Plan Review Details - Permit 03051398
Plan Review Stops For Permit 03051398
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-09 Cont ID  
Sent By jgomez Date 2003-07-09 Time 18:47 Rev Time 0.33
Received By jgomez Date 2003-07-09 Time 18:47 Sent To PC
Notes
2003-07-09 00:00:00REVISED TRUSS ANCHOR SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-06-18 Cont ID  
Sent By shernand Date 2003-06-26 Time 08:15 Rev Time 2.00
Received By jgomez Date 2003-06-16 Time 18:27 Sent To PC
Notes
2003-06-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-STORM SHUTTERS: ANCHORS TO BE 12"O.C
 MAXIMUM (NOT 12.5") IF EDGE DISTANCE
 IS 2". SEE ENGINEERED DRAWINGS.
 2-REVISE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T
 ALLOW THE STEEL STRESSS INCREASE TO
 BE USED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-06 Cont ID  
Sent By btrobaug Date 2003-11-06 Time 10:11 Rev Time 0.33
Received By btrobaug Date 2003-11-06 Time 10:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-29 Cont ID  
Sent By csiegber Date 2003-10-24 Time 09:23 Rev Time 0.50
Received By btrobaug Date 2003-05-29 Time 17:07 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-03 Time 14:17 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 14:17 Sent To M
Notes
2003-11-03 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 09:23 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 09:23 Sent To E
Notes
2003-10-24 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 08:15 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 08:15 Sent To B
Notes
2003-06-26 00:00:00JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-19 Time 17:02 Rev Time 0.00
Received By shernand Date 2003-05-19 Time 17:02 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-21 Cont ID  
Sent By pkrauss Date 2003-11-21 Time 07:45 Rev Time 0.25
Received By pkrauss Date 2003-11-21 Time 07:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-16 Cont ID  
Sent By csiegber Date 2003-11-03 Time 14:17 Rev Time 0.25
Received By pkrauss Date 2003-06-16 Time 08:05 Sent To B
Notes
2003-06-16 00:00:00MECHANICAL PERMIT 03051412

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-24 Cont ID  
Sent By kstevens Date 2003-05-24 Time 07:27 Rev Time 0.25
Received By kstevens Date 2003-05-24 Time 07:27 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-19 Time 17:02 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***