Plan Review Details - Permit 03051572
Plan Review Stops For Permit 03051572
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-30 Cont ID  
Sent By rmcdouga Date 2003-06-30 Time 11:48 Rev Time 2.00
Received By rmcdouga Date 2003-06-30 Time 11:47 Sent To  
Notes
2003-06-30 00:00:00BUILDING PROVISO
  
 1) SUBMIT DRAWINGS FOR THE AMARR GARAGE
 DOOR WHICH HAVE THE MIAMI-DADE COUNTY
 PRODUCT CONTROL APPROVAL STAMP WITH NOA
 NUMBER AND APPROVAL DATE PRIOR TO
 INSTALLING DOOR.
  
 2) SUBMIT THE FINAL NOA FOR THE SINGLE-
 HUNG WINDOWS AND THE DRAWINGS WITH THE
 MIAMI-DADE APPROVAL STAMP PRIOR TO
 INSTALLING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-18 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:33 Rev Time 2.00
Received By rmcdouga Date 2003-06-17 Time 14:12 Sent To  
Notes
2003-06-17 00:00:00BUILDING DENIED
  
 1) A NEW NOTICE OF COMMENCEMENT WILL BE
 REQUIRED TO BE RECORDED AND SUBMITTED
 FOR THIS PERMIT. FLORIDA STATUTE 713.13
 REQUIRES THE WORK ON THE PROJECT TO
 START WITHIN 90 DAYS OF RECORDING.
  
 2) THE POSITIVE AND NEGATIVE PRESSURES
 FOR THE DOOR TO THE GUEST COTTAGE THAT
 WERE ADDED (DRAWN IN) ARE REQUIRED TO
 BE INITIALED AND DATED.
  
 3) THE PRODUCT APPROVAL FOR THE OVERHEAD
 GARAGE DOOR DOES NOT HAVE DESIGN
 PRESSURES CAPABLE OF WITHSTANDING THE
 PRESSURES INDICATED ON THE PLAN.
  
 4) THE PRODUCT APPROVAL SUBMITTED FOR
 THE EXTERIOR DOORS IS FOR GLAZED FRENCH
 DOORS, WHICH REQUIRE IMPACT PROTECTION.
 SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE SPECIFIC TYPES OF ANCHORS THAT WILL
 BE USED, SPACING ETC. INDICATE THE
 LENGTH AND EMBED DEPTH OF THE 1/2" LAG
 SCREWS SPECIFIED IN THE SHUTTER MOUNTING
 DETAIL ON SHEET 1 OF THE PLANS. THE
 ANCHOR SCHEDULE ON SHEET 6 OF THE STORM
 PANEL PRODUCT APPROVAL DRAWINGS REQUIRES
 1/4" DIAMETER X MIN. 3" LONG LAG SCREW
 WITH MIN. 2" EMBEDMENT.
  
 5) CLARIFY WHY THE PROJECT DESCRIPTION
 ON THE PERMIT APPLICATION WAS CHANGED
 FROM GUEST COTTAGE TO POOL CABANA. THE
 PLANS ARE FOR A GUEST COTTAGE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-06-16 Time 14:16 Rev Time 4.00
Received By rmcdouga Date 2003-05-30 Time 10:30 Sent To  
Notes
2003-05-30 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR WINDOWS
 - EXTERIOR DOORS
 - OVERHEAD GARAGE DOOR
  
 3) THE FBC 1606.1.4 REQUIRES GLAZED
 OPENINGS IN WINDBOURNE DEBRIS REGIONS TO
 BE IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERINGS.
 PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) SPECIFY THE INSULATION FOR THE WALLS
 AND ATTIC OF THE HABITABLE SPACE. FBC
 CHAPTER 13 REQUIRES THE COMPONENTS BEING
 REPLACED OR RETROFITTED TO COMPLY WITH
 ENERGY CODE.
  
 6) OPENINGS FROM A GARAGE DIRECTLY INTO
 A ROOM USED FOR SLEEPING PURPOSES IS NOT
 PERMITED PER FBC 411.2.8.
  
 7) INDICATE THE POSITIVE AND NEGATIVE
 DESIGN WIND PRESSURES FOR THE NEW DOOR
 THAT WAS DRAWN IN.
  
 8) ITEMS THAT WERE ADDED (DRAWN IN) TO
 THE PLANS ARE REQUIRED TO BY INITIALED
 AND DATED BY THE DESIGNER OF RECORD.
  
 9) INDICATE ON THE PLAN THAT ADEQUATE
 SUBSTRATE WILL BE PROVIDED FOR THE
 ATTACHMENT OF THE HURRICANE PANELS.
  
 10) REVIEW PLANS FOR SHEARWALL
 COMPLIANCE PER FBC 2313. SPECIFY THE
 NAIL SIZE AND SPACING FOR SHEAR WALL
 PANELS PER FBC 2310.4.
  
 11) IF WIRE MESH IS USED IN THE SLAB IT
 IS REQUIRED TO BE SUPPORTED ON APPROVED
 MATERIAL AT A MAXIMUM OF THREE FEET O.C.
 PER FBC 1909.3.
  
 12) THE NAIL SPACING FOR THE ROOF
 SHEATHING HAS 6" THROUGHOUT IN ONE NOTE
 AND 4"EDGES & 6" IN THE FIELD IN ANOTHER
 PLEASE CORRECT.
  
 13) SPECIFY THAT A 3"X3" WASHER IS
 REQUIRED ON THE 1/2" ANCHOR BOLTS.
  
 14) SPECIFY THE CONNECTOR THAT WILL BE
 USED TO ATTACH THE BOTTOM PLATE TO THE
 STUDS IN ORDER TO CREATE A CONTINOUS
 LOAD PATH FROM THE ROOF TO FOUNDATION
 PER FBC 1606.1.3.
  
 15) THE UPLIFT VALUE IN THE TRUSS ANCHOR
 SCHEDULE FOR THE (2) HTS-20 CONNECTORS
 IS INCORRECT. THE VALUE SHOULD BE 2900#
 (1450# EACH STRAP) PER 2003 SIMPSON
 CATALOG.
  
 16) NOTES UNDER WOOD FRAME CONSTRUCTION
 ON SHEET 1 SPECIFIES 8D COMMON OR HOT
 DIPPED GAL. NAILS AND NOTE ON SHEET 8
 CALLS FOR 8D RING SHANK NAILS FOR ROOF
 SHEATHING ATTACHMENT. PLEASE CLARIFY.
  
 17) PLEASE CLARIFY IF THE 3" SCREEN VENT
 AT THE SOFFIT IS CONTINOUS.
  
 18) SHEETS 2 THROUGH 7 OF THE DRAWINGS
 ARE MISSING. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-08-08 Cont ID  
Sent By btrobaug Date 2003-08-08 Time 12:06 Rev Time 0.50
Received By btrobaug Date 2003-08-08 Time 11:44 Sent To P
Notes
2003-08-08 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SEE NOTES FROM LAST REVIEW,NO
 COMMENTS WERE ADDRESSED.(ATTACHED).
  
 PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.
  
 THIS REVISION REMOVED THE REQUIRED
 RECEPTACLE FROM THE COUNTERTOP,IT MUST
 BE ADDED BACK TO CONFORM WITH
 210.52(C)(1).
  
 THE GARAGE MUST COMPLY WITH 210.52(G) &
 210.8.
  
 THERE MUST BE A RECEPTACLE IN THE
 BATHROOM PER 210.52(D).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-01 Cont ID  
Sent By alange Date 2003-07-28 Time 09:02 Rev Time 1.00
Received By btrobaug Date 2003-06-30 Time 17:45 Sent To P
Notes
2003-07-01 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 THE PLANS AND RESUBMIT FOR REVIEW PRIOR
 TO CALLING ANY ELECTRICAL INSPECTIONS.
  
 1} INDICATE CONDUIT AND WIRE TYPE AND
 SIZE FEEDING THE GARAGE.
  
 2} SHOW OCP ON MAIN PANEL SCHEDULE FOR
 GARAGE FEED.
  
 3} INDICATE DISCONNECTING MEANS PER 225.
 32 AND GROUNDING PER 250.32,FOR GARAGE
 FEED.
  
 4} THE RECEPTACLE ON THE COUNTER MUST
 COMPLY WITH 210.8(A)(7).GFI.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.LISTED WITH #14
 ON SCHEDULE.
  
 6} NOTE THAT THE HEAT LOAD IS LARGER
 THAN THE A/C LOAD AND MUST USED IN THE
 LOAD CALCULATION. PLEASE RECALCULATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-22 Time 09:39 Rev Time 0.50
Received By btrobaug Date 2003-05-23 Time 10:05 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-28 Cont ID  
Sent By alange Date 2003-07-28 Time 09:02 Rev Time 0.00
Received By alange Date 2003-07-28 Time 09:02 Sent To E
Notes
2003-07-28 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:33 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 16:33 Sent To B
Notes
2003-06-27 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-16 Cont ID  
Sent By shernand Date 2003-06-16 Time 14:16 Rev Time 0.00
Received By shernand Date 2003-06-16 Time 14:16 Sent To B
Notes
2003-06-16 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-22 Cont ID  
Sent By shernand Date 2003-05-22 Time 09:39 Rev Time 0.00
Received By shernand Date 2003-05-22 Time 09:39 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-21 Cont ID  
Sent By mmclean Date 2003-05-21 Time 16:50 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 09:52 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-08-13 Cont ID  
Sent By kstevens Date 2003-08-13 Time 14:30 Rev Time 0.50
Received By kstevens Date 2003-08-13 Time 14:30 Sent To  
Notes
2003-08-13 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) 61G15-23.002(2) INFORMATION REQUIRED
 ON EACH SHEET. SEE ATTACHED SHEET FOR
 THIS INFORMATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-03 Cont ID  
Sent By btrobaug Date 2003-08-08 Time 12:35 Rev Time 1.00
Received By kstevens Date 2003-07-03 Time 14:25 Sent To  
Notes
2003-07-03 00:00:00SANT. RISER DIAGRAM TO BE VOIDED PER
 ENGINEER AND CONTRACTOR. PLUMBING
 CONTRACTOR TO SUBMIT AT TIME OF APPLICAT
 ION

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 09:52 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***