Plan Review Details - Permit 03051386
Plan Review Stops For Permit 03051386
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-07 Cont ID  
Sent By rbrown Date 2003-07-07 Time 14:14 Rev Time 0.00
Received By rbrown Date 2003-07-07 Time 14:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-01 Cont ID  
Sent By rbrown Date 2003-07-01 Time 09:54 Rev Time 0.00
Received By rbrown Date 2003-07-01 Time 09:54 Sent To  
Notes
2003-07-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/12/03:
  
 3) FBC 1606.1.7SHEET S2, STRUCTURAL
 NOTES, CODES AND STANDARDS #3.THE
 ADDITION OF WIND PRESSURES IS NOTED.
 THE STATED PRESSURES ARE ASSUMED TO BE
 APPLICABLE TO THE WALLS (FOR
 SPECIFICATION OF THE NEW FRENCH DOOR) AS
 THEY ARE TOO LOW TO BE APPLICABLE TO
 ROOF (AND ROOF OVERHANG) ZONES 2 & 3.
 ANNOTATE THE PLAN TO CLARIFY.
  
 7) FBC 1606COLUMN BASE ANCHORS.THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED
 AS POINTED OUT IN THE PREVIOUS REVIEW
 THE SIMPSON ABA44 COLUMN BASE ANCHORS DO
 NOT HAVE SUFFICIENT UPLIFT CAPACITY TO
 RESIST THE WIND UPLIFT ACTING ON THE
 PORCH ROOF.USING THE PORCH DIMENSIONS
 AND COLUMN SPACING NOW PROVIDED, THE
 555# UPLIFT CAPACITY GIVEN IN THE 2003
 SIMPSON CATALOGUE CAN WITHSTAND A WIND
 UPLIFT PRESSURE OF -37 PSF ACTING ON THE
 ROOF.THIS IS NOT SUFFICIENT TO ANCHOR
 THE ROOF, EVEN ALLOWING FOR THE
 ASSISTANCE OFFERED BY THE DEAD LOAD OF
 THE STRUCTURE.EITHER, JUSTIFY THE USE
 OF SIMPSON ABA44 ANCHORS BY STATING THE
 PORCH ROOF UPLIFT PRESSURE ON THE PLAN,
 OR SPECIFY AN ALTERNATIVE ANCHOR WITH
 SUFFICIENT UPLIFT CAPACITY.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-26 Time 16:36 Rev Time 0.00
Received By rbrown Date 2003-06-12 Time 15:46 Sent To E
Notes
2003-06-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED ALTERATIONS MAY REQUIRE
 PAYMENT OF IMPACT FEES.THE PROPOSALS
 SHOULD BE ASSESSED BY PALM BEACH COUNTY,
 THE PLANS STAMPED BY THEM AND A COPY OF
 THE RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT BEFORE A BUILDING PERMIT CAN
 BE ISSUED.
  
 3) FBC 1606.1.7SHEET S2, STRUCTURAL
 NOTES, CODES AND STANDARDS #1.IN
 ADDITION TO THE INFORMATION PROVIDED,
 THE PLANS SHALL ALSO STATE THE DESIGN
 WIND PRESSURES FOR SPECIFICATION OF THE
 ROOF COVERINGS AND NEW FRENCH DOOR.
  
 4) ROOF COVERING.THE SUBMITTAL OF A
 PRODUCT APPROVAL IS NOTED.THE PLANS
 DO NOT STATE WHAT TYPE OF ROOF COVERING
 IS TO BE PROVIDED.AMEND THE PLANS TO
 SPECIFY THE TYPE OF ROOF SYSTEM/MATERIAL
 OVER THE NEW FRONT PORCH AND THE
 EXISTING REAR PORCH (FOLLOWING REMOVAL
 THE SECOND FLOOR 'BONUS ROOM')
  
 5) FBC 1005.4.1REMOVAL OF EXISTING
 EXTERIOR DOOR.ANNOTATE THE BEDROOMS ON
 THE PLAN.IS THE EXTERIOR DOOR BEING
 REMOVED FROM A BEDROOM, AND IF SO DO THE
 REMAINING WINDOWS COMPLY WITH THE
 REQUIREMENTS FOR EMERGENCY EGRESS
 OPENINGS?ANNOTATE THE PLANS
 ACCORDINGLY.
  
 6) FBC 2304.2.5SHEET S3, SOUTH
 ELEVATION, PATCHING OF WOOD SIDING AFTER
 REMOVAL OF THE EXISTING EXTERIOR DOOR.
 THE WOOD SIDING SHALL BE AT LEAST 6"
 CLEAR OF THE GROUND.
  
 7) THE PLANS SHALL STATE THE DIMENSIONS
 (AS "NOT TO EXCEED.." IF NECESSARY) FOR
 THE NEW FRONT PORCH.WHAT IS THE
 SPACING OF THE COLUMNS?FROM THE
 SIMPSON CATALOGUE, THE ABA44 COLUMN BASE
 ANCHORS MAY HAVE INSUFFICIENT UPLIFT
 CAPACITY.CHECK AFTER ESTABLISHING THE
 PORCH DIMENSIONS.
  
 8) FBC 1804.1.3 AND FBC 1606.1.3
 SHEETS S2, PORCH SECTION.THE DOWELLED
 EXTENSION TO THE EXISTING PORCH SLAB IS
 SHOWN TO BE SUPPORTING THE NEW PORCH
 COLUMNS.THE COLUMNS SHALL BE
 ANCHORED TO A FOUNDATION CAPABLE OF
 RESISTING WIND-INDUCED UPLIFT.ALSO THE
 BOTTOM OF FOUNDATIONS SHALL EXTEND NO
 LESS THAN 12" BELOW FINISHED GRADE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-06-13 Cont ID  
Sent By rbrown Date 2003-06-12 Time 16:59 Rev Time 0.33
Received By btrobaug Date 2003-06-13 Time 16:09 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-07 Cont ID  
Sent By rbrown Date 2003-07-07 Time 10:18 Rev Time 0.00
Received By rbrown Date 2003-07-07 Time 10:17 Sent To  
Notes
2003-07-07 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 16:36 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 16:36 Sent To B
Notes
2003-06-26 00:00:00RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-19 Cont ID  
Sent By sgraham Date 2003-05-21 Time 11:04 Rev Time 0.00
Received By shernand Date 2003-05-19 Time 09:12 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-18 Cont ID  
Sent By kstevens Date 2003-06-14 Time 06:10 Rev Time 0.10
Received By pkrauss Date 2003-06-18 Time 12:34 Sent To  
Notes
2003-06-18 00:00:00NO MECHANICAL PLANS OR INFORMATION
 SUBMITTED FOR REVIEW.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-06-14 Cont ID  
Sent By btrobaug Date 2003-06-13 Time 16:17 Rev Time 0.25
Received By kstevens Date 2003-06-14 Time 06:07 Sent To M
Notes
2003-06-14 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 2 Status P Date 2003-05-21 Cont ID  
Sent By sgraham Date 2003-05-21 Time 11:04 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-19 Time 09:12 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-19 00:00:00DENIED, NEED SURVEY SHOWING DEMO &
 PORCH ADDITION