARIOUS ANCHORS
 SHOWN AND WHERE SPECIFICALLY DO THESE
 DETAILS APPLY?ARE THE EXISTING WALLS
 CONCRETE? PLEASE CLARIFY THE DESIGN.
  
 SHEET S11.IN THE TRANSVERSE SECTION
 WHICH SHOWS THE AUDIO-STORAGE HAVING
 NEW 2X8 CEILING JOISTS IN A DIFFERENT
 PLANE THEN THE EXISTING CEILING JOISTS.
 WILL THE TRUSS CHORD BE INTERRUPTED?
 WHAT DO THE NEW CEILING JOISTS BEAR ON?
  
 WHAT WILL SUPPORT THE NEW 2X12 FLOOR
 JOISTS?THE STAIRS AND LANDING?
  
 ARCH SECTION 4/A4 CALLS OUT NEW FLOOR
 TRUSSES AND THIS SECTION 2X12'S.
 PLEASE CLARIFY.
  
 SHEET S11.THE LONGITUDINAL SECTION
 MAKES REFERENCE TO RELOCATED TENSION
 CABLE STAYS.HOW IS THAT TO BE
 ACCOMPLISHED?IS THERE AN ENGINEERED
 CONNECTIONMETHOD? A PRESCRIBED TENSION?
 A SPECIFIC LOCATION FOR THE CABLE?
 PLEASE PROVIDE THE NECESSARY DETAILS.
  
 PLEASE PROVIDE STRUCTURAL DETAILS FOR
 THE DJ BOOTHS WHICH ARE SHOWN AS
 SUSPENDEDFROM ABOVE ON THE
 ARCHITECTURAL PLANS.
  
 S11.WHY ARE THE 2X6 CHANNELS ATTACHED
 TO THE BOTTOM CHORD OF THE TRUSS AT GRID
 LINE 2?
  
 THE ADDED AREA OF THE NEW MEZZANINES IS
 SUBJECT TO IMPACT FEES COLLECTED BY THE
 COUNTY.THE PERMIT PLANS MUST BE
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 THE DECLARED PERMIT VALUATION OF
 $130,000.00 APPEARS TOO LOW FOR THIS
 SCOPE OF WORK.PLEASE PROVIDE A COPY
 OF THE SIGNED CONTRACT AND A DETAILED
 ESTIMATE TAKEOFF, INCLUDING EXTENSIONS,
 TO JUSTIFY THE PRICE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-28 Cont ID  
Sent By jleahy Date 2004-04-28 Time 08:51 Rev Time 0.30
Received By jleahy Date 2004-04-28 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-26 Time 13:05 Rev Time 0.75
Received By btrobaug Date 2004-04-06 Time 12:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-30 Cont ID  
Sent By dpalmer Date 2004-01-30 Time 07:44 Rev Time 1.50
Received By dpalmer Date 2004-01-30 Time 07:44 Sent To  
Notes
2004-01-30 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 AS REQ'D UNDER FS 471.023 ON TITLE
 BLOCK. PER FAC 61G15-23.002
  
 2)NOTE: PLEASE CORRELATE AIC RATING
 SHOWN FOR MDP. RISER SHOWS A MIN OF
 40,000 AND MDP PANLE SHOWS @ 22,000??
 PLEASE CORRECT. 110.9
  
 3)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS AND PANEL SCHEDULES. EM LT AND EXT
 LTS DO NOT CORRELATE WITH PANEL SCHEDULE
 . ALL TO BE CIRCUITED PER 700.12E.
  
 4)NOTE: PLEASE CLARIFY REQ'D SIGN CIR-
 -CUIT PER 600.5
  
 5)NOTE: PLEASE SEE MISSING LICENSE #S
 FROM ARCH'S TITLE BLOCKS, ALSO REQ'D
 PER FS 481.219 AND FAC 61G1-16.004
 ARCH'S # AND FIRM LICENSE # REQ'D
 WEATHER OR NOT COMMENT IS MADE BY ANY
 OTHER REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-30 Cont ID  
Sent By btrobaug Date 2003-05-30 Time 17:10 Rev Time 1.00
Received By btrobaug Date 2003-05-30 Time 15:25 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-07-22 Cont ID  
Sent By hpiskura Date 2003-07-22 Time 11:07 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 14:54 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-08-22 Cont ID  
Sent By mcarsill Date 2003-08-22 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2003-08-22 Time 15:02 Sent To  
Notes
2003-08-22 00:00:00ON AUGUST 22, 2003, A FAX WAS RECEIVED
 BY BLAKE THORSON, TELEPHONE NUMBER
 305-531-1800. ON THE PAGES THAT WERE
 FAXED THE THREE EXIT DOORS THAT WERE
 SHOWN AT THE TOP OF MAIN ENTRY/EXIT
 STAIR WERE DELETED. THIS OFFICE WILL
 APPROVE THE PLANS PROVISO BUT NEW
 A PAGE WILL BE REQUIRED TO BE INSERTED
 IN THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-08-20 Cont ID  
Sent By mcarsill Date 2003-08-20 Time 11:36 Rev Time 0.00
Received By mcarsill Date 2003-08-20 Time 11:36 Sent To  
Notes
2003-08-20 00:00:001) A PORTABLE FIRE EXTINGUISHER APPEARS
 TO BE NEEDED ON THE SECOND FLOOR
 MEZZANINE FIRE PLAN.
  
 2) THE CLUBS FOYER, AREA 203 APPEARS
 TO BE A CONCERN. THE DRAWINGS REFLECT
 123 PERSONS LEAVING THE TECHNO CLUB
 AND 188 PERSONS LEAVING THE HIP HOP
 CLUB. THE CLUB'S FOYER IS APPROXIMATELY
 267 SQUARE FEET. HOW DOES QUEING
 EFFECT EXITING IN THIS LOCALE DUE
 TO ITS LIMITED SIZE AND RESTRICTIONS
 CAUSED BY THE DOORS. DOES THIS
 ARRANGEMENT PROVIDE FOR THE BEST
 POSSIBLE EXITING. REMEMBER IN A FIRE
 SITUATION, MOST PERSONS WILL ATTEMPT
 TO EXIT THE WAY THEY CAME IN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-07-24 Cont ID  
Sent By mcarsill Date 2003-07-24 Time 15:52 Rev Time 0.00
Received By mcarsill Date 2003-07-24 Time 15:52 Sent To  
Notes
2003-07-24 00:00:001) STAIR LANDING SHALL BE AT LEAST
 FOUR FEET WIDE BY USING THE EXCEPTION
 IN THE LIFE SAFETY CODE 7.2.2.3.2
  
 2) WHAT PREVENTS THE EXIT DOORS LOCATED
 ON THE NORTH SIDE FROM BEING BLOCKED.
 SIGNS OF THE BACKS OF THIS DOORS
 STATING "EXIT DOOR, DO NOT BLOCK.
  
 3) PROVIDE SURVEY TO CONFIRM EXIT
 DISCHARGE LOCATIONS. DOORS CANNOT
 OPEN ONTO PUBLIC RIGHT OF WAYS.
  
 4) ITEM # 12 OF YOUR RESPONSE IS
 INCORRECT. THE NEW ELEVATOR IS A SHAFT
 AND SHALL BE MARKED AS ONE.
  
 5) OCCUPANT LOAD SIGN IS REQUIRED TO
 BE POSTED AFTER CONFIRMATION WITH
 THE BUREAU OF FIRE PREVENTION.
  
 6) PLANS INDICATE A NEW FIRE ALARM
 CONTROL PANEL. PLEASE INDICATE WHERE
 FIRE ALARM DEVICES CAN BE LOCATED.
  
 7) PLEASE INDICATE WHERE INTERIOR
 FINISH CLASSIFICATION INFORMATION
 CAN BE LOCATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-26 Cont ID  
Sent By mcarsill Date 2003-06-26 Time 16:18 Rev Time 0.00
Received By mcarsill Date 2003-06-26 Time 16:18 Sent To  
Notes
2003-06-26 00:00:001) IS THERE ANY PLANNED WAITING IN THE
 CLUB FOYER.
  
 2) REFERENCE MADE TO NFPA 13R ON PAGE
 A-5. NFPA 13R IS NOT APPLICABLE TO THIS
 PROJECT.
  
 3) PLEASE VERIFY IF DOORS AT THE
 MARTINI BAR SWING IN THE RIGHT
 DIRECTION.
  
 4) PLEASE INDICATE TRAVEL DISTANCE
 TO REACH EXITS, DEAD-ENDS, ETC.
  
 5) PLEASE EXPLAIN 6" STEP AT VIP AREA.
  
 6) PLEASE VERIFY THAT ALL DOORS THAT
 ARE SUBJECT TO AN OCCUPANCY OF 100 OR
 MORE PERSONS ARE EQUIPPED WITH PANIC
 HARDWARE.
  
 7) NO FIRE SPRINKLER PLANS HAVE BEEN
 PROVIDED.
  
 8) HOW DO THE TV PLATFORMS WORK.
  
 9) PLEASE CLEARLY ILLUSTRATE EXIT
 DISCHARGE LOCATIONS.
  
 10) PLEASE INDICATE SEATING LOCATIONS
 FOR THE HANDICAPPED.
  
 11) TACTILE SIGNAGE REQUIRED AT STAIRS.
  
 12) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY IN 6" HIGH LETTERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-04-26 Time 13:05 Rev Time 0.00
Received By csiegber Date 2004-04-26 Time 13:05 Sent To E
Notes
2004-04-26 00:00:00TO DP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:55 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:55 Sent To  
Notes
2004-03-19 00:00:00TO COMM BD#52

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 11:49 Rev Time 0.00
Received By csiegber Date 2004-01-22 Time 11:49 Sent To  
Notes
2004-01-22 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-19 Cont ID  
Sent By alange Date 2003-08-19 Time 09:48 Rev Time 0.00
Received By alange Date 2003-08-19 Time 09:48 Sent To B
Notes
2003-08-19 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 08:02 Rev Time 0.00
Received By alange Date 2003-08-05 Time 08:02 Sent To  
Notes
2003-08-05 00:00:00TO COMM BD #53

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-14 Time 15:52 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 15:52 Sent To  
Notes
2003-07-14 00:00:00COMM BOARD #34

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 16:44 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 16:44 Sent To  
Notes
2003-06-26 00:00:00COMM BOARD #5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 16:09 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 16:09 Sent To  
Notes
2003-06-26 00:00:00COMM BOARD #35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-22 Cont ID  
Sent By shernand Date 2003-05-22 Time 09:30 Rev Time 0.00
Received By shernand Date 2003-05-22 Time 09:30 Sent To  
Notes
2003-05-22 00:00:00COMM BOARD #59

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-03-30 Cont ID  
Sent By pkrauss Date 2004-03-30 Time 13:21 Rev Time 0.40
Received By pkrauss Date 2004-03-30 Time 12:44 Sent To  
Notes
2004-03-30 00:00:00PLAN SHEET M-1 / ADDING 200 CFM EXHAUST
 FAN TO THE ELEV EQUIP RM. CONTROLLED BY
 T-STAT SET @ 90 DEGREE F

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-02-03 Cont ID  
Sent By pkrauss Date 2004-02-03 Time 08:35 Rev Time 0.35
Received By pkrauss Date 2004-02-03 Time 07:36 Sent To  
Notes
2004-02-03 00:00:00DENIED:
 REFERENCE FS 471 & FAC 61G15-23.002(2).
 SEE ALSO COMMENTS BY PLUBMING AND
 ELECTRICAL PLAN REVIEW.PLANS ARE OTHER
 WISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-20 Cont ID  
Sent By pkrauss Date 2003-06-20 Time 07:41 Rev Time 0.50
Received By pkrauss Date 2003-06-20 Time 07:38 Sent To  
Notes
2003-06-20 00:00:00PROVISO:
  
 DUCT SMOKE DETECTORS SHALL BE TIED TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 OR ACTIVATE A VISIBLE AND AUDIBLE
 SUPERVISORY SIGNAL AT A CONSTANTLY
 ATTENDED LOCATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2004-03-23 Cont ID  
Sent By kstevens Date 2004-03-23 Time 09:37 Rev Time 0.50
Received By kstevens Date 2004-03-23 Time 09:37 Sent To  
Notes
2004-04-07 00:00:00REVISION OK

Review Stop P PLUMBING
Rev No 5 Status F Date 2004-02-02 Cont ID  
Sent By kstevens Date 2004-02-02 Time 11:10 Rev Time 0.50
Received By kstevens Date 2004-02-02 Time 11:10 Sent To  
Notes
2004-02-02 00:00:00DENIED
 REFERENCE: FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-08-18 Cont ID  
Sent By kstevens Date 2003-08-18 Time 17:54 Rev Time 1.00
Received By kstevens Date 2003-08-18 Time 17:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-07-26 Cont ID  
Sent By kstevens Date 2003-07-26 Time 11:11 Rev Time 1.50
Received By kstevens Date 2003-07-26 Time 11:10 Sent To  
Notes
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
 FLORIDA STATUTES.
  
 A) MOST COMMENTS FROM ORIGINAL REVIEW
 HAVE NOT BEEN ADDRESSED. ORIGINAL NUMBER
 SHALL BE SHOWN FOR CLAIRITY.
 1) ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA ST. W.P.B. FOR RE-
 VIEW PRIOR TO RESUBMITTING TO THE CITY
 FOR PLAN REVIEW. SEC 101.4.7
 3) SHT A-9 SECTION 11-4.22.4 WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION TO
 THE STALL COMPLYING WITH 11-4.17.3, AT
 LEAST ONE STALL 36" WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND PARALLEL
 GRAB BARS COMPLYING WITH FIGURE 30(D) &
 11-4.26 SHALL BE PROVIDED.
 4) SHT P-1 MAIN HIP HOP BAR, NO SANT.
 DRAIN LINE SHOWN FOR HAND SINK. ALSO NO
 SANT. DRAIN LINE SHOWN FOR ICE MACHINES.
 PLEASE CLAIRFY. SECTION 104.2.1
 5) SHTS P-1 & P-3 CLEANOUT BY BAR #2
 SHALL CLEAN IN THE DIRECTION OF FLOW.
 SEE RED LINE CORRECTIONS ON FLOOR PLAN &
 SANITARY RISER DIAGRAM. SEC 708.3.3
 6) SHT P-2 NO WATER SHOWN FOR THE ICE
 MACHINES. PLEASE CLAIRFY. SEC 104.2.1
 7) SHT P-2 GENERAL PLUMBING NOTES:
 #11 CONDENSATE SHALL RUN SEPARATELY OUT
 OF THE BLDG AND TIE INTO STORM, A CATCH
 BASIN, OR A DRYWELL. UTILITY ORDINANCE
 90-125(5)
 #12 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SEC 604.9
 8) SHT P-4 ELECTRIC WATER HEATER DETAIL,
 EMERGENCY PAN REQUIRED SEC 504.8. THERM-
 AL EXPANSION CONTROL REQUIRED. SECTION
 607.3.2
 9) SHT P-4 WATER RISER ISOMETRIC, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 NEAR THE FIXTURES NOT IN THE CEILING AT
 THE TOP OF THE DROPS. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 10) SHT P-4 WATER HEATER FOR PRIVATE
 BATHROOM, T/P RELIEF VALVE SHALL DRAIN
 TO A FLOOR SINK OR A HUB DRAIN. FUNNEL
 DRAINS ARE NOT APPROVED. SEC'S 802.3 &
 802.3.2
 NEW COMMENTS.......
 11) ONLY ONE FULL SET OF PLANS HAS BEEN
 SUBMITTED. OTHER ROLL OF PLANS HAVE ONLY
 A2, A3, A4, A8, & A9 SHEETS. SUBMIT TWO
 COMPLETE SETS OF PLANS.
 12) SEE ATTACHED SHEET CONCERNING
 FLORIDA STATUTE 553.80(2)(B) DESIGN
 PROFESSIONAL DOCUMENTS. NEXT REVIEW WILL
 BE THE THIRD REVIEW. FIRST TWO HAVE THE
 SAME COMMENTS.
 ---------WHEN RESUBMITTING PLANS--------
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-09 Cont ID  
Sent By kstevens Date 2003-07-09 Time 09:07 Rev Time 0.50
Received By kstevens Date 2003-07-09 Time 09:07 Sent To  
Notes
2003-07-09 00:00:001ST RESUB - PLANS NOT COMPLETE - ORIG-
 INAL PERMIT NOT SUBMITTED WITH RESUB.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-14 Cont ID  
Sent By kstevens Date 2003-06-14 Time 15:47 Rev Time 1.75
Received By kstevens Date 2003-06-14 Time 15:47 Sent To  
Notes
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 ADMIN. CODE, CHAPTER
 1, & AMENDMENTS.
  
 1) ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA ST W.P.B. FOR REVIEW
 PRIOR TO RESUBMITTING TO THE CITY FOR
 PLAN REVIEW. SEC 101.4.7
 2) SHT A-3 BATHROOM #310, 11-4.1.3(11).
 OTHER TOILET ROOM PROVIDED FOR THE USE
 OF OCCUPANTS OF SPECIFIC SPACES (I.E. A
 PRIVATE TOILET FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. SUB-
 MIT DETAIL, SHOWING TURNING CIRCLE, AND
 BACKING GRAB BARS FOR TOILET AND SHOWER.
 SHOW CONTROL AREA FOR SHOWER AND CURB
 PER SECTIONS 11-4.16.4, 11-4.21.4, 11-4.
 21.5, AND 11-4.21.7.
 3) SHT A-9 SECTION 11-4.22.4 WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION TO
 THE STALL COMPLYING TO 11-4.17.3, AT
 LEAST ONE STALL 36" WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND PARALLEL
 GRAB BARS COMPLYING WITH FIGURE 30(D) &
 11-4.26 SHALL BE PROVIDED.
 4) SHT P-1 MAIN HIP HOP BAR, NO SANT.
 DRAIN LINE SHOWN FOR HAND SINK. ALSO NO
 SANT. DRAIN LINE SHOWN FOR ICE MACHINES.
 PLEASE CLAIRFY. SEC 104.2.1
 5) SHTS P-1 & P-3 CLEANOUT BY BAR #2
 SHALL CLEAN IN THE DIRECTION OF FLOW.
 SEE REDLINE CORRECTIONS ON FLOOR PLAN &
 SANITARY RISER DIAGRAM. SEC 708.3.3
 6) SHT P-2 NO WATER SHOWN FOR THE ICE
 MACHINES. PLEASE CLAIRFY. SEC 104.2.1
 7) SHT P-2 GENERAL PLUMBING NOTES:
 #11 CONDENSATE SHALL RUN SEPARATELY OUT
 OF THE BLDG AND TIE INTO STORM,A CATCH
 BASIN, OR A DRYWELL. UTILITY ORDINANCE
 90-125(5)
 #12 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SEC 604.9
 8) SHT P-4 ELECTRIC WATER HEATER DETAIL,
 EMERGENCY PAN REQUIRED SEC 504.8. THERM-
 AL EXPANSION CONTROL REQUIRED. SECTION
 607.3.2.
 9) SHT P-4 WATER RISER ISOMETRIC, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 NEAR THE FIXTURE NOT IN THE CEILING AT
 THE TOP OF THE DROPS. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 10) SHT P-4 WATER HEATER FOR PRIVATE
 BATHROOM, T/P RELIEF VALVE SHALL DRAIN
 TO A FLOOR SINK OR A HUB DRAIN. FUNNEL
 DRAINS ARE NOT APPROVED. SEC'S 802.3 &
 802.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-31 Cont ID  
Sent By mmclean Date 2003-07-17 Time 10:37 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-07-31 00:00:00APPROVED BY ANGELLA JONES-VANN