2003-05-29 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03051518 |
| ADD: 641 34TH ST |
| CONT: NEWBOLD CONST |
| TEL: (561)254-0805 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) THE R-30 INSULATION IS 12" THICK, THE |
| PROPOSED ROOF TRUSSES ARE 2"X6", ADDI- |
| ITIONAL INFORMATION REQUIRED FOR HOW THE |
| INSULATION (R-30) WILL FIT? |
| |
| 2) INDICATE ON EITHER THE SURVEY THE |
| EXISTING CARPORT OR ON THE FLOOR PLAN |
| THE DISTANCE FROM THE PROPERTY LINE? |
| THE SURVEY AND THE EXISTING FLOOR PLAN |
| DO NOT MATCH? |
| |
| 3) THE PLAN INDICATES THAT THE LEDGER IS |
| TO BE ANCHORED TO THE EXISTING BUILDING |
| AT 2'-0" O.C., ARE THE STUDS IN THE |
| EXISTING DWELLING LAID OUT AT 24"O.C.? |
| |
| 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 5)1507.3.8. ASPHALT SHINGLES LOW |
| SLOPE ROOFING, UNDERLAYMENT APPLICATION |
| FOR ROOF SLOPES FROM 2:12 UP TO 4:12, |
| UNDERLAYMENT SHAL BE A MINIMUM OF TWO |
| LAYERS APPLIED AS FOLLOWS: |
| 1) STARTING AT THE EAVE, A 19-INCH |
| STRIP OF UNDERLAYMENT SHALL BE APPLIED |
| PARALLEL WITH THE EAVE AND FASTENED |
| SUFFICIENTLY TO STAY IN PLACE. |
| 2) STARTING AT THE EAVE, 36-INCH-WIDE |
| STRIPS OF UNDERLAYMENT FELT SHALL BE |
| APPLIED OVER LAPPING SUCCESSIVE SHEETS |
| 19 INCHES AND FASTENED SUFFICIENTLY TO |
| STAY IN PLACE. |
| |
| 6) 1403.1.6 IN ORDER TO PROVIDE FOR |
| INSPECTION FOR TERMITE INFESTATION, |
| CLEARENCE BETWEEN EXTERIOR WALL COVERING |
| AND FINAL EARTH GRADE ON THE EXTERIOR OF |
| A BUILDING SHALL NOT BE LESS THAN 6". |
| |
| 7)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |