2003-06-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03051578 |
| ADD: 3648 TURTLE ISLAND COURT |
| CONT: M/I HOMES INC |
| TEL: (561)471-3440 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ACTION: DENIED |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| PROVIDE SOILS REPORT, WITH THE MINIMUM |
| SAFE BEARING VALUE. |
| |
| 3) SHEET 4 OF 6 INDICATES THE USE OF |
| ATTIC STORAGE WITHIN THE ROOF TRUSSSES, |
| NOTE THAT THE BOTTOM CHORD OF THE TRUSS |
| SHALL BE DESIGNED TO BEAR A MINIMUM OF |
| 30LBS PSF LIVE LOAD TABLE 1604.1 |
| |
| 4)1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| CIFIED IN THE MATERIALS SECTIONS OF THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| RE-EVALUATE TRUSS ANCHOR SCHEDULE. |
| |
| 5) PROVIDE ENGINEERING FOR BUTT GLASS |
| ASSEMBLIES PER 2001 FBC 2406.2. |
| |
| 6)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| STORM SHUTTER ANCHOR SCHEDULE VS DETAIL |
| SHEET. CONTRACTOR NEGLECTED TO INDICATE |
| WHAT CONNECTION TYPE WAS TO BE USED, |
| WITHOUT THIS INFORMATION THE SPACING IS |
| USLESS? |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |